4demerits
CHARLOTTE COUNTRY CLUB - COMP POOL
2465 MECKLENBURG AVE, Charlotte, NC 28205
Seasonal Swimming Pool · NC permit/State ID 2060501582
Latest result4 demerits
Last inspectedApr 15, 2026
Inspections on record4
On record sinceApr 26, 2023
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Apr 26, 2023Lower is betterApr 15, 2026
Inspections & violations
Apr 15, 2026 4 demerits · 2 violations
Inspector comments: Paddock drain covers - installed May 2022. Provide yearly documentation for recertification of drains after 5/1/2032. Screws due 5/1/2030.
PERMIT RESTRICTION: 1) FLOW METER SHALL REMAIN OPERABLE. FLOW MUST BE MAINTAINED WITH RANGE OF 500 - 900 GPM TO MEET TURNOVER AND FLOW RESTRICTION OF 6" RETURN LINE. 2) SIGNAGE REQUIRED INSIDE KITCHEN TO INDICATE NO GLASS ON POOL DECK. 3) DOUBLE GATE WITH REMOVABLE CENTER POST IS APPROVED. CENTER POST MUST REMAIN SECURELY LOCKED IN PLACE AT ALL TIMES WHEN THE COMPLEX IS OPEN.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Observed 5 bags of sodium bicarbonate stored directly on the floor in the chemical storage room.
Keep all non-waterproof containers of chemicals stored off of the floor.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(l) Provide toilet paper and dispensers in restrooms.
Observed no toilet paper available in the unisex restroom.
Keep all restrooms stocked with toilet paper.
.2526(j) Provide soap and soap dispenser, no glass, at each sink.
Observed glass container full of mouthwash stored at the handsink in the women's restroom.
CPO removed glass container of mouthwash.
Apr 17, 2025 4 demerits · 1 violation
Inspector comments: FILTRATION MAIN DRAINS PADDOCK. Recertification required May 1, 2032. Screws required May 1 2030th. Permit restrictions. 1. Flow meter shall remain operable. Flow must be maintained within range of 500 to 900 GPM to meet turnover and flow restriction of 6 inch return line. 2. Signage required inside kitchen to indicate no glass on pool deck. 3. Double gate with removable center post is approved. Center post must remain securely locked in place at all times when the complex is open.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Observed pool personnel have installed Vertical tent style boards with depths on them on the side of the pool.
Apr 9, 2024 4 demerits · 1 violation
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching.
Observed gate near clubhouse not self-latching.
Gate was repaired during inspection and is now self-closing.
Apr 26, 2023 10 demerits · 2 violations
Inspector comments: David Johnson present during inspection.
#2 · Water quality: disinfectant residual provided by −6
Observed CL at .5 corrected to 3.0 during inspection.
.2535(4) Maintain chlorine at least 1.0 ppm.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed pool furniture within 8' of pool deck. Corrected during inspection.
.2522(a) Provide 8 ft of clear walking space around the pool at all times (>1600 sq. ft).
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “CHARLOTTE COUNTRY CLUB - COMP POOL” or State ID 2060501582). Inspection type (routine vs. follow-up) is not published in the county's data.