18demerits
1001 TYVOLA
2155 ESTABLISHMENT WY, Charlotte, NC 28217
Seasonal Swimming Pool · NC permit/State ID 2060501593
Latest result18 demerits
Last inspectedApr 10, 2026
Inspections on record5
On record sinceJun 9, 2023
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jun 9, 2023Lower is betterApr 10, 2026
Inspections & violations
Apr 10, 2026 18 demerits · 4 violations
Inspector comments: PDSC form and permit restrictions verified to be in compliance during today’s inspection: Pump must remain at 92 gpm to meet turnover, maintain flow meter operable if pump not set at 3450 rpm.
All critical items corrected during today’s inspection with CPO Darryl McCain.
Not permitted for night swimming. Permit issued.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8.
Observed pH at 7.1. CDI - pH increased to 7.7 by CPO during the inspection.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair.
Observed loose skimmer plate in pool. CDI - CPO corrected during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Provide no openings in fence and/or gate greater than 4".
Observed opening measuring over 4.5” between vertices in corner area of fencing near pool at 1/2 ft depth. CDI - CPO corrected during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(b) Provide at least 5 ft of clear walking space around the pool at all times.
Observed lounge chairs placed around edge of pool. CDI - Chairs were removed to allow proper clearance on pool deck.
Apr 1, 2025 14 demerits · 4 violations
Inspector comments: Inspection completed with CPO, Deion Padilla
All permit compliance items corrected during inspection.
CPO log records begin today.
Pump is locked to 3450rpm / 90gph.
Permit issued
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs.
Observed one missing weir plate on the shallow end of the pool.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching.
Observed two of the three gates not self-closing or self-latching. CPO was able to repair one of the gates but was unable to fix the second gate. This gate was permanently locked until it can be repaired. Two self closing, self latching gates are present.
.2528(a) Pool fence shall be at least 48" in height measured from outside of barrier.
Observed 43-46” fence in areas where rocks and mulch have been piled up by landscapers. CPO was able to remove the mulch and rocks to keep the fence at 48”.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering.
.2530(c) Provide "Adults should not swim alone." in 1" lettering.
Observed missing signage. CPO was able to obtain a new sign from a pool supply store for permitting.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526(h) Shower(s) shall be provided.
Observed no working shower during inspection due to the water being turned off.
May 21, 2024 6 demerits · 1 violation
Inspector comments: Verified that pump was set at 3450 RPM
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. - pH was at 7.0, increased to 7.2 during the inspection.
Aug 1, 2023 8 demerits · 2 violations
Inspector comments: Intent issued for pool gate and record keeping.
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
Pool checks are required to be completed by a CPO on all days that the pool is open.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no cyanuric acid or total alkalinity test recorded.
Observed no daily checks for main drains.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
Intent to suspend
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed one gate not self closing self latching. Gate not properly functioning is on the right side.
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing.
Intent to suspend
Jun 9, 2023 8 demerits · 2 violations
Inspector comments: Onsite visit to pool with Mason Garrett, Hot Springs Pools and Doug Tetting, CPO, for return construction and operating permit inspection.
All items from previous visit corrected. Phone still has the wrong address listed with 911. Correct address with phone company who will automatically update in 911 system. Given 2 weeks to correct or permit will be suspended. When 911 is dialed, address should list as 2155 Establishment Way.
Construction final passed. Holds released in system.
Pump was not set at 32450 RPM during inspection. Ensure pump set to meet permit restrictions.
Pentair Intelliflo VSF, 011056 drain cover installed with (2) VGBA 2017 Hayward WG1031BHF2 drain covers. EQ lines capped on underside/plugged in skimmer.
Permit Restriction Pump must remain set at 92 gpm to meet turnover. Flow meter must remain operable if pump not set at 3450 RPM.
Please note a follow-up inspection will occur within 30 days of permit issuance today, June 9th.
Max Depth 5 ft.; Pool Width 42 ft.; Rope Length 50 ft.
EHS left computer at house and did not have onsite for write-up. No signature since not onsite for write-up.
Note: NC and SC pool rules signs on the deck. Ensure NC pool rules signage stays onsite.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No main drain checks recorded. Ensure daily record keeping for main drain checks in log book. Address by follow-up inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Back gate located next to large planter dragging. Corrected during the inspection.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “1001 TYVOLA” or State ID 2060501593). Inspection type (routine vs. follow-up) is not published in the county's data.