SPOKE AT TYVOLA STATION

5746 WESTPARK DRIVE, Charlotte, NC 28217
Seasonal Swimming Pool · NC permit/State ID 2060501632
Latest result24 demerits
Last inspectedMay 13, 2026
Inspections on record2
On record sinceMay 20, 2025

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01530 May 20, 2025: 30May 13, 2026: 24
May 20, 2025Lower is betterMay 13, 2026

Inspections & violations

May 13, 2026 24 demerits · 6 violations
Inspector comments: Information on PDSC form verified during today’s inspection. All critical items corrected during today’s inspection with CPO. Not permitted for night swimming. Permit issued.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed two ring buoy with throw ropes tied, one of which measures under the required throw rope length of 30 ft. CDI - CPO removed ring buoy with throw rope < 30 ft as only 1 is required.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed sharp edge on coping and offset > 1/2” in other areas of coping around edge of pool. CDI - CPO repaired all areas.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed incorrect callback number posted at pool phone. CDI - Phone number verified and CPO posted correct pool phone number.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed inoperable flow meter. .2518(f) Observed vacuum port uncovered (located at 4 ft next to ladder).
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Observed old spa equipment in equipment room, no clearance around piping. Chemicals in equipment room. Pool built ‘84. .2533(d) Pump room floor shall be kept dry and free of standing water. Observed water pooling on floor in the pump room due to water leak from pool fill valve and flow meter.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. Observed no air gap at back wash. Pool built ‘84.

View this inspection on the county portal ›

May 20, 2025 30 demerits · 8 violations
Inspector comments: Could not issue permit due to following permit items: PDSC information (plug skimmer equalizers on wall), emergency phone (correct information and callback), pole for body hook at least 12 ft and non-telescoping. Contact main line at 980-314-1620 to pay $100 revisit fee, pool ID 501632. Once revisit fee has been paid and all permit items are in compliance. Contact Marie Daley at 704-507-6806 for additional inspection. Pool must remain closed with signage posted until permitted by the Health department. No Night Swimming Pool not heated
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Récords missing main drain check, weekly total alkalinity and cyanuric acid. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Educated staff on how to check these items. *Permit item
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
PDSC has been updated and indicated skimmer equalizer lines have been plugged per state recommendations (on wall and in skimmer). At time of inspection old, expired SDX retro covers still on wall. Plug on wall per state recommendation. Dummy covers are allowed, if plugged underneath and indicated on PDSC form. .2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7. .2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions. *Permit item
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Body hook with telescoping pole. .2530(a) Provide at least 12 ft. long pole with body hook securely attached. .2530(a) Pole for body hook must be non-telescoping, non-adjustable, and non-collapsible. *Permit item
#22 · Premises: emergency telephone provided −6
Emergency phone address incorrect (should have 5746 Westpark Dr, which is address from Polaris of clubhouse, pool does not have own address). When dialed back and connected, phone rings busy. Callback number not posted at time of visit. .2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone. .2530(f) Emergency phone shall remain operable. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. *Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Spa equipment in equipment room, no clearance around piping. Chemicals in equipment room. Pool built 84. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at back wash. Pool built 84. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Restrooms have been renovated. Ensure backing on mirrors. .2526(k) Provide shatterproof mirrors.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No floor drains in restrooms. Restrooms remodeled, but original construction did not have drains. .2526(c) Floor drains shall be provided in restrooms.

View this inspection on the county portal ›