Apr 16, 2026 12 demerits · 3 violations
Inspector comments: Inspection conducted with CPO Ray Cruz. Concrete deck with added expansion joints within the 6 feet walkway around the pool hold water. Decking needs to be sloped to drains and not hold water. Recommend caulking so it doesn’t hold water or so people don’t stub their toes. Far floor returns on sunshelf don’t appear to be working. Ensure all returns are working properly. Permit issued with the following conditions No Night Swimming Flow meter must remain operation and be between 113 GPM for minimum turnover and 138 GPM for restriction of the suction piping. Paper permit will be on our website https://eh.mecknc.gov/ in 3-5 business days for your records.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No place on log sheet for main drain checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Corrected.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
From construction, needed to add 1/2 ft - 4 ft depth markers at both sunshelves. Observed depth markers on pool deck but not pool wall. .2523(a) Provide depth markers on pool walls and pool deck at both ends of the pool. - Will follow up with facility to correct.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter at 80 GPM with pump at 2350 RPM. Needs at least 113 GPM for minimum turnover. .2518(b) The water circulation system shall circulate and filter the entire volume of the pool 4 times in 24 hours. - Corrected to 118 GPM at 3350 RPM.