6demerits
STONE GROVE AT WHITEHALL - SPA
7700 STONEGROVE LN, Charlotte, NC 28273
Seasonal Spa · NC permit/State ID 2060520170
Latest result6 demerits
Last inspectedJun 12, 2026
Inspections on record2
On record sinceApr 1, 2026
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Apr 1, 2026Lower is betterJun 12, 2026
Inspections & violations
Jun 12, 2026 6 demerits · 2 violations
Inspector comments: Inspection conducted with CPO, Chris Gundacker. Permit issued.
Permit restriction: filtration flow meter must remain operable with flow at 87 to 98 GPM to meet turnover and flow restriction of filter.
-Field verification conducted; no interlock/autochlorinator used
-Spa is to remain unheated due to timer malfunction. Heating unit outside (in front of pump room) is not operational and shall remain unused. Permitted for unheated spa only
-Equalizer plugs have been installed in both skimmers
**Inspection conducted 04/28/26, resubmitted 06/12/26 to correct status code**
#14 · Pool maintenance: spa timer working properly −4
14.2537(b) Spa times shall not exceed 15 minutes without manual resetting.
Observed spa jets still running after 15 minutes.
Corrected- EHS notes spa heater is not operational and not used. Spa must remain unheated at all times.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water.
Observed 1/5inch of standing water nears pumps at pump room back wall. EHS verified source of leak is not pump or filtration equipment; water seeps in from outside. Adding an additional floor drain near pumps is advised.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Observed open bag of granulated chlorine on floor in pump room. CPO advised to bring chlorinated off floor and provide waterproof buckets for storage of opened chemical bags, or ensure they remain closed and off the floor.
Apr 1, 2026 14 demerits · 4 violations
Inspector comments: CPO instructed to reach out for re-inspection once noncompliant items are resolved.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7.
Observed both equalizers in skimmer baskets without plugs. According to PDSC form, establishment should have both equalizers lines disabled. CPO should ensure properly fitted plugs on both lines.
#14 · Pool maintenance: spa timer working properly −4
.2537(b) Spa times shall not exceed 15 minutes without manual resetting.
Observed timer not shutting off jets after 15 minutes. Repair so that jets do not run for longer than 15 minutes with each cycle.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water.
Observed leak at water heater for spa causing standing water about 1/2 inch in back of pump room. Remove water and repair leak.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
.2518(d) Piping and valves shall be labeled with color codes or labels.
Observed pipes to spa not directionally labeled. EHS advises PIC to correct ahead of re-inspection.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “STONE GROVE AT WHITEHALL - SPA” or State ID 2060520170). Inspection type (routine vs. follow-up) is not published in the county's data.