6demerits
JEWISH COMMUNITY CENTER - INDOOR
5007 PROVIDENCE RD, Charlotte, NC 28226
Year-Round Swimming Pool · NC permit/State ID 2060530025
Latest result6 demerits
Last inspectedJul 23, 2026
Inspections on record27
On record sinceDec 5, 2013
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Dec 5, 2013Lower is betterJul 23, 2026
Inspections & violations
Jul 23, 2026 6 demerits · 2 violations
Inspector comments: 22) Emergency phone callback rang to voicemail then staff who could not see emergency call made or location. Tested again and could see emergency call out with no location of where emergency call was made from.
Pool is life guarded and has emergency system, due to other safety protocols in place and emergency phone operable, allowing until Wed 7/29 to ensure emergency calls are routed correctly at callback in case of emergency. Failure to correct will warrant permit action.
Rule for reference:
.2530 A telephone capable of directly dialing 911 or other emergency notification system shall be provided and
accessible to all pool users. Effective April 1, 2005 the telephone shall be permanently affixed to a location inside
the pool enclosure or outside the enclosure within 75 feet of a bather entrance. The telephone shall be visible from
within the pool enclosure or a sign shall be posted indicating the location of the emergency telephone. A sign with
legible letters shall be posted at the telephone providing dialing instructions, address of the pool location and the
telephone number. Where the telephone does not directly access 911, the emergency notification system shall:
(1) Provide 24 hour monitoring of all incoming calls by a telecommunicator who answers only
emergency calls;
(2) Be capable of routing calls to the local 911 telecommunicator via the 911 dedicated emergency
trunk line; and
(3) Electronically transfer Automatic Number Identification and Automatic Locator Identification for
the emergency telephone at the pool to the Enhanced 911 system for all calls routed to 911.
Inspection with Brent Miller
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door onto pool deck from main entry not latching at time of inspection.
.2528(a) Ground level doors shall be self-closing, self-latching or self-closing and child protected by audible alarm. Adjusted to self-close, self-latch. Corrected.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water over 110 F in shower.
.2526(i) Water at showers and in restrooms shall not exceed 110 F.
Mar 25, 2026 8 demerits · 2 violations
Inspector comments: Inspection completed with Brent Miller present.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed door leading from men’s locker room to pool deck not self-latching. CDI- repaired and self-latching.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter non operational.
Sep 25, 2025 4 demerits · 1 violation
Inspector comments: Inspection completed with Brent Miller present.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter non operational.
Mar 13, 2025 4 demerits · 1 violation
Inspector comments: Inspection completed with Bob Peterson present.
Note: observed body hook without metal screw, only plastic pushpin. Add metal screw to ensure hook is securely affixed to pole.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter non operational.
Jul 24, 2024 4 demerits · 1 violation
Inspector comments: Inspection completed with Brent Miller present.
Observed some floor depth markers covered by slip resistant rug. Relocate rugs so depth markers are clearly visible.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed non operational flow meter.
Mar 20, 2024 0 demerits · 0 violations
Inspector comments: Inspection completed with Bob Peterson and Brent Miller present.
No violations noted during inspection.
No violations were recorded for this inspection.
Nov 29, 2023 0 demerits · 0 violations
Inspector comments: Inspection completed with Josh Steinberger, Bob Peterson, and Brent Miller present.
No violations were recorded for this inspection.
Apr 26, 2023 4 demerits · 1 violation
Inspector comments: Inspection completed with Josh Steinberger present.
Note: observed runner rugs partially covering some depth markers on pool deck. Ensure depth markers are clearly visible.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter non-operational.
Nov 9, 2022 8 demerits · 2 violations
Inspector comments: Inspection completed with Josh Steinberger present.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed one door leading onto pool deck from women’s locker room self-closing but not self-latching. CDI- door repaired.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(e) Provide a spare basket for pump. Observed no spare pump basket.
.2518(g) Keep flow meter operational. Observed flow meter non-functional.
Mar 8, 2022 4 demerits · 1 violation
Inspector comments: Inspection completed with Josh Steinberger present. No signature due to COVID.
Observed one area in pool deck where deck drain is cracked. Repair.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed non-operational flow meter.
.2518(e) Provide a spare basket for pump. Observed no spare pump basket on site.
Dec 15, 2021 8 demerits · 2 violations
Inspector comments: Inspection completed with Josh Steinberger present. No signature due to COVID.
NOTE: When measuring pool perimeter for trip hazards (5 feet of clearance required for indoor pools), measurements were taken beginning at waters edge (gutter of pool included in measurement).
Observed pump replaced with new EQK-500 pump. PDSC form was emailed to E. Freese for approval during inspection. E. Freese notified Josh Steinberger that an electrical permit and inspection needs to be completed on the grounding wire and electrical work as soon as possible.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed one door leading onto pool deck self-closing but not self-latching. CDI- door repaired.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(e) Provide a spare basket for pump. Observed no spare pump basket.
Mar 31, 2021 6 demerits · 1 violation
Inspector comments: Inspection completed with Josh Steinberger and Brent Miller present. No signature due to COVID-19.
Observed grounding wire not affixed to pump motor assembly. The wire was reattached by end of inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed emergency phone unable to connect to 911. CDI- phone was repaired and was fully functional by end of inspection.
Aug 12, 2020 0 demerits · 0 violations
Inspector comments: Inspection completed with Josh Steinberger on-site. No signature due to COVID-19.
No violations were recorded for this inspection.
Jan 28, 2020 0 demerits · 0 violations
Inspector comments: Pool operator Josh Steinberger provided documentation today that indicates drain covers have been verified and are in good repair.
No violations were recorded for this inspection.
Nov 5, 2019 8 demerits · 2 violations
Inspector comments: ITS for doors.
5) Temperature reading for indoor pool 102 degrees F multiple days. Maximum temperature for heated pool is 90 degrees F. Ensure records are accurate or appropriate action noted in records.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Women's locker room door onto pool deck not self-latching and door out of locker room open. Door onto pool deck from main entry propped open at time of visit.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Door onto pool deck adjusted.
*30 Day Intent to Suspend for doors. Contact Marie Daley at 704-507-6806 when corrected to lift ITS.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some pool equipment within 5' of pool. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Operator moved items. Corrected.
Mar 5, 2019 16 demerits · 5 violations
Inspector comments: ITS for doors self-closing, self-latching or audible alarm, 5' clearance and flow meter. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
Unable to verify chlorinator at time of inspection due to lack of staff available (swim lessons starting at time of inspection).
PADDOCK DRAIN COVERS - REQUIRED SCREW REPLACEMENT EVERY 7 YEARS AND RE-CERTIFICATION OF
DRAINS EVERY 10 YEARS FROM DATE OF INSTALL. Installed April 2009, provide required documentation for permit 2019.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door from hallway into pool area, door from women's locker room onto pool deck and back door to outside from pool deck, not self-closing, self-latching at time of inspection. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
**30 Day Intent to Suspend (ITS) item. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Benches and belongings within 2 feet of pool at time of inspection. Swim lessons in session at time of inspection. If items are in use and in pool, items may be present, but otherwise need adqequate storage space and seating arranged to maintain 5' clear walking space. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times.
**30 Day ITS item
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck at time of inspection.
.2518(g) Keep flow meter operational.
**30 Day ITS item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some chemicals stored in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms over 110 degrees F at time of inspection.
.2626(i) Water in restrooms shall not exceed 110 F.
Nov 14, 2018 6 demerits · 2 violations
Inspector comments: ITS for doors.
**Note: PADDOCK DRAIN COVERS - REQUIRED SCREW REPLACEMENT EVERY 7 YEARS AND RE-CERTIFICATION OF DRAINS EVERY 10 YEARS FROM DATE OF INSTALL. Installed April 2009, required documentation for permit 2019.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Back hallway door not self-latching.
**30 Day Intent to Suspend item. Contact Marie Daley at 704-507-6806 to lift when corrected.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2626(i) Water in restrooms shall not exceed 110 F.
Mar 6, 2018 16 demerits · 4 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Some depth and 'No Diving' markers covered by mats. Ensure markers are visible at all times. Mats moved back to display depth markers and 'No Diving'. Corrected.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Fixtures holding main drain into place rusted. Keep in good repair and stainless steel. Pool built prior to '93 and did not warrent Intent to Suspend due to lack of severity.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Underwater lights not operable in pool. Pool lighting is sufficient to illuminate all parts of the pool, the water, the depth markers, signs, entrances, restrooms, safety equipment and the required deck area and walkways, at time of inspection.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not working at time of inspection. Keep operational. Operator corrected. (Pool built prior to '93)
Nov 28, 2017 32 demerits · 9 violations
Inspector comments: 15 - Push buttons on body hook. Could not remove but replace with screw by 30 day return visits to assure secured.
Intent to Suspend issued for temperature logs, depth markers on pool walls, and doors on to deck self-latching, self-closing.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Temperature logs not maintained. Maintain daily temperature logs. Intent to Suspend issued.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
27 ft between depth markers on wall at shallow near pump room. 32.5 ft between wall depth markers at deep end. Assure depth markers maintained 25 ft apart or less in 4" lettering. Depth marker sticker worn off at 6 ft 3 in. Replace to maintain 4" height requirement and contrasting. Intent to Suspend issued for both items.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder handrail loose. Keep tightened.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Fixtures holding one main drain into place rusted. Keep fixtures in good repair. All fixtures shall be stainless steel in pool.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One door on to deck not latching when closing. Restroom doors and double doors not self-closing, self-latching. Repair to self-close, self-latch or provide audible alarm at entry points. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed deck near pump room with rust and some build-up on deck. Keep clean and in good repair.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Lights not operable in pool. For night swimming, lights shall be operational or main drains must be clearly visible at all times including all areas of pool deck.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Filter leaking and flow meter not operational. Repair filter (was being repaired during inspection) and keep flow meter operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Light burnt out and forced ventilation not operable in chemical storage room. Repair light and maintain continous forced ventilation in chemical storage room.
May 17, 2017 4 demerits · 1 violation
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
OBSERVED FLOW METER TO BE STUCK. CORRECT FLOW METER.
Dec 8, 2016 4 demerits · 1 violation
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck. Repair it.
Mar 16, 2016 0 demerits · 0 violations
No violations were recorded for this inspection.
Nov 18, 2015 6 demerits · 2 violations
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck. Repair it.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed hot water to be 114F at least. hot water shall be no hotter than 110F.
Mar 17, 2015 4 demerits · 2 violations
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed leak in fluid line in pump room wetting the floor. Fix the leak.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed hot water to be 121F in bathroom fixtures. Hot water shall be 110F or less.
Dec 3, 2014 10 demerits · 3 violations
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed a hose used to fill the pool to be laying across the deck. The deck must be clear of obstruction withing a five foot space around the pool edge. -CDI- The hose was removed.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter to be stuck. Ensure that flow meter is working properly.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed hot water to be at least 113F in bathroom fixtures. Hot water shall be no more than 110F.
Feb 17, 2014 0 demerits · 0 violations
No violations were recorded for this inspection.
Dec 5, 2013 4 demerits · 1 violation
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
FLOW METER STUCK
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “JEWISH COMMUNITY CENTER - INDOOR” or State ID 2060530025). Inspection type (routine vs. follow-up) is not published in the county's data.