16demerits
YMCA CHILDRESS KLEIN
301 S COLLEGE ST, ONE WELLS FARGO STE 200, Charlotte, NC 28202
Year-Round Swimming Pool · NC permit/State ID 2060530038
Latest result16 demerits
Last inspectedFeb 11, 2025
Inspections on record21
On record sinceSep 30, 2013
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Sep 30, 2013Lower is betterFeb 11, 2025
Inspections & violations
Feb 11, 2025 16 demerits · 4 violations
Inspector comments: Intent to Suspend issued for:
.2537 - secure pool perimeter drains and replace rusted screws where needed
.2518 - repair flow meter
A return visit will be made on 2/18 for drain covers. If completed prior to 2/18, please let me know.
Brandon Cheek present during the inspection.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
New drain covers installed. Left side, lower left missing Aquastar star and appears to be installed backwards. Not flush to wall. Used body hook to ensure still secure. Drain cover shall be flush. Verify installed per mfg. instructions. Does not appear to look like 24xxx with horizontals and verticals. Given one week to correct or permit will be suspended. If not installed backwards, missing piece of product and should be replaced.
Some screws appear to be loose in both sets of drain covers. Tighten screws per mfg. instructions. Given one week to correct or permit will be suspended.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Multiple drains around pool with either missing screws and not secure or rusted screws. Replace screws and secure where needed. Intent to Suspend issued.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. No permit restriction. Keep flow meter operable. Was not able to verify flow of system. Intent to Suspend issued.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One sink slow draining in women's restroom. Keep all fixtures in good repair.
Nov 4, 2024 20 demerits · 5 violations
Inspector comments: Intent to Suspend issued for:
.2535 - replace expired thiosulfate; maintain and provide weekly and daily record keeping as rule requires.
.2535 - automated feeder shall detect flow and turn off with loss of flow - be able to demonstrate.
Given until Friday, mid-day, to fix callback on phone or permit will be suspended. Please notify when complete otherwise site visit will be made on Friday, late morning.
Main drains expire on 1/20/2025. A new PDSC is required for approval by expiration or permit will be suspended.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Thiosulfate reagent expired in test kit. Provide new reagent.
Could not view records for October or previous months. Swimming pool manager out on leave. Provide records for at least September/October showing daily record keeping for chlorine, pH and main drain checks. Weekly record keeping for total alkalinity.
Intent to suspend issued the above items.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Some rust around drain fittings at coping/overflows. Keep fixture fittings in good repair.
#22 · Premises: emergency telephone provided −6
Dialing instructions did not match actual instructions for phone. Corrected during the inspection. Signage read dial 9-911. 9 was marked through on signage to reflect actual dialing instructions.
Phone not ringing back when phone number is dialed. Number does go to phone. Phone answered when picked up. Phone shall audibly ring when dialed. Repair by Friday, mid-day, November 8th.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Could not verify automated feeder. No pool manager available. Feeder shall detect flow and turn off with no flow from pump. Intent to Suspend issued.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >114 F. Maintain at 110 F or below.
Mar 4, 2024 24 demerits · 7 violations
Inspector comments: Lindsay Ellis present during the inspection.
Intent to Suspend issued for the following:
.2535 - could not verify chlorinator. Chlorinator must be set up to detect flow. Demonstration required. Calibrate chlorinator/acid feeder. Feeder reading at 7.92 while reading at 7.5.
.2535 - maintain accurate record keeping and ensure weekly testing for alkalinity.
.2518 - verify door near pump room self-closes, self-latches from men's locker room.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Alkalinity only recorded once in last month. Record alkalinity weekly.
Pool pH recorded at 7.0. If pH is below 7.2, pool shall be closed. Tested pH at 7.5. Ensure accurate record keeping.
Intent to Suspend issued.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some build-up on vinyl liner near window side of pool on coping. Keep pool floor clean.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Could not verify door located near pump room to self-close, self-latch. All doors shall self-close, self-latch. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck drains around pool coping starting to rust. Continue to monitor. Replace as needed. Escutcheon plates around ladder handrails beginning to rust. Continue to monitor. Replace as needed.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Could not verify automated feeder. Chlorinator must be set up to detect flow. Demonstration required. Calibrate chlorinator/acid feeder. Feeder reading at 7.92 while reading at 7.5. Intent to Suspend issued.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >113 F. Maintain at 110 F or below.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No air gap at backwash line to pit. Provide air gap.
Nov 27, 2023 20 demerits · 6 violations
Inspector comments: 6 - One screw loose on main drains on top right of drain looking down from lifeguard stand. Tighten screw. Given 30 days to correct. Will verify on return visit for ITS items.
Intent to suspend issued for:
.2535 - maintain weekly record keeping for total alkalinity
.2523 - provide FT at 4 ft. signage on pool perimeter wall clearly visible
.2528 - repair leak at heater to ensure floor kept dry
Dave Thompson present during the inspection. Was not present until end of inspection.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Could not view total alkalinity records. Operator not present during inspection. Not recorded in daily logs kept on pool deck. Provide record keeping for total alkalinity. Intent to Suspend issued.
Thiosulfate reagent expired, used for Total Alkalinity. Provide new test reagent.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
FT on 4 ft on either side of pool, around pool perimeter not visible from other side of swimming pool. Depth markers shall be clearly visible. FT written in with permanent marker in very small lettering. Provide FT on either side on wall depth marker so visible and contrasting. Intent to Suspend issued.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Some rust on drain covers around pool perimeter. Fixtures shall be stainless, free of rust and in good repair. Some rust on metal between coping and pool deck near lifeguard stand. Eliminate rust.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Heater leaking. Repair leak on heater. Substantial amount of water on pump room floor due to leak. Intent to Suspend issued.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Floor in pump room wet due to leak at heater. Repair leak. Keep pump room floor dry.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >115 F. Maintain at 110 F or below.
Feb 6, 2023 14 demerits · 4 violations
Inspector comments: 30 - No check valve apparent on fill line. Check valve shall be per rule .2512. Original construction.
Marissa Cheek present during the inspection.
Intent to Suspend issued for the following.
.2535 - maintain weekly record keeping in logs for cyanuric acid and total alkalinity
.2535 - automated feeder reading at 7.9 with pH at 7.3. Calibrate feeder so accurately reading.
.2537 - some rust on drain fixtures around pool perimeter. Eliminate rust/keep in good repair.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Stabilizer used in tablets for AccuTab. Maintain weekly cya readings. Record weekly alkalinity readings. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Left handrail at ladder handrails on right side of pool loose. Tighten and keep in good repair.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Some rust on drain covers around pool perimeter. Fixtures shall be stainless, free of rust and in good repair. Intent to Suspend issued.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Automated feeder reading pH of 7.9. Pool pH at 7.3. Calibrate feeder. Intent to Suspend issued.
Dec 5, 2022 20 demerits · 5 violations
Inspector comments: Michele Evers present during the pool inspection. Permit suspended for the emergency phone.
Once phone is corrected, contact Katie Rudisill at 704-309-5494 to re-open the pool. The pool shall remain closed until a return visit has been made.
Note: Chlorinator verified during inspection.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Depth markers on perimeter walls do not match or are not directly back from pool deck depth markers. For wall depth markers that can not be located on the pool wall but are located on the pool perimeter wall, the depth marker shall match the deck depth marker and be located directly back on the perimeter wall from the deck depth marker. ITS item.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Doors from men's and women's locker rooms on to pool deck do not self-latch. Repair doors to self-close, self-latch. ITS items.
#22 · Premises: emergency telephone provided −6
Phone not operable. No dial tone. Repair phone so that phone dials 911. 911 shall have the correct address and phone number for the pool. Phone shall audibly ring back. Immediate Suspension issued.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
No spare pump basket for pump. Provide spare pump basket. ITS item.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in locker rooms >115F. Maintain at 110 F or below.
Feb 24, 2022 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Mirrors in restrooms at sink area not verified as shatterproof.
.2526(k) Provide shatterproof mirrors.
Feb 19, 2020 8 demerits · 3 violations
Inspector comments: 911 does not identify pool phone as Suite 200. Repeat Item. If re-occurance, will result in suspension of permit. Given 30 days to correct address with 911. If completed prior to 30 days, please notify Katie at 704-309-5494.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Missing some main drain checks. Record daily.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
Note: Some days with chlorine at 0 ppm and no pool notes for closure and no corrective action (2/13 and 2/12). Ensure pool is closed to public if chlorine is less than 1.0 ppm.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder handrail loose near lifeguard stand.
.2521 Install ladders per manufacturer instructions.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Mirrors in restrooms at sink area not verified as shatterproof. Water in women's locker room >110 F.
.2526(k) Provide shatterproof mirrors.
.2526(i) Water in restrooms shall not exceed 110 F.
Dec 18, 2019 12 demerits · 4 violations
Inspector comments: 23 - Chlorinator/muriatic acid feeder verified to detect flow at time of inspection.
25 - Box of bicarb stored below but not directly under muriatic acid. Store chemicals as to not to present a hazard.
Note: Pool drains to expire in February 2020. Permit will be suspended if not replaced by expiration date. Permit will not be issued in 2020 until new drains installed and new PDSC form submitted and approved.
Intent to Suspend issued for signage visibility and door self-closing, self-latching from locker room.
Emergency pool phone does not identify suite with 911. Address with 911 so that phone identifies location (Suite 200) when 911 is contacted. Given 30 days to address or permit will be suspended.
Note: Follow-up on Cryptosporidium treatment. Spoke with Daniela Zambrano who stated that the pool did not close to the public. Facility made decision not to close pool to public. The pool was brought up to 10 ppm for 3 to 4 hours then brought back down to lower levels for opening. Per CDC requirements, treatment for Crypto shall be at least 10 ppm for 25 1/2 hrs. Recommend that pool treats per CDC requirements. Provided document with treatment requirements in email at time of inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder handrail loose near lifeguard stand.
.2521 Install ladders per manufacturer instructions.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door from women's locker room not self-latching. Repair to self-latch, self-close. Intent to Suspend issued.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
#18 · Premises: lifeguards present or warning signs posted −4
Warning signage blocked by changing areas. Move signage so visible upon entry to pool from locker room areas. Intent to Supend issued.
.2530(c) All pool signage shall be visible upon entrance to the pool and permanently affixed.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Water in women's restroom >112 F.
.2526(i) Water in restrooms shall not exceed 110 F.
Damaged handicap showerhead in women's restrooms.
.2526(m) Keep restrooms and fixtures clean and in good repair.
Mens could not be viewed at time of inspection due to occupancy.
Jan 31, 2019 22 demerits · 7 violations
Inspector comments: Intent to suspend issued for self-latching door, drain cover, and chemical storage.
Inspection completed by Sarah Coppa.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Ladder closest to the lifeguard chair is loose. Repair needed.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Drain cover not secure on gutter of right side on pool. Repair needed. Intent to suspend.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Door to stair well is not self-latching. Repair door to self-latch. Intent to suspend issued.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Emergency phone not functioning. Temporary phone placed on cardio floor within 75 feet of bather entrance. Contact Katie Wilson once phone repaired to verify phone is corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Liquid chemicals stored above dry chemicals in pump room. Intent to suspend.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap. No air gap at backwash line to pit.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2626(i) Water in restrooms shall not exceed 110 F. Water temperature at restroom handsink >110 F.
Nov 20, 2018 20 demerits · 6 violations
Inspector comments: 25 - Ventilation could not be verified in pump room. Piece of red flag tape was limp which is typically used to show flow of ventilation in pump room. Assure continuous forced ventilation.
Note - Main signage for pool rules located near lifeguard stand and not clearly visible upon entry to pool. Recommend placing Pool Rules sign closer to main entry points.
Intent to Suspend issued for depth marker, test kit and door self-closing.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Test kit in need of replacement. Intent to Suspend issued.
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some algea on pool floor. Keep pool floor clean and in good repair.
.2537(14) Keep pool surface and pool floor free of debris.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
4 ft. depth marker blocked by handicap lift. Intent to Suspend issued.
.2523 Depth markers shall be 4" in height and of contrasting color no greater than 25 ft. apart and visible to patron.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Back door on to pool deck not self-closing. Repair to self-close, self-latch. Intent to Suspend issued.
.2537(b) All gates and doors shall be self-closing, self-latching.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >110 F.
.2626(i) Water in restrooms shall not exceed 110 F.
Mirrors could not be verified as shatterproof.
.2626(k) Provide shatterproof mirrors.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No air gap at backwash line to pit.
.2512 Provide air gap for backwash line. No cross connection.
Apr 23, 2018 10 demerits · 3 violations
Inspector comments: #5) Periodic visits will be made to check on daily and weekly records. If found to be out of compliance, permit action may be initiated.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide weekly recordings for cyanuric acid and total alkalinity weekly. Total alkalinity not being recorded on weekly basis.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Some rust on ladder handrails. Keep in good repair.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Flow meter observed to not be operational.
Nov 27, 2017 26 demerits · 8 violations
Inspector comments: 2 - Chlorine noted as below 1.0 ppm at openings on some days. Assure chlorine is maintained at least 1.0 ppm while pool is open to the public.
23 - Chlorinator not verified during inspection. Liquid chlorinator. Assure chlorinator can detect flow and turns off when no flow of water. Head CPO not at site today.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Alkalinity not recorded weekly. Record weekly and maintain log books accessible. Intent to Suspend issued.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some algea build-up begining on pool floors and walls. Keep clean.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Some rust on ladder handrails. Keep in good repair.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Some drain covers loose at coping around the pool (specifically at 3 1/2 ft to left of door entrance). Assure all fixtures secure and in good repair.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Front doors into pool not self-closing, self-latching. All doors on to pool deck shall be self-closing, self-latching. Intent to Suspend issued.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operational. Keep operational.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash line to pit. Provide air gap above pit.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Water >112 F in restrooms and shower head holder damaged in one shower stall. Maintain water at 110 F or below and repair holder.
Feb 13, 2017 12 demerits · 4 violations
Inspector comments: 15 - General Comment: Some damage to lifeguard tubes. Replace where needed.
22 - General Comment: Some static on emergency phone. 911 must be clearly audible. Still audible. Replace when needed.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some standing water on pool deck; mildew in caulking around perimeter of the pool especially by ladders. Keep clean and free of standing water.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Keep operational.
General Comment: Acid feeder could not be verified. CPO on staff was required to stay on deck due to Lifeguard being sick. On next inspection, verify that acid feeder turns off when pump turns off.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash line to pit. Provide air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Some mildew in tiling in showers. Keep clean.
Water in restrooms >115 F. Maintain at 110 F or below.
Nov 28, 2016 14 demerits · 5 violations
Inspector comments: 16 - General Comment: Doors on to pool deck are not self-closing, self-latching. Attendant located outside of the doors at the fitness desk. Attendant must be present at all times and lifeguard must also be present in order for doors to remain as is.
22 - General Comment: New emergency phone signage. Recommend making larger so that public can see from across the pool.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Some days missing dates. Could not verify records daily due to lack of dating. Observed a couple days without main drain checks. Record daily.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Some ladders loose. Keep tight and in good repair.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Keep operational.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash line to pit. Provide air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Water in restrooms >115 F. Maintain at 110 F or below.
Jun 21, 2016 24 demerits · 7 violations
Inspector comments: 16 - General Comment: Door on to pool deck not self-closing. Lifeguard present on deck at all times and facing door to monitor. Repair door to self-closing, self-latching or provide lifeguard AND attendent at all times.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Some days missing main drain checks. Assure drains are checked daily and recorded.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
PDSC form indicates WAV24xxx covers when 24xxx covers installed. Resubmit PDSC form within one week or permit will be suspended. Covers approved with pump installed. No suction hazard.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders with rust. Keep in good repair.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Some drains on coping area with rust. Keep in good repair.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some mildew around edge of pool on caulking. Keep clean.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash line over pit. Provide air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Water in restrooms >114 F. Maintain at 110 F or below.
Dec 22, 2015 34 demerits · 9 violations
Inspector comments: 22 - General Comment - Emergency phone with static. Replace by next inspection. Note: Renovation in pump room. Pool size - 82,000 gallon. Turnover required 227 gpm. EQ500 pump with max flow of 400 gpm. Filter replaced in pump room with (3) TR100c rated at 98 gpm. At design flow, pump is at approx. 250 gpm. Filters can handle flow of pump.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Alkalinity not recorded in week prior. Record weekly.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some shipping paint on overflow grates. Keep in good repair.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
One wall depth marker blocked. Keep visible at all times.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Body hook not secured to pool and hook on collapsable pole. Corrected during inspection to secured and 12 foot non-collapsable.
#22 · Premises: emergency telephone provided −6
Posted emergency phone number not correct. New phone line at pool. Corrected during inspection.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Keep operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No ventilation in pump room. Provide cross or forced ventilation in pump room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash line to pit. Provide air gap over bit to prevent cross contamination.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Water in restrooms >115 F. Maintain at 110 F or below.
Feb 11, 2015 8 demerits · 3 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some floor tile and step ladder tiles missing. Replace.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No ventilation in pump room. Provide forced continuous or cross ventilation.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Water >118 F in restrooms. Maintain at 110 F or below.
One inoperable toilet and dusty ceiling vent in women's. Keep clean and in good repair.
Nov 19, 2014 18 demerits · 6 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Main drain checks and alkalinity not recorded regularly. Record main drains daily and alkalinity weekly.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some tiles missing on pool floor. Replace.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Few ladder handrails loose. Tighten.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No ventilation in pump room. Provide cross or continuous forced ventilation.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Water >120 F in restrooms. Maintain at 110 F or below.
Jan 22, 2014 8 demerits · 3 violations
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck. Keep operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed no ventilation in pump room. Provide cross or continuous forced ventilation.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed water >118 F. Maintain at 110 F or below.
Sep 30, 2013 10 demerits · 4 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed one ladder handrail loose. Keep in good repair.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck. Keep operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed no ventilation in pump room. Provide continuous forced ventilation or cross ventilation.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed water >120 F in restrooms. Maintain at 110 F or below. Observed battery dead in one paper towel dispenser in women's. Keep operational.