10demerits
EMBASSY SUITES HOTEL
4800 S TRYON STREET, Charlotte, NC 28217
Year-Round Swimming Pool · NC permit/State ID 2060530043
Latest result10 demerits
Last inspectedSep 16, 2026
Inspections on record24
On record sinceOct 9, 2013
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Oct 9, 2013Lower is betterSep 16, 2026
Inspections & violations
Sep 16, 2026 10 demerits · 4 violations
Inspector comments: Inspection conducted with PIC Cortez. INTENT TO SUSPEND issued today. Facility has 30 days to bring ITS item into compliance. Please contact EHS Rusi Woo at 704-430-7960 once repaired.
Night swimming previously approved.
PERMIT RESTRICTION: FLOW METER MUST REMAIN OPERABLE. FLOW SHALL NOT EXCEED 100 GPM DUE TO DRAIN COVER FLOW RESTRICTION. SUCTION HAZARD. 2 HP MOTOR ON 1.5 HP PUMP.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions.
Observed one ladder missing an endcap. Observed other ladder missing both endcaps.
CPO replaced all missing endcaps during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
.2537(3) There shall be no loose coping.
Observed multiple loose coping, damaged/cracked tiles, and offsets greater than half inch on pool deck.
INTENT TO SUSPEND ITEM.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Observed chemicals stored in pump room. Pool built in 1989.
#27 · Equipment room: filter backwash discharged through an air gap −2
.2513(b) Filter backwash shall be discharged through an air gap.
Observed no air gap at backwash. Pool discharges through pipe under equipment. Pool built in 1989.
Jan 27, 2026 12 demerits · 4 violations
Inspector comments: Conducted inspection with CPO Otto. Pool remains in good standing and on A status.
EHS Devon recommends replacing audible alarm for back door leading to walled off courtyard area.
Permit Restriction: Flow meter must remain operable. Flow shall not exceed 100 gpm due to drain cover flow restriction. Suction Hazard. 2 HP MOTOR ON 1.5 HP PUMP
Const. Date: 1/1/1989 Rope Length: 33'
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Missing end caps on one ladder. Same ladder with some rust and corrosion may need replacement.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable.
Phone not operational. CPO replaced handset and corrected. No permit action.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. Items around piping. Pool built in 1989. No backflow at hose bib.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Pool discharges through pipe under equipment. Pool built '89. .2513(b) Filter backwash shall be discharged through an air gap.
Sep 30, 2025 6 demerits · 3 violations
Inspector comments: Conducted inspection with Cortez. Pool remains in good standing and on A status.
Const. Date: 1/1/1989
Rope Length: 33'
Permit Restriction: Max
pump flow limited to
100gpm for main drain
cover limitation. Flow
meter must remain
operational.2 HP MOTOR ON A 1.5HP PUMP
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Missing end caps on one ladder. Same ladder with some rust and corrosion may need replacement.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. Items around piping. Pool built in 1989. No backflow at hose bib.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Pool discharges through pipe under equipment. Pool built '89. .2513(b) Filter backwash shall be discharged through an air gap.
Feb 25, 2025 10 demerits · 4 violations
Inspector comments: Conducted pool inspection with CPO Otto. Pool cloudy but clear enough to see main drains. Some bricks on floor getting loose. Pool remains in good standing and on A status.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Missing two out of four weirs. Replace. No permit action.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Missing end caps on one ladder. Same ladder with some rust and corrosion may need replacement.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. Items around piping. Pool built in 1989. No backflow at hose bib.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Pool discharges through pipe under equipment. Pool built '89. .2513(b) Filter backwash shall be discharged through an air gap.
Sep 16, 2024 6 demerits · 3 violations
Inspector comments: Performed inspection with CPO Otto. Pool remains on A status and in good standing.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Missing end caps on one ladder. Same ladder with some rust and corrosion may need replacement.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. Items around piping. Pool built in 1989. No backflow at hose bib.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Pool discharges through pipe under equipment. Pool built '89. .2513(b) Filter backwash shall be discharged through an air gap.
Jan 18, 2024 10 demerits · 4 violations
Inspector comments: EHS conducted inspection onsite Otto Williams. One intent to suspend item .2518(k) Replace missing weirs. Missing one of four weirs. Replace. Call or text Devon Moeller when weir has been replaced.
Past water quality records kept onsite.
Doors have audible alarms installed.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Missing one of four weirs. Replace. Intent to suspend item.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. One skimmer blocked by large toy in basket. Remove obstruction.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Missing end caps on one ladder. Same ladder with some rust and corrosion may need replacement.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. Items around piping. Pool built in 1989. No backflow at hose bib.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Pool discharges through pipe under equipment. Pool built '89. .2513(b) Filter backwash shall be discharged through an air gap.
Oct 11, 2023 28 demerits · 9 violations
Inspector comments: Inspection conducted with Otto Williams. Pool permit issued. Sticker provided during inspection. Permit will be available for printing from the website.
A 30 day intent to suspend the permit will be issued for doors leading onto the pool deck not self closing and latching shut or audibly alarmed. EHS will return at 30 days to evaluate all 3 doors leading onto pool deck. At that time, water chemistry will also be evaluated as readings inconsistent.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Missing one of four weirs. Replace. No permit action.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Missing end caps on one ladder. Same ladder with some rust and corrosion may need replacement.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy with rope greater than 36’. Corrected to 33’.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. All three entry doors onto pool deck observed to not be self closing and self latching each time and not alarmed. *permit item
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Furniture within 5’ of pool. Operator relocated.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. Items around piping. Water under pump. Pool built in 1989. No backflow at hose bib.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. .2533(d) Pump room floor shall be kept dry and free of standing water.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
.2518(d) Piping and valves shall be labeled with color codes or labels. Pipework re-plumbed needs to be labeled or color coded.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Pool discharges through pipe under equipment. Pool built '89. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(j) Provide soap and soap dispenser, no glass, at each sink. No soap available in either restroom.
Oct 31, 2022 36 demerits · 11 violations
Inspector comments: Immediate suspension issued for emergency phone. Pool closed signs posted. Pool must REMAIN CLOSED until suspension is lifted by health department. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension.
Main drains and skimmer equalizer covers expire November 2022. Replace and update PDSC form and submit to health department for approval. Failure to gain approval will keep pool closed with suspension.
Manager stated pool is being renovated. Ensure in field plan review is submitted with spec sheets for approval for all major changes done to the pool PRIOR to work done.
Pool deck must be repaired prior to 2023 for operating permit.
Other permit items include: record keeping, pool floor/plaster, weirs, doors and deck clearance.
Inspection with Hope McIntosh and Nermin Boutros
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records observed missing daily records. .2535(11) The pool operator must maintain records for at least six months. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*Permit item.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Debris collecting on pool floor. Plaster starting to crack in pool. 2537(14) Keep pool surface and pool floor free of debris. Keep in good repair.
*permit item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir missing at time of inspection.
.2518(k) Replace missing weirs.
*permit item
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders missing rubber caps and one ladder loose.
.2521 Install ladders per manufacturer instructions.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Side door onto pool deck and not latching or completely closing at time of inspection. Door for stairwell onto pool deck not latching or alarmed at time of inspection.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
*Permit item
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some chairs within 5' of pool. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Some pavers not secure to deck.
.2522(b) Provide at least 5 ft of clear walking space around the pool at all times.
.2537(2) Decks shall be kept in good repair.
*permit item
#22 · Premises: emergency telephone provided −6
Emergency phone not operable, no dial tone at time of inspection.
.2530(f) Emergency phone shall remain operable.
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone.
**Immediate suspension item. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. Items around piping. Water under pump. Pool built in 1989. No backflow at hose bib.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. .2533(d) Pump room floor shall be kept dry and free of standing water.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Two pipes labeled “Skimmers” and no vacuum line. Ensure pipes are labeled correctly. .2518(d) Piping and valves shall be labeled with color codes or labels.
CPO not present to verify correct labeling.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Pool discharges through pipe under equipment. Pool built '89. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Men's restroom sink leaking at time of inspection. .2526(m) Keep restrooms and fixtures clean and in good repair.
Jan 4, 2022 42 demerits · 11 violations
Inspector comments: Immediate suspension issued for water quality and emergency phone. Chlorinator must be in working order (cannot shock pool as corrective action). Contact Marie Daley at 704-507-6806 when items are in compliance to lift suspension. Pool MUST REMAIN CLOSED with signage posted until suspension is lifted by Health Dept.
Other permit items to be verified at return visit: record keeping, doors onto pool deck self-closing, self-latching or alarmed, spare pump basket
Note: All drain covers expire November 2022. Update, submit new PDSC form for approval prior to expiration to avoid permit action
Pavers are loose around pool in some areas. If this worsens, repair of deck will be required for permit.
Inspection with Otto WIlliams and Cortz
No signature due to COVID
"E" Immediate Suspension
#2 · Water quality: disinfectant residual provided by −6
Chlorine 0 ppm at time of inspection .2535(4) Maintain chlorine at least 1.0 ppm.
**Immediate suspension item. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records observed with multiple days of water quality out of compliance with no corrective action. Multiple forms, not all filed out daily and not retrievable for last 6 months. .2535(11) The pool operator must maintain records for at least six months. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*Permit item.
Recommended using single form with required fields daily.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir stuck at time of inspection. Keep in good repair. Operator adjusted and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Alarm not working on side door onto pool deck and not latching or completely closing at time of inspection.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
*Permit item
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some chairs within 5' of pool. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Items moved. Corrected.
*Some pavers not secure, but not offset. Advised monitoring. If worsens, repair may be warranted.
#22 · Premises: emergency telephone provided −6
Emergency phone not dialing back to phone or showing outgoing emergency call. Number listed is mainline to hotel.
.2530(f) Emergency phone shall remain operable.
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone.
**Immediate suspension item. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Chlorinator not working at time of inspection.
.2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions.
*Permit item
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Unable to locate spare pump basket at time of inspection (Whisperflo WF-6) .2518(e) Provide a spare basket for pump.
*Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room, some on floor. Items around piping. Water under pump. Pool built in 1989. No backflow at hose bib.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. .2533(d) Pump room floor shall be kept dry and free of standing water.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Pool discharges through pipe under equipment. Pool built '89. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Men's restroom sink leaking at time of inspection. .2526(m) Keep restrooms and fixtures clean and in good repair.
Jul 29, 2021 16 demerits · 5 violations
Inspector comments: Visit to pool for pre-permit inspection. Issued permit. Changed to "A" Open for Business.
Deck has been renovated and approved. If drainage worsens into pool or standing water, deck renovations will be required.
Motor replacement passed electrical inspection, 2 HP motor on 1 1/2 HP pump.
Inspection with Otto Williams
No signature due to COVID
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Buoy rope tangled at time of inspection, not 33'.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Keep accessible. Untangled and corrected.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Hole in deck by entry handrail greater than 1/2" where deck repaired. Ladder within 5' of pool.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
.2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Operator patched hole with cement and eliminated gap. Moved ladder. Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room, some on floor. Items around piping. Water under pump. Pool built in 1989. No backflow at hose bib.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. .2533(d) Pump room floor shall be kept dry and free of standing water.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Pool discharges through pipe under equipment. Pool built '89. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Soap dispenser not working in restrooms. Paper towels out in restrooms. Men's restroom sink leaking at time of inspection. .2526(m) Keep restrooms and fixtures clean and in good repair. Keep soap and paper towels in restroom for hand washing.
Feb 20, 2020 22 demerits · 7 violations
Inspector comments: 6) Water murky, but main drains visible and water quality in compliance. Ensure water clarity allows visibility of main drains at all times.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder missing step.
.2521 Install ladders per manufacturer instructions.
.2521(b) Ladders shall have slip-resistant tread.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Small hole, drain port, in pool wall by handicap chair, greater than 1/2" open offset. Cover hole to eliminate offset. Lack of severity does not warrant permit action. Operator is sending verification of correction to Marie Daley 704-507-6806 and item will be checked at next inspection.
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Buoy rope tangled at time of inspection. Keep accessible. Operator untangled and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Alarm not working on side door onto pool deck and not latching at time of inspection.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Operator adjusted alarm and corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room, some on floor. Items around piping. Pool built in 1989.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Pool discharges through pipe under equipment. Pool built '89. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Men's restroom sink leaking at time of inspection. .2526(m) Keep restrooms and fixtures clean and in good repair.
Nov 12, 2019 24 demerits · 6 violations
Inspector comments: Pump motor not grounded at time of inspection. Pump must be grounded and certified by licensed electrician.
Pool voluntarily closed until permit pulled.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Buoy rope tangled at time of inspection. .2530(a) Lifesaving equipment should be conveniently located. Operator untangled and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Front door onto pool deck sensor not turning off to allow door to latch within 30 seconds. Back door not self-latching or alarmed.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Operator installed alarms on both doors to self-close and have audible alarm. Corrected.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some chairs and tables within 5' of pool.
.2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Items moved. Corrected.
#22 · Premises: emergency telephone provided −6
Emergency phone not operating at time of inspection.
.2530(f) Emergency phone shall remain operable. Operator replaced phone. Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room, some on floor.Pool built in 1989.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Men's restroom sink leaking at time of inspection. .2526(m) Keep restrooms and fixtures clean and in good repair.
Provide paper towels/hand drying in both restrooms.
Apr 15, 2019 18 demerits · 4 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
No rubber caps on ladder at deep end. .2521 Install ladders per manufacturer instructions.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One inlet fitting missing at time of inspection. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Lack of severity did not warrant permit action. Send verification of replacement to Marie Daley. This item will be verified for compliance on next inspection.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Buoy rope tangled at time of inspection. .2530(a) Lifesaving equipment should be conveniently located. Operator untangled and made accessible. Corrected.
#22 · Premises: emergency telephone provided −6
Emergency phone not operable at time of inspection. .2530(f) Emergency phone shall remain operable.
Operator replaced phone and corrected.
Nov 13, 2018 24 demerits · 6 violations
Inspector comments: 30 Day ITS for spare pump basket, depth marker and door.
General Comment:
Deck starting to crack up in two places. Keep offsets less tha 1/2" as trip hazard. Reccomended repairing before worse/out of compliance.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator cleaned. Corrected.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
.2523(a) Provide depth markers on pool walls and pool deck next to the swimming pool. Pool wall depth marker rusting, hard to read. (5 FT)
**30 Day Intent to Suspend (ITS). Contact Marie Daley 704-507-6806 to lift when corrected
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Provide rubber caps on ladders.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment should be conveniently located. Rope tangled. Operator untangled. Corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
**30 Day Intent to Suspend (ITS). Contact Marie Daley 704-507-6806 to lift when corrected
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(e) Provide a spare basket for pump. Pentair Whisperflo WF-6 1.5 HP
**30 Day Intent to Suspend (ITS). Contact Marie Daley 704-507-6806 to lift when corrected
Jan 29, 2018 26 demerits · 6 violations
Inspector comments: Immedate suspension issued for emergency phone and main drains and equalizers with risers extending over 2"
Call Chris Sells when repairs have been completed or with questions at 704 576 8678
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Observed Paramount SDX Retros covers with riser ring extending over 2 inches on wall and floor.
Drain outlets shall comply with ASME/ANSI A112.19.8-2007. No drains shall extend over 2 inches.
**Immedate suspension issued
Removed riser rings and replace covers.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed pool floor collecting debris. Observed pool wall tile collecting residue.
Keep pool walls and floors clean.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 2 skimmers missing weirs.
Keep skimmers in good repair.
**Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed 2 ladders missing end caps.
Replace caps
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed motion sensor on doors. Doors must be self closing self latching, or self closing with an audible alarm.
**Intent to suspend item
#22 · Premises: emergency telephone provided −6
Observed emergency phone connection not consistant. Wall jack damaged not making constant connection.
**Immediate suspension
Nov 7, 2017 6 demerits · 1 violation
Inspector comments: Observed motion sensor for door unlock into lobby.
Observed no Cl feeder in pump room, pool is utilizing a salt generator only.
PDSC information states that drains expire on 11/9/17.
#22 · Premises: emergency telephone provided −6
Pool phone cutting out. Phone repairs completed during inspection.
Jun 30, 2017 38 demerits · 10 violations
Inspector comments: 1. Observed pool to be somewhat cloudy, but drains visible
#2 · Water quality: disinfectant residual provided by −6
Chlorine level < 1.0ppm, corrected to 1.0 ppm during inspection
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Replace missing weir
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Replace ladder bumpers
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Replace 2 missing eyeball return fittings
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Corrected rope length to 33'
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Replace burned out pool light
#22 · Premises: emergency telephone provided −6
No phone number posted-corrected during inspection, removed 2nd emergency phone that wasn't working
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Continuous forced ventilation required, keep 3' of clear walkway around equipment
#27 · Equipment room: filter backwash discharged through an air gap −2
2" air gap required on backwash line
#32 · Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean −2
Bathroom floors should be slip-resistant
Dec 6, 2016 32 demerits · 9 violations
#2 · Water quality: disinfectant residual provided by −6
No chlorine in pool. Pool has saline system. Maintain chlorine at least 1.0 ppm. Immediate Suspension issued.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Some records missing from log books. Maintain chlorine, pH, main drain checks and temperature daily.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder greater than 6" from pool wall and missing end cap. Pool built prior to 2010. Maintain between 3" and 6" from wall to ladder and replace end cap.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Two wall returns missing fittings. Replace.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Severe damage to deck in several locations. Repair decking where needed.
4 ft from pool to wall in several locations. Pool built prior to 2010. Maintain 5 ft clearance around swimming pool.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
One light burnt out in swimming pool and dim lighting in pool room. Pool must maintain at least 10 ft candles of light to operate at night.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Coupling broken on piping into pump. Repair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room floor wet due to leaking valve in pump room. Keep dry and repair line.
#32 · Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean −2
Floors in restrooms slick. Floors shall be slip-resistant.
Jan 21, 2016 20 demerits · 6 violations
Inspector comments: #12 Missing 1 inlet fitting. **Install.
Note: Emergency phone had heavy static.
** Phone replaced while EHS on-site.
Intent to Suspend issued for #16.
EHS training staff for pool authorizations.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder at least 8" from pool wall. ** Maintain 3" to 6" maximum.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
2 ring buoys (only 1 required). Throw rope not secured to one ring buoy & throw rope on 2nd buoy 31' (33' throw rope required). ** Corrected during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door from pool enclosure to stairwell will not self-close completely/ will not self-latch. ** Resolve.
Intent to suspend.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck chipping & coping chipped in many areas. ** Repair/ resurface.
Water pooling on deck @ cube wall. ** Resolve.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment/ chemical room floor wet due to water line leak. ** Resolve.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Automatic soap dispensers in restrooms not working.
** Provide soap at all times.
Nov 10, 2015 12 demerits · 4 violations
Inspector comments: #12 Missing 1 inlet fitting. ** Install.
GC #15 2 ring buoys. Throw rope on one ring buoy 36' in length. ** Rope shortened to 33' while on-site. (Only one buoy required.)
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed soil/ scum on pool wall tiles. ** Clean.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder 8" from pool wall. ** Maintain 3" up to 6" maximum.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck chipped & coping chipped in many areas.
** Repair/ resurface.
Water pooling @ end of deck by "cube" wall. ** Resolve.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Automatic soap dispensers in restrooms not working.
** Replace batteries so that soap is available.
Feb 16, 2015 12 demerits · 5 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders >8" from pool wall. Maintain 3" to 6".
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Pool deck wet and some chipping paint on coping. Keep dry and in good repair.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Clearly identify all pipes in pump room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash line to pit. Provide air gap.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No floor drain/hose bib in restrooms. Provide.
Dec 2, 2014 4 demerits · 1 violation
Inspector comments: #11 Observed ~8" clearance between ladders & pool wall. **Clearance should not be any more than 6". Correct.
GC #17 Observed baskets for used towels 4.5' from pool dege. **Maintain 5' of clear walking space.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed scum on pool wall tiles. **clean.
Mar 20, 2014 2 demerits · 1 violation
Inspector comments: #17 Observed linen baskets ~4.5' from pool edge. **Maintain 5' of clear walking spce.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed hot water at least 114.4F @ lavatory in men's restroom. Hot water @ lavatory in women's restroom is shut off. **Maximum temperature allowed is 110F. Hot water @ lavatory in men's restroom shut off during inspection.
Oct 9, 2013 6 demerits · 1 violation
Inspector comments: #17 Observed chipped coping near custom pool rules sign. Observed some chipped paint on white border.
GC #25 Observed some water on equipment room floor. **Keep floor dry.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed one ring buoy (of 2) with broken strap. Only one ring buoy required. **Ring buoy with broken strap removed while on-site.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “EMBASSY SUITES HOTEL” or State ID 2060530043). Inspection type (routine vs. follow-up) is not published in the county's data.