MECKLENBURG CO AQUATIC CENTER
800 E MARTIN LUTHER KING JR BLVD, Charlotte, NC 28202
Year-Round Swimming Pool · NC permit/State ID 2060530056
Latest result12 demerits
Last inspectedFeb 16, 2026
Inspections on record25
On record sinceOct 7, 2013
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Oct 7, 2013Lower is betterFeb 16, 2026
Inspections & violations
Feb 16, 2026 12 demerits · 4 violations
Inspector comments: 6 - One screw missing from drain cover, third over from left side. Replace screw within 30 days.
Intent to Suspend issued for:
.2528 - Double door entry, far right door from inside not latching every time.
Double doors on right side of pool that lead to outside - one door stuck and other door not latching correctly.
Office 114 with audible alarm not operable and door not self-latching.
Repair doors to self-close, self-latch.
.2523 - replace depth marker at 11 ft. 10 in. on pool wall.
Daniel Osucha present during the inspection.
Paddock drain covers - Installed March 2016. Provide yearly documentation for recertification of drains after March 2026.
Screws changed Dec 2019 - due Dec 2026.
PERMIT RESTRICTION - SET POINT FOR VFD AT 40 HZ - FLOW METER RESTRICTION AT MAX 2147 GPM DUE TO PUMP DESIGN FLOW
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Depth marker at 11 ft. 10 in on left side of pool damaged.
Replace all depth markers where damaged so 4 in. in height. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Slip-resistant tread beginning to wear off of some starting platforms. Monitor and replace where needed.
No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
Bulkhead with some damage to slip-resistant tread. Monitor and repair as needed if worsens.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Double door entry, far right door from inside not latching every time.
Double doors on right side of pool that lead to outside - one door stuck and other door not latching correctly.
Office 114 with audible alarm not operable and door not self-latching.
Repair doors to self-close, self-latch.
Door closest to main pool pump room dog eared back. Corrected during the inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One sink not operable in women's restroom. Keep all fixtures in good repair.
Spoke with patron while onsite who stated that two shower stalls in the men's had inoperable faucets and one toilet is not operable. Keep all fixtures in good repair.
Dec 2, 2025 20 demerits · 6 violations
Inspector comments: Daniel Osucha present during the inspection.
Intent to Suspend issued for: .
.2528 - All doors on back side of pool area either sticking or not latching. Repair doors to self-close, self-latch. Office room 12 handle not latching. Repair to self-close, self-latch.
.2523/.2537 - replace all wall depth markers where needed to ensure 4" height and not damaged.
Screws due to be changed December 2026.
Permit Restriction: VFD required at 40 hz, with flow at 2147 gpm based on design flow of pump VFD verified at 40 hz and flow at 2160 gpm.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some debris on pool floor near main drains. Ensure vacuuming to keep pool floor clean.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Multiple depth markers on pool walls damaged so not 4 in. in height.
1) 7 ft. 0 in. near center of the pool on main entry side.
2) (2) 6 ft. 9 in. markers.
Replace all depth markers where damaged so 4 in. in height. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Slip-resistant tread beginning to wear off of some starting platforms. Monitor and replace where needed.
No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
Bulkhead with some damage to slip-resistant tread. Monitor and repair as needed if worsens.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Handicap door not closing upon arrival. Working by end of inspection.
Door near pump room dog eared back. Corrected to latch during the inspection.
All doors on back side of pool area either sticking or not latching. Repair doors to self-close, self-latch. Intent to Suspend issued.
Office room 12 handle not latching. Repair to self-close, self-latch. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs on pool deck within 5 ft. of pool edge. Ensure 5 ft. clearance around the pool in all areas.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One sink not operable in women's restroom. One shower faucet holster damaged in women's shower. Keep all fixtures in good repair.
Mar 31, 2025 18 demerits · 6 violations
Inspector comments: Intent to Suspend issued for:
.2523 - replace wall depth marker and repair N to meet 4" requirement.
.2527 - replace cap at deep end on pool deck.
.2528 - repair all doors to self-close, self-latch
Daniel Osucha present during the inspection.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
7 ft. 4 in depth marker on side closest to pump room coming off of wall. Replace depth marker. 6 ft. 9 in. with N missing some of the lettering on right side of pool near lane flag. Depth markers shall be 4" height. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Slip-resistant tread beginning to wear off of some starting platforms. Monitor and replace where needed.
No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
Bulkhead with some damage to slip-resistant tread. Monitor and repair as needed if worsens.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Most double doors at family dressing rooms and also double doors to main entrance dog-eared back. Doors shall self-close, self-latch. Double doors that lead to outside at deep end of pool not self-closing, self-latching. Appears that weather stripping is preventing doors from latching. Rooms 114 and Ste 12 with either audible alarms not operable or not latching. All doors shall self-close, self-latch. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Cap missing from pool deck at far end of pool. Replace cap. No openings/offsets >1/2". Intent to Suspend issued.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Check valve for fill line leaking. Catch drain leaking. Floor wet under leak. Keep floor dry.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Cold water handle in the women's locker room damaged. Repair.
Nov 7, 2024 14 demerits · 4 violations
Inspector comments: 22 - Emergency phone number starting to fade on signage. Number shall be clearly visible. Repair in 30 days. Will verify on return visit.
Intent to Suspend issued for:
.2523 - replace depth markers where needed
.2528 - repair doors to self-close, self-latch where needed; repair handicap door to shut so that it does not stay open to exceed 3-5 minutes
.2537 - repair deck damage near hose; install plugs to holes in pool deck.
Daniel Osucha present during the inspection.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
8 in on wall depth marker near double doors peeling off of wall. 6 ft. 8 in. on corner nearest to warm pool coming off of wall. Replace wall depth markers. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Slip-resistant tread beginning to wear off of some starting platforms. Monitor and replace where needed.
No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
Bulkhead with some damage to slip-resistant tread. Monitor and repair as needed if worsens.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Multiple doors not self-closing, self-latching. Repair as listed: Multipurpose room 123, door nearest to diving boards dog eared back, double doors with one door on each secured shut (could not verify), double doors with one door not latching, office 114. Intent to Suspend issued.
Handicap door stays open for at least 3 minutes. Door shall self-close, self-latch to eliminate child access. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Holes on pool deck and bulkhead without plugs where dive platforms/handrails placed. Provide plugs for holes in deck. Intent to Suspend issued.
Severe damage to deck near water hose at steps near the stadium. Opening/offset >1/2". Repair deck. Intent to Suspend issued.
Feb 12, 2024 14 demerits · 5 violations
Inspector comments: Intent to Suspend issued for:
.2523 - repair depth marker on pool deck at IN and on far pool wall - both at 6 ft. 9 in.
.2537 - repair deck drains so offsets <1/2"; provide plugs on pool deck for ladder/pole openings on deck and on bulkhead
Daniel Osucha present during the inspection.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Depth marker on pool deck for 9 in. with some damage to in. Repair deck depth marker.
One deck marker on pool wall at 6 ft. 9 in. at far end. Replace depth marker.
Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Slip-resistant tread beginning to wear off of some starting platforms. Monitor and replace where needed.
No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
Bulkhead with some damage to slip-resistant tread. Monitor and repair as needed if worsens.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Holes on pool deck and bulkhead without plugs where dive platforms/handrails placed. Provide plugs for holes in deck. Intent to Suspend issued.
Deck drain with grates >1/2" apart. Maintain openings/offsets less than 1/2". Intent to Suspend issued.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room floor wet/damaged next to backwash pit. Water on floor under UV - leak at UV. Keep pump room floor dry.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Two soap dispensers in the women's restroom are damaged. Replace dispensers so operable.
Hot water >113F. Maintain at 110 F or below.
Nov 16, 2023 18 demerits · 5 violations
Inspector comments: Note: Emergency operator indicated the phone was staticky. 911 operator could be clearly heard and address/phone number were able to be verified. Continue monitor. May require replacement in the future.
Note: One body hook was not attached to pole. Facility had two additional body hooks securely attached to the pole. Recommend attaching body hook to pole.
Intent to Suspend issued for the following:
.2523/.2537 - repair/replace depth markers on pool wall in multiple locations
.2528 - repair door to self-close, self-latch
.2537 - plug openings on pool deck for dive platforms/ladders
.2525 - provide new test kit testing tubes
Daniel Osucha present during the inspection.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Test kit tubes with staining. Replace test kit testing tubes. Intent to Suspend issued.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Multiple depth markers on pool wall damaged missing lettering or ft/in. Replace around pool perimeter in all locations where wall depth markers are damaged. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Slip-resistant tread beginning to wear off of some starting platforms. Monitor and replace where needed.
No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
Bulkhead with some damage to slip-resistant tread. Monitor and repair as needed if worsens.
Large fan stored behind diving board. Maintain 5 ft. clearance around dive boards at all times.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Second door on double doors to outside not self-closing, self-latching. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Holes on pool deck without plugs where dive platforms/handrails placed. Provide plugs for holes in deck. Intent to Suspend issued.
Mar 17, 2023 10 demerits · 3 violations
Inspector comments: Daniel Osucha present during the inspection.
Intent to Suspend issued for:
.2537 - repair deck drains to ensure no openings >1/2"
.2537 - replace stoppers in lane line and ladder holes on deck
.2528 - repair both doors to self-close, self-latch
Chlorinator and VGB verified during the inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Slip-resistant tread beginning to wear off of some starting platforms. Replace where needed.
No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
Bulkhead with some damage to slip-resistant tread. Monitor and repair as needed if worsens.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One door with push bar not operational. Repair door to self-close, self-latch.
One door with push bar dogged back. Repair to self-close, self-latch.
Intent to Suspend issued for above items.
One door on to pool deck with audible alarm disengaged. Corrected during the inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck drain with >1/2" openings between diving boards and behind 7 ft. 8 in. by back doors. Maintain openings on pool deck less than 1/2".
Some lane line stoppers/ladder stoppers missing from holes in deck. Maintain openings <1/2".
Intent to Suspend issued for above items.
Nov 22, 2022 10 demerits · 3 violations
Inspector comments: Inspection completed with Daniel Osucha. Hannah Howard present for training.
Recommend moving body hooks and poles so that not present in the same location. Poles and body hook should be located so that public can access easily.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Two wall depth markers at 6 ft. 9 in. and 7 ft. 9 in. with damage. Replaced during the inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Slip-resistant tread beginning to wear off of some starting platforms. Replace where needed.
No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
One diving platform on long side of pool >30 from water edge. Maintain at max 30" from water line.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One door not self-closing, self-latching at far end of pool near deep end. Repair door to self-close, self-latch. Corrected during the inspection.
Feb 1, 2022 20 demerits · 6 violations
Inspector comments: 15 - Recommend moving one body hook to opposite side of pool to ensure accessible by patrons at all times. No pressure gauges on filter. Original construction.
Daniel Osucha present during the inspection. No signature due to covid restrictions.
Intent to suspends issued for depth markers, barrier repair, and drain flies in drains.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Total alkalinity reagent expired. Replaced during the inspection.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Damage to depth markers in multiple locations. Provide 4 ft. contrasting lettering at least every 25 ft. around pool perimeter. Intent to Suspend issued for the following.
1. Replace N where damaged at 7 ft. 4 in. - left side of pool wall.
2. Damage to 4 at 7 ft. 4 in at far side of pool wall.
3. Damage to deck depth markers at N's. Two at far side of pool - 6 ft. 9 in.
4. Damage to ft. on wall 6 ft. 9 in. at far side of pool. 2nd from end of pool.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Slip-resistant tread beginning to wear off of some starting platforms. Replace where needed. No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517. Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One double door from pool to lobby not self-latching. Only latches sometimes. Right door near pump room not self-latching every time. Repair doors to self-close, self-latch. Intent to Suspend issued.
Note: Roll-up door remains locked from inside and is maintenance gate. Automated system only controlled by employee's/pool operator.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some damage near deck drain near egress doors to outside. Keep flooring in good repair. No offset >1/2". Continue to monitor and repair if worsens.
Slip-resistant tread beginning to wear off bulk head flooring. Continue to monitor and repair as needed. Public does not have access to bulk heads. Flooring shall be slip-resistant.
Some staining on deck around the pool. Does not appear to be slick. Monitor to ensure floor is maintained as slip-resistant.
Some drain flies on pool deck above drain at end nearest to locker room entrance. Keep drains clean and free of insects. Intent to Suspend issued.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One damaged shower clip in family locker room. Repair fixture.
Sink faucet handles with springs not running for full hand wash. Repair faucet handles to ensure proper handwashing can occur.
Oct 28, 2021 16 demerits · 5 violations
Inspector comments: 5 - Test kit tubes with black build-up. Recommend replacing test kit tubes.
6 - One main drain off center. Operator inspected drain covers 10/5 and had to secure to sump. Continue to monitor. Operator stated secure once repaired.
15 - Recommend moving one body hook to opposite side of pool to ensure accessible by patrons at all times.
No pressure gauges on filter. Original construction. Daniel Osucha present during the inspection. No signature due to covid restrictions.
Intent to Suspend issued for depth markers and pool barrier.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Multiple no diving markers on pool walls worn off/coming off including but not limited to:
- 7 ft 4 in on grand stand side.
- 12 ft. 8 in. on both sides.
- 11 ft 10 in and 7 ft 8 in by outside egress near grand stand side
Replace depth markers on pool wall where needed. Intent to Suspend issued.
>25 ft. between wall depth markers at 6 ft 9 in. center and to left of center. Maintain 25 ft. between wall depth markers. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
11 - Slip-resistant tread beginning to wear off of some starting platforms. Replace where needed. No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517. Warning signage peeled off on multiple dive platforms. Dive platforms shall have warning signage along with constant monitoring from lifeguard. Replace warning signage on platforms or provide other means to keep inaccessible.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Multiple doors not self-closing, self-latching or self-closing with audible alarm. Repair to self-close, self-latch or self-close with audible alarm. Intent to Suspend issued.
1. Men's and women's doors from locker rooms.
2. Multi-purpose room.
3. Office rooms 116 and 114.
Note: Roll-up door remains locked from inside and is maintenance gate. Automated system only controlled by employee's/pool operator.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some damage near deck drain near egress doors to outside. Keep flooring in good repair. No offset >1/2". Continue to monitor and repair if worsens.
Slip-resistant tread beginning to wear off bulk head flooring. Continue to monitor and repair as needed. Public does not have access to bulk heads. Flooring shall be slip-resistant.
Some staining on deck around the pool. Does not appear to be slick. Monitor to ensure floor is maintained as slip-resistant.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Sink faucet handles with springs not running for full hand wash. Repair faucet handles to ensure proper handwashing can occur. One sink missing handle in the family restroom. Keep all fixtures in good repair.
Mar 3, 2021 6 demerits · 2 violations
Inspector comments: Note: Recommend investigating gutters on far ends of pools. Currently without grates on underside.
No pressure gauges on filter. Original construction.
Daniel Osucha present during the inspection. No signature due to covid restrictions.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Some depth markers on walls beginning to peel back. Continue to monitor and repair as needed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Slip-resistant tread beginning to wear off of some starting platforms. Replace where needed.
No labeling on diving boards. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Sep 17, 2020 14 demerits · 4 violations
Inspector comments: No signature due to covid restrictions. Daniel Osucha present during inspection.
Automated chlorinator verified during inspection.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
9 in. of 6 ft. 9 in. damaged. Corrected during inspection with new wall depth marker.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Some slip-resistant tread wearing off of dive platforms. Replace tread where needed.
Some Danger stickers wearing off on dive platforms. .2517(e) Secure starting platforms from use by removal; covering; or signage and active supervision.
Two of five dive platforms at 31" from water line. Ensure, in water >5 ft., no greater than 30" from water line.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some slip-resistant tread wearing off on bulkheads. Continue to montitor and repair as needed.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Bicarb stored on top of filter in pump room. Store chemicals in chemical storage rooms.
Jan 29, 2020 14 demerits · 4 violations
Inspector comments: 22 - Emergency phone not clearly audible. 911 indicated they could barely hear inspector. Given 30 days to repair phone so clearly audible.
29 - Some sink faucet handles not staying on when pushed. Repair to ensure proper handwashing can occur.
Note: Chlorinator verified to detect flow during inspection.
Note: Facility was vacuuming at time of inspection. Instructed staff to not vacuum while pool is open to the public. Portable vacuum used.
Intent to Suspend issued for depth markers and doors on to pool deck.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Two 6 ft. 9 in. depth markers on pool walls on either side damaged. Replaced where needed. Intent to Suspend issued.
.2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder handrail loose closest to large doors by storage area. Keep handrails tight and in good repair.
.2521 Install ladders per manufacturer instructions.
No labeling on diving equipment. .2517(a)3 Provide labeling affixed to diving equipment.
Some Danger labeling on diving platforms not in place or damaged. .2517(e) Secure starting platforms from use by removal; covering; or signage and active supervision.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door from main entry area and right family restrooms not self-closing, self-latching. Repair to self-close, self-latch. Intent to Suspend issued.
.2537(b) All gates and doors shall be self-closing, self-latching.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some damage to slip-resistant tread around bulkhead where diving platforms are installed. Keep decking slip-resistant. Some anchors around pool deck missing plugs. Corrected during inspection.
.2522(g) Decks and walkways shall be slip-resistant.
Minor deck damage around drains. Continue to monitor to ensure no offsets >1/2".
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
Nov 12, 2019 10 demerits · 3 violations
Inspector comments: Intent to Suspend issued for wall depth markers and fittings for diving platforms/ladders.
Note: Ants were visibly seen throughout the pool deck area surrounding the swimming pool.
Note: One drain cover in deep end not sitting square. Verify within 30 days and provide documentation that drain cover is affixed per manufacturer specifications.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Some damaged wall depth markers at 6 ft 9 in. near locker room entry and also at 7 ft 4 in. in two locations on right side of pool looking from locker room. Replace wall depth markers where needed. Intent to Suspend issued.
.2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some holes from ladder/diving platforms missing fittings. Provide fittings for all holes in deck to eliminate hazard. Intent to Suspend issued..2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
Some damage to decking around deck drains in some locations. .2537(2) Decks shall be kept in good repair.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One damaged shower fixture in handicap stall in women's. Some sink faucet handles with springs not staying engaged. Repair fixtures and equipment.
Mar 13, 2019 10 demerits · 2 violations
Inspector comments: Observed flow rate as high as 2200 gpm. Permit restriction requires no flow greater than 2147.
Maintain flow at 2147 or below. Ensure percent error is included in flow meter calculation. If 1% error is present max flow cannot exceed 2125gpm.
Return visit to verify.
Only one lifeguard with buoy was provided for indoor pool that is greater than 3,000 sq. feet. Corrected during inspection - two more lifeguards were provided by facility without prompting from the inspector.
Verified PDSC information
Call Chris Sells with questions at 704 576 8678.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed body hook on telescoping poll. Corrected during inspection.
.2530(a) Pole for body hook must be non-telescoping, non-adjustable, and non-collapsible.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed holes in deck that were not covered at time of inspection. Replaced during inspection.
Nov 28, 2018 18 demerits · 6 violations
Inspector comments: Note: Only one lifeguard noted on deck when inspection was first started. Assure 2 lifeguards at all time. Corrected during inspection
23 - Chlorinator could not be verified at time of inspection. Chlorinator and acid feeder must detect flow and turn off when pump turns off. Operator not present at time of inspection to verify.
24 - Operator indicated pressure gauge on vacuum of pump utilized to measure pressure for filter.
Note: Doors near the pump room for shallow and spa are sticking. Self-close, and self-latch; however doors are considered fire egress and both doors shall open and self-close, self-latch at all times.
Intent to Suspend issued for depth markers and flow for pump.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Depth markers at 12 ft. 11 in. missing "inches" on wall at deep end of pool. Provide 12 ft. 11 in. in 4" lettering. Intent to Suspend issued.
Some depth markers in disrepair - 8 in. at 12 ft. 8 in.; 4 in. at 7 ft. 4 in; 6 ft. at 6 ft. 9 in. Intent to Suspend issued.
.2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Bleachers at less than 5 ft. from diving board. Assure 5 ft. clearance. .2517 Diving equipment shall be installed in accordance with Rule .2517.
Diving platforms with some slip-resistant tread wearing off. Maintain as slip-resistant. .2517(a)1 Diving equipment shall be installed per manufacturer's instructions.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Two sets of diving platform holes missing. Replaced during inspection.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter exceeding set point by engineer and specifications of pump. Pump max flow at 2147 gpm and flow rating indicating 2225 gpm. Operator indicated that they had just backwashed which accounted for the increase of flow. Pump flow should equate to max flow rating of engineer on original permit and PACO listing. Intent to Suspend issued.
.2518(h) Provide approved pump in good repair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Standing water on pump room floor between backwash pit and filter.
.2533(d) Pump room floor shall be kept dry and free of standing water.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One sink leaking in women's restroom at faucet.
.2626(m) Keep restrooms and fixtures clean and in good repair.
Apr 4, 2018 18 demerits · 5 violations
Inspector comments: 23 - General Comment - Could not verify chlorinator at time of inspection. CPO not present.
Intent to Suspend issued for depth marker, roll-up door, plugs for starting platforms on deck and VFD setpoint.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Sticker depth marker on wall at 6 ft 9 in with damage. Replace depth marker. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
No labeling on diving boards per rule instruction. Diving boards must be installed per manufacturer instruction and labeled per rule .2517. Observed bleachers out and 8 ft clearance around diving boards not maintained. Provide 8 ft. clearance around all diving equipment. Some damage to slip resistant surface on starting platforms. Keep in good repair.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Roll-up door propped open. All doors on to pool deck must self-close, self-latch. Door is equipped to be kept locked and shall remain locked when not in use. Intent to Suspend issued. One other door propped open. Keep closed. Corrected during the inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some diving platform anchors and flag anchors missing plugs. Provide no openings in pool deck >1/2". Intent to Suspend issued. Some minor deck damage around deck drains. Keep in good repair. Metals platforms located near warm pool at 4 ft. from pool edge. Maintain 5 ft clearance around pool at all times.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter exceeding permit restriction and flow of pump at 2147 gpm. Flow meter indicating 2300 gpm average. Permit restriction of 40 Hz on VFD. Currently set at 40 Hz. Required adjustment to meet permit restrictions. Intent to Suspend issued.
Nov 6, 2017 12 demerits · 4 violations
Inspector comments: 5 - DPD-3 Reagent expired in test kit. Replace reagents.
Note: Chemical feeder not verified during inspection. Operator not trained on how to test.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
12 in 12 ft missing on pool wall near diving boards. Replace depth marker. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Some damage to slip resistant tread on diving blocks. Keep in good repair.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some missing plugs in openings on deck from diving blocks. Corrected during inspection.
Some build-up on deck. Keep decking clean and in good repair.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One toilet seat in women's restroom with some build-up. Keep all fixtures clean and in good repair.
Apr 3, 2017 14 demerits · 4 violations
Inspector comments: 9 - General Comment - 9 in 9 IN faded. Replace when needed.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some debris on pool floor. Keep clean.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Exit egress door at deep end not self-latching. Repair door. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some plugs missing from bulkhead platform. Replace plugs to eliminate openings greater than 1/2".
Some damage to slip resistant tread on bulkhead. Keep in good repair.
Some deck drains with build-up. Keep clean.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One shower with damaged holder for spray nozzle. Repair.
Nov 22, 2016 20 demerits · 5 violations
Inspector comments: Note: Chlorinator could not be verified during inspection.
Intent to Suspend issued for deck plugs, doors self-latching, self-closing and automated chlorinator alarm.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Body hook missing from the pool deck. Replaced during inspection with additional body hook and pole that was located on the warm pool deck.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door located at pump room entrance with pushbar locked in place. Corrected during inspection.
One door at double doors located at street side of the pool not self-closing. Door into men's locker room not self-closing, self-latching. Both are getting stuck once opened. Repair all doors to self-close, self-latch. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
•Damage to the slip resistant tread around the diving platform holes on the bulkhead.
Some floor plugs missing from the bulkhead and on the street side of the pool. Keep plugs in all holes >1/2" when not in use. Intent to Suspend issued.
Some staining on deck drains. Keep clean and in good repair.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Alarm flashing on automated chlorination system. Repair so operating properly. Intent to Suspend issued.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Holders for portable shower sprays broken in women's locker room. Keep all fixtures in good repair.
May 31, 2016 6 demerits · 2 violations
Inspector comments: Go to Meckpools.charmeck.org to print a copy of the pool permit to post in the pool area.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One of the emergency exit doors by warm pool pump room not self-latching. Corrected.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Water in restrooms > 110F. Maintain at no more than 110F.
Jan 20, 2015 20 demerits · 6 violations
Inspector comments: 22 - General Comment: Emergency phone sign not posted. Corrected.
Intent to Suspend issued for #9, #17
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some debris around main drains. Clean.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Between 26 1/2 ft and 26 ft between 13 ft deck depth markers. Provide every 25 ft or less. Intent to Suspend issued.
Wall 7 1/2 ft depth marker peeling. Repair.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder handrails loose. Tighten.
Incorrect labeling on diving boards. Provide proper labeling. See rule.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door at deep end not monitored and self-latching. Repair.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Coping damaged at 7 1/2 ft. Repair.
Plugs at dive platforms in shallow damaged. openings >1/2". Repair. Intent to Suspend issued.
Bleachers/judges deck <5 ft to pool. Maintain 5 ft clearance.
Damage/sharp edge at shallow bulkhead (plastic edge for side). Repair. Intent to Suspend issued.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Sink in womne's closest to entrance leaking and one hand dryer not operable. Repair.
Oct 21, 2014 20 demerits · 5 violations
Inspector comments: 29 - General Comment: One hand dryer not operable in women's and one urinal not operable in men's. Keep in good repair.
Intent to Suspend issued for #17, #7, and #9
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some tile missing on pool floor. Replace.
Damage to metal on floor grating >1/2" between with one piece broken and other raised up with screws showing. Repair to prevent hazard. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder handrails loose. Tighten.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Severe damage to bulkheads. Repair to prevent pinch/trip hazard. Intent to Suspend issued.
Judges stand <4 ft to pool. Maintain 5 ft clearance.
Some tile damage on deck at 7 1/2 ft. Keep tile in good repair.
#22 · Premises: emergency telephone provided −6
911 could not hear inspector. Cord replaced.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Damaged wall depth markers at 6 1/2ft and 7 1/2 ft. Replace. Intent to Suspend issued.
Feb 5, 2014 14 demerits · 4 violations
Inspector comments: 9 - General Comment: Observed 6 1/2 ft depth markers starting to come off wall. Repair to wall. 29 - General Comment: Observed one hand dryer not operating. Keep operational.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed loose ladder handrails. Keep tightened.Observed starting platforms not labeled. Provide active supervision and signage/removal.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed tile damage at 7 ft. Keep in good repair.Observed platform/lane rollers 5 ft from pool. Maintain 5 ft clearance.
#22 · Premises: emergency telephone provided −6
Observed incorrect phone # posted at phone and no ringer. Phone # corrected. Ringer turned on.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed light burnt out in chemical storage room. Replace light.
Oct 7, 2013 8 demerits · 3 violations
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Observed 26 1/2 ft between wall depth markers at 13 ft and one depth marker missing the 2. Maintain at 25 ft apart on wall. Corrected during inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed some ladders loose. Keep in good repair. Observed diving platforms not in use, not secure. Secure from use with covering, signage or removal and active supervision. Observed incomplete labeling on diving boards. See .2517(3).
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed light in chemical storage room burnt out/dim. Replace lighting.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “MECKLENBURG CO AQUATIC CENTER” or State ID 2060530056). Inspection type (routine vs. follow-up) is not published in the county's data.