6demerits
RENAISSANCE CHARLOTTE SOUTHPARK
5501 CARNEGIE BOULEVARD, Charlotte, NC 28209
Year-Round Swimming Pool · NC permit/State ID 2060530065
Latest result6 demerits
Last inspectedOct 27, 2026
Inspections on record27
On record sinceDec 12, 2013
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Dec 12, 2013Lower is betterOct 27, 2026
Inspections & violations
Oct 27, 2026 6 demerits · 1 violation
Inspector comments: Inspection conducted with LeCram.
SR 229544 - Renovations to fitness center to include finishes in restrooms. Requires site visit for IFPR once complete - 2026
PERMIT RESTRICTION:
FLOW METER MUST REMAIN OPERABLE. FLOW REQUIRED LESS THAN 100 GPM DUE TO DRAIN COVER FLOW RESTRICTION. SUCTION HAZARD.
Night swimming previously approved.
#22 · Premises: emergency telephone provided −6
.2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system. Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
Observed emergency number to the pool was incorrect. Callback number posted for the emergency phone is 978-643-5756, while 911 operator has 659-244-3679.
EHS confirmed callback number dials directly to the emergency phone located at the pool.
PIC Marcel posted correct callback number on sign.
Jan 22, 2026 10 demerits · 2 violations
Inspector comments: Permit restriction - flow meter must remain operable with flow less than 100 GPM due to drain cover flow restriction.
Permit suspended for emergency phone and barriers.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed alarm on door to pool from exercise room not audible. Also, observed door leading outside not self-latching. Permit suspended.
#22 · Premises: emergency telephone provided −6
.2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system. Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Emergency phone goes to front desk (not direct 911), dialing instructions are incorrect, 911 operator does not have an address associated with the number, and the call back number is incorrect. Permit suspended.
Oct 28, 2025 4 demerits · 1 violation
Inspector comments: Inspection completed with Edwin Rosario present.
Inspection completed by Kurtis Nelson with Eli Freese present.
Permit restriction - flow meter must remain operable with flow less than 100 GPM due to drain cover flow restriction.
Intent to suspend permit issued for missing daily main drain safety record checks. Ensure drains are checked and marked off in log book daily. Correct within 30 days.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Records not kept consistently for September and October. ITS issued.
Mar 18, 2025 4 demerits · 1 violation
Inspector comments: Inspection completed with Marcel Lecram present.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace damaged skimmer lid. Observed cracked skimmer lid.
.2518(k) Replace missing weirs. Observed 1 of 2 weirs installed.
Aug 29, 2024 16 demerits · 4 violations
Inspector comments: Inspection completed with David Timchula and John Linhart present.
Intent to suspend permit issued for door alarm not audible. Correct within 30 days.
Could not verify flow rating today due to maintenance being done to pump (cleaning of salt cells, pump was disassembled). No issues notated on previous inspections with flow ratings.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 1 of 2 weirs missing.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed ring buoy in poor repair. CDI- buoy replaced.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed alarm on door to pool from exercise room not audible. Intent to suspend permit issued.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. Observed door lock in poor repair so door can be bypassed easily.
Feb 8, 2024 6 demerits · 2 violations
Inspector comments: Inspection completed by Konya Parker and Eli Freese.
Inspection completed with John Linhart present.
Intent to suspend permit issued for door leading onto patio not self-latching properly. Correct within 30 days or permit may be suspended.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed hand rail loose. Repair.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed door leading onto patio not self-latching properly. Intent to suspend permit issued. Correct within 30 days.
Sep 6, 2023 10 demerits · 2 violations
Inspector comments: Inspection completed with John Linhart present.
Immediate suspension issued for chlorine at 0.0ppm.
Correct and contact Eli Freese at 704.621.2298 to reopen pool.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Observed no chlorine in water. No chlorine tablets on site for erosion feeder. Permit suspended.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed door at back of pool leading to parking garage not self-latching. Observed pool from gym self-closing but not adequately audibly alarmed. Intent to suspend item.
Mar 2, 2023 14 demerits · 3 violations
Inspector comments: Inspection completed with John Linhart and David Timchula present.
Note: Observed 1 underwater light not completely flush with wall. E. Freese will make return visit in 30 days to ensure light has been repaired in such a way that it is flush with wall or more secured. An intent to suspend the permit may be issued if not corrected within 30 days.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.0. CDI- adjusted to 7.2.
#4 · Water quality: water temperature of heated pool −6
.2535(12) Maintain pool temperature at 90 F or below. Observed temperature at 91.9. CDI- fresh water added to pool until water temperature was at 90.0F
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Observed water on pump room floor.
Nov 17, 2022 16 demerits · 3 violations
Inspector comments: Inspection completed with David Timchula present.
Intent to suspend permit issued for door leading from pool deck to outdoor patio not self-latching. The facility has also removed their equalizer line coverings and sealed them off on the pool wall. The ports inside the skimmers have not been sealed for the equalizers. Seal off these lines as well. Submit documentation to the health department with updated information for review and approval.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 8.0. CDI- adjusted to 7.2.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Observed rope at 50 feet. CDI- adjusted to 24 feet.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed door leading onto outdoor patio from pool deck not self-latching. Intent to suspend issued. Correct within 30 days.
Jan 11, 2022 6 demerits · 2 violations
Inspector comments: Inspection completed with David Timchula and Bryan Todd present. No signature due to COVID.
Observed grounding wire detached from pump during inspection. Wire was reaffixed by end of inspection.
Observed pool plaster corroding/pitting at bottom of pool. Repair/replaster pool within within 1 years time (by 1/11/2023).
Intent to suspend permit issued for door audible alarm not loud enough to be heard when entering pool. Correct within 30 days by 2/10/2022.
Inspection conducted by Anna Ortiz with E. Freese present.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed non-functional audible alarm on door that leads directly onto pool deck. Intent to suspend the permit issued. Repair within 30 days.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. Observed inadequate ventilation in chemical/pump room.
Sep 21, 2021 10 demerits · 2 violations
Inspector comments: Inspection completed with Bryan Todd present. No signature due to COVID.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed emergency phone non-operational. CDI- phone was replaced, second phone in compliance.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed stuck flow meter.
Jan 7, 2021 16 demerits · 4 violations
Inspector comments: Inspection completed with Eddie Anguisaca present. No signature due to COVID-19.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Observed one door leading onto pool deck not self-latching. CDI- door was repaired.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Observed chairs within 5 feet of edge of pool. CDI- chairs were relocated to provide 5 feet of walking space.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed 911 operator could not hear EHS. CDI- phone replaced.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. Observed inadequate ventilation in chemical/pump room.
Sep 17, 2020 4 demerits · 1 violation
Inspector comments: Inspection completed with Tyrone Davis. No signature due to COVID-19.
General comment: Observed some days missing recordings in log book. Ensure log book is filled out daily, including weekends.
ITS issued for one door not self-latching. Repair by October 17, 2020 or permit may be suspended.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed door that leads directly onto pool deck not self-latching. Intent to suspend the permit issued. Repair within 30 days.
Mar 10, 2020 6 demerits · 1 violation
Inspector comments: NOTE: EQUALIZER LINE COVERINGS (2) AQUASTAR 6HPxxx expire on December 2020. Replace and re-submit new PDSC form to health department to remain in compliance.
GENERAL COMMENT: Observed one chair within 3 feet of walking space around pool deck. Maintain 5 foot of walking space around pool perimeter.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length. Observed ring buoy not connnected to throw rope. CDI- rope was connected.
Nov 1, 2019 6 demerits · 2 violations
Inspector comments: PDSC information verified in-field.
Note: equalizer line coverings expire in December 2020.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
.2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. Observed inadequate amount of chlorination equipment (one salt cell) connected to pump with no additional equipment for chlorine dispensing. Facility must be able to provide 5.07 pounds/day of chlorine generation. ITS issued.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Observed no force or cross ventilation in pump room.
Feb 18, 2019 14 demerits · 4 violations
Inspector comments: Pool has HP6 EQ covers. Aquastar has changed the flow rating for this cover to 92GPM on the wall. The previous flow rate was 224GPM. The pump flow rate for this pool (Pentair Challenger CHII-N1-2F, 2HP) is 139GPM. The HP6 covers expire in December 2020. The new covers must be flow rated to handle the pump flow rate.
This pool has 2 insignias, one on the top tread of the stairs and another on the bottom of the pool. It has been determined that some types of insignia, based on color, size, and placement, require removal under State law. This insignia will be evaluated and if the removal of the insignia is required, the Health Department will let the facility know.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed sand on the pool floor. This is not currently a hazard, but may indicate a problem with the sand filter. Have the filter system evaluated for problems. Keep the pool floor clean. No permit action taken.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed 1 eyeball fitting missing the nozzle. Repair the fitting. No permit action taken.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
OBSERVED DOOR ALARM SWITCHED OFF/NON-FUNCTIONAL. DOOR MUST HAVE AUDIBLE ALARM AS IT DOES NOT SELF-LATCH. ALARM WAS SWITCHED ON. -C.D.I. THIS IS A REPEAT VIOLATION FROM THE PREVIOUS INSPECTION. ENSURE THAT THE DOOR ALARM IS KEPT FUNCTIONAL.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at the backwash line.
Nov 5, 2018 6 demerits · 2 violations
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
OBSERVED DOOR ALARM SWITCHED OFF. DOOR MUST HAVE ALARM AS IT DOES NOT SELF-LATCH. ALARM WAS SWITCHED ON. -C.D.I.
#27 · Equipment room: filter backwash discharged through an air gap −2
OBSERVED NO AIR GAP AT BACKWASH LINE.
Jan 31, 2018 20 demerits · 5 violations
#4 · Water quality: water temperature of heated pool −6
Observed temperature to be 91.1F in heated pool. Temperature shall not exceed 90F Cold water was introduced, corrected to 89.9F. C.D.I.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed a few gaps in daily record data. Ensure daily checks and records are properly kept. •
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed door not alarmed as required. Observed other door not fully self latching. C.D.I. Alarm was activated and other door was repaired.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed items to be closer than 5 feet to the water. Items were moved back. C.D.I.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at backwash line.
Oct 19, 2017 8 demerits · 3 violations
Inspector comments: Pool has 2 Paramount SDX Retro main drain covers. These will expire August 2018. These must be replaced before they expire. Once they are replaced an, updated PDSC sheet must submitted to the Health Department.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed door from gym to be self-closing, but not self latching. Doors onto the pool deck must be self-closing/self latching, or have an audible alarm that sounds upon the door opening to alert that the door has been opened. -I.T.S. Issued. Correct the door.
This shall be corrected before 11/19/17.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed chemicals stored in pump room instead of in separate chemcial room.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed backwash not to have an air gap.
Jun 26, 2017 12 demerits · 3 violations
Inspector comments: 22) EHS observed static while conducting an emergency test call. However EHS was able to confirm correct address and phone number for the location.
Bryon and Gabriel Bermeo were present during the inspection.
#2 · Water quality: disinfectant residual provided by −6
Observed Cl at 0.6 PPM. CDI- CPO brought Cl to 4.0 PPM before the inspection was over.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed a loose hand rail. Tighten this item.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed a large storage container for vacuum equipment less than 5FT from the pools edge. Also observed chairs less than 5FT from the pools edge. CDI- CPO moved all items to 5FT away from the pools edge.
Dec 16, 2016 28 demerits · 6 violations
#3 · Water quality: pool water pH −6
Observed pH to be 8.1. pH shall be 7.2-7.8 to be in required safe range. Corrected pH to 7.5. -CDI
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed 1 broken eyeball return fitting. Repair it.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed buoy rope to be 20ft. long. Rope corrected to 24ft. -CDI
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck must have 5ft of clear space. Items were too close to water. Items were moved. -CDI
#22 · Premises: emergency telephone provided −6
Observed 911 phone non-functional. 911 Phone must work properly. -CDI Phone was corrected.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at back wash line.
Jun 30, 2016 6 demerits · 1 violation
Inspector comments: #5: General Comment: Add cyanuric acid to log. Check CA weekly
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy is not USCG approve (Torn Strap) Reeplaced during inspection.
Dec 17, 2015 24 demerits · 6 violations
Inspector comments: Immediate Suspension issued for #3 & #22.
Pool cannot be re-opened without written approval from the Mecklenburg County Health Department.
#3 · Water quality: pool water pH −6
Observed pH @ 8.0. ** Maintain 7.2 to 7.8.
Immediate Suspension (IS)
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Planters as close as 3' & deck chairs as close as 3.5' from pool edge. ** Maintain 5' of clear walking space.
#22 · Premises: emergency telephone provided −6
Only high pitched noise heard when emergency phone handset lifted. Call did reach 911 (front desk called back by 911), but EHS could not hear 911 operator.
** Resolve. (IS)
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter float stuck. ** Keep operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No natural cross draft or forced air ventilation in equipment/ chemical room. ** Provide.
#27 · Equipment room: filter backwash discharged through an air gap −2
Backwash pipe extends down into sump.
** Provide complete air gap.
Jun 30, 2015 26 demerits · 7 violations
Inspector comments: #30 Hose bib in equipment/ chemical room needs vacuum breaker.
Note: SDX Retro equalizer line covers installed with risers. Environmental Health Specialist to verify if riser rings need to be removed.
#3 · Water quality: pool water pH −6
Observed pH @ 8.0. ** Maintain 7.2 to 7.8. Pool closed & pH lowered to 7.6 while on-site.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No entries on pool record for 6/8, 6/18, 6/19 & 6/28.
** Maintain complete pool records. Check & record daily. If pool is closed indicate such on record.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed scum on pool wall tiles. ** Clean.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Planters ~3.5' & some chairs ~4' from pool edge.
** Maintain 5' of clear walking space.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter float stuck. ** Corrected during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No cross or forced air ventilation in equipment / chemical room.
#27 · Equipment room: filter backwash discharged through an air gap −2
Backwash pipe extends into sump. ** Provide complete air gap.
Dec 2, 2014 28 demerits · 6 violations
#2 · Water quality: disinfectant residual provided by −6
Observed chlorine residual to be .6ppm. Chlorine must be at least 1.0ppm -IS- issued.
#3 · Water quality: pool water pH −6
•Observed pH to be 6.9. pH must be within the range of 7.2-7.8. -IS- Issued.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
I Observed doors leading to the outside patio to not be self closing, self latching at the time of inspection. These doors must self close and self latch or they must remain locked due to the fact that the outside fence for the patio does not meet the minimum standards for pool fencing and gates. -CDI- The doors were locked.
#22 · Premises: emergency telephone provided −6
Observed the ER phone not to work properly. The 911 operator could be heard, but could not hear the caller. -IS- issued.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck. Repair it.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed the hot water in the Men's bathroom shower to reach at least 114F. The hot water shall reach no higher than 110F.
Feb 26, 2014 0 demerits · 0 violations
No violations were recorded for this inspection.
Dec 12, 2013 6 demerits · 1 violation
#22 · Premises: emergency telephone provided −6
PHONE NOT WORKING; REPAIRED DURING OSV
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “RENAISSANCE CHARLOTTE SOUTHPARK” or State ID 2060530065). Inspection type (routine vs. follow-up) is not published in the county's data.