16demerits

SAGEWOOD, THE

14325 PLANTATION PARK BLVD, Charlotte, NC 28277
Year-Round Swimming Pool · NC permit/State ID 2060530115
Latest result16 demerits
Last inspectedAug 25, 2026
Inspections on record26
On record sinceJul 18, 2013

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01632 Jul 18, 2013: 26Jun 4, 2014: 22Oct 28, 2014: 12Jun 4, 2015: 0Oct 16, 2015: 8Mar 1, 2016: 10Oct 30, 2017: 26May 10, 2018: 28Aug 20, 2018: 20Feb 26, 2019: 22Jul 30, 2019: 16Mar 10, 2020: 8Aug 12, 2020: 16Apr 6, 2021: 10Oct 4, 2021: 24Feb 2, 2022: 32Jun 13, 2022: 26Aug 8, 2022: 32Mar 20, 2023: 28Aug 2, 2023: 24Apr 23, 2024: 16Dec 5, 2024: 16Apr 16, 2025: 26Oct 8, 2025: 26May 13, 2026: 18Aug 25, 2026: 16
Jul 18, 2013Lower is betterAug 25, 2026

Inspections & violations

Aug 25, 2026 16 demerits · 4 violations
Inspector comments: Inspection conducted with operators. Pool remains in good standing and on A status. Permit Restriction: Flow meter must remain operable. Flow required at least 120 gpm for turnover. Const. Date: 8/27/1999 Rope Length: 35' Night Swim?: N
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity. Some records missing from the end of July. All records missing from August. Operator found missing records in office. No permit action.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment should be conspicuously and conveniently located. Body hook not easily accessible or visible. Operator corrected. No permit action. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope less than approved 35ft due to knot. Operator untied and corrected. No permit action.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operable at time of inspection. Operator corrected and new reading shows 100gpm. Ensure flow on pump is at least 120 gpm for turnover. No permit action. .2518(g) Keep flow meter operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room in above ground vault, difficult to access. Built in 1999. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Not able to easily access pool equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Pump room and chemical storage room vaults unlocked. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. Chemical storage in a small plastic shed. .2534(1) Chemical storage room shall be weatherproof with a minimum ceiling height of 7 ft. No forced ventilation in above ground vault. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.

View this inspection on the county portal ›

May 13, 2026 18 demerits · 4 violations
Inspector comments: Inspection conducted with CPO Richard Dungan. Permit suspended for emergency phone not operational to receive calls. All other 6 point items and flow meter corrected during the inspection. Contact Kurtis Nelson (980) 378-7896 for re-inspection once issues have been corrected. Flow meter must remain operable. Flow required at least 120 GPM for turnover.
#3 · Water quality: pool water pH −6
Observed pH at 6.8. Adjusted to 7.3 onsite. CDI .2535(1) Maintain pH at 7.2 to 7.8.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone. Emergency phone can not receive calls. Immediate suspension item.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operable at time of inspection. Flow restriction on pump must be at least 120 gpm for permit restriction. .2518(g) Keep flow meter operational. Flow meter fixed and operational during inspection. CDI
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room in above ground vault, difficult to access. Built in 1999. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Leak at filter, filter partially underwater. .2533(d) Pump room floor shall be kept dry and free of standing water. Not able to easily access pool equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Pump room and chemical storage room vaults unlocked. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator.

View this inspection on the county portal ›

Oct 8, 2025 26 demerits · 8 violations
Inspector comments: Inspection conducted with maintenance staff Guy DeBrosse. Facility does not currently have a night swimming permit. Will need to schedule a night lighting inspection prior to opening the pool at night. Immediate suspension issued 3) Contact Will Harrison (704) 507-6824 for re-inspection once issues have been corrected.
#3 · Water quality: pool water pH −6
PH 6.9. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No records, CPO took them home with him. Records must be kept on site and readily available. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity. - Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Escutcheon plates missing from handrails. .2521 Install handrails per manufacturer instructions.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gap > 4” through bottom of fence section. .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Foothold near pool pump vault. .2528(a) Maintain 30" between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010). 3-4” gaps under gates. .2528(a) Maintain 2" or less under gates. - Intent to suspend item. Double doors to clubhouse open with a motion sensor. .2537(b) All gates and doors shall be self-closing, self-latching. - Intent to suspend item.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operable at time of inspection. Flow restriction on pump must be at least 120 gpm for permit restriction. .2518(g) Keep flow meter operational. - Intent to suspend item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room in above ground vault, difficult to access. Built in 1999. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. Leak at filter, filter partially underwater. .2533(d) Pump room floor shall be kept dry and free of standing water. Not able to easily access pool equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Pump room and chemical storage room vaults unlocked. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Some valves and piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One faucet not working in men’s restroom. .2526(m) Keep restrooms and fixtures clean and in good repair.

View this inspection on the county portal ›

Apr 16, 2025 26 demerits · 7 violations
Inspector comments: Immediate suspension issued for water quality. Pool must remain closed with “Pool Closed” signs posted at all bather entrances until suspension is lifted by health department. Contact Marie Daley at 704-507-6806 when pool is in compliance to lift suspension. Other permit items to verify on return visit include records, horizontals less than 30” and flow meter. “E” Immediate Suspension status Inspection with Victor Romero
#3 · Water quality: pool water pH −6
Observed pH at 6.8. .2535(1) Maintain pH at 7.2 to 7.8. *Immediate suspension
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Main drain checks not on records at time of inspection. Missing weekly cyanuric acid and alkalinity. No maintenance recorded. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. *Permit item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir installed backwards. .2518(k) Replace missing weirs. Install correctly. Operator adjusted and corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Top tread missing slip resistant strip on ladder. .2521(b) Ladders shall have slip-resistant tread.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Brick wall less than 30"in height creating horizontal by restroom door. Brick wall and outlet box by garage less than 30" in height. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010). *permit item for horizontal
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operable at time of inspection. Flow restriction on pump must be at least 120 gpm for permit restriction. .2518(g) Keep flow meter operational. *Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large plastic pieces outside. There are vats of liquid chemical in plastic storage container. No walking space/clearance. Pump and chemicals not locked at time of inspection. Pool built '99. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up.

View this inspection on the county portal ›

Dec 5, 2024 16 demerits · 3 violations
Inspector comments: Issued immediate suspension for inoperable emergency phone. Pool must remain closed until emergency phone is repaired. Call James Bjorneboe at 704-507-6820 once repairs have been made and to schedule re-inspection.
#3 · Water quality: pool water pH −6
Observed pH at 6.8. Adjusted to 7.2 onsite. .2535(1) Maintain pH at 7.2 to 7.8.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed excessive leaves in skimmers. Keep skimmers free of debris. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
#22 · Premises: emergency telephone provided −6
Observed emergency phone inoperable at time of visit. Repair. .2530(f) Pool telephone shall be capable of directly dialing 911 or another emergency notification system.

View this inspection on the county portal ›

Apr 23, 2024 16 demerits · 5 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
MAINTAIN WEEKLY CYA RECORDS
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
LADDER NEAR OFFICE MISSING ANTI-SLIP RUBBER ON TOP STEP
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
RING BUOY GRAB ROPE IN DISREPAIR -- REPLACE W/IN 1 WEEK
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
NO PAPER TOWELS IN MENS ROOM
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
EQUIPMENT AND CHEMICALS STORED IN OUTDOOR ENCLOSURES -- POOL BUILT IN '99

View this inspection on the county portal ›

Aug 2, 2023 24 demerits · 7 violations
Inspector comments: 30 Day Intent to Suspend (ITS) issued for records, weirs and inlet fittings. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS. No Night Swimming
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records not being kept at time of visit. Last entry July 14, date of inspection Aug 2. .2535 (11) The pool operator shall inspect the pool at least daily and maintain written records. Will check on return visit. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. *Permit item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some skimmers with debris at time of inspection. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator emptied baskets and corrected. Multiple weirs missing. .2518(k) Replace missing weirs. *Permit item
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Top tread missing slip resistant strip on ladder. .2521(b) Ladders shall have slip-resistant tread.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gap under fencing by grill area greater than 4”. Brick wall less than 30"in height creating horizontal by restroom door. Brick wall and outlet box by garage less than 30" in height. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010). .2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010).
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Lighting fixture detached from pool wall, protruding causing hazard..2524(c) Lighting fixtures shall not present a hazard to the public. *Permit item
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Inlet fitting missing at stairs and not circulating water. Fitting at bottom of pool by main drains missing. .2518(i) Arrange inlets to produce uniform circulation. *Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large plastic pieces outside. Dry bags of chemicals stored on floor under plastic rock with vats of liquid chemical. No walking space/clearance. Pump and chemicals not locked at time of inspection. Pool built '99. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up.

View this inspection on the county portal ›

Mar 20, 2023 28 demerits · 9 violations
Inspector comments: 30 Day Intent to Suspend (ITS) for records and replace missing fitting. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS. Establishment no longer wishes to have night swimming. Night swimming approval expired. New visit required before dawn or after dusk to permit night swimming. Note: Deck starting to crack by entry ladder, offset not currently greater than 1/2”. Some plaster chipping at deep end. Monitor these areas to ensure it does not worsen. If it worsens, permit action may be taken in future.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Main drain checks not on records at time of inspection. Missing weekly cyanuric acid. No maintenance recorded. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. *Permit item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some skimmers with debris at time of inspection. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator emptied baskets and corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail at entry not secure. .2521 Install ladders per manufacturer instructions.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Brick wall less than 30"in height creating horizontal by restroom door. Brick wall and outlet box by garage less than 30" in height. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010).
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs within 6' of pool at time of inspection. .2522(a) Provide 6 ft of clear walking space around the pool at all times. Operator moved and corrected.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Inlet fitting missing at stairs and not circulating water. .2518(i) Arrange inlets to produce uniform circulation. *Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large plastic pieces outside. Dry bags of chemicals stored on floor under plastic rock with vats of liquid chemical. No walking space/clearance. Pump and chemicals not locked at time of inspection. Pool built '99. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Glass soap dispenser at sink in restroom. .2526(j) Provide soap and soap dispenser, no glass, at each sink.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No backflow prevention device on spigot at shower. Provide backflow prevention device

View this inspection on the county portal ›

Aug 8, 2022 32 demerits · 8 violations
Inspector comments: Immediate suspension issued for chlorine. Pool MUST REMAIN CLOSED until suspension is lifted by Health Dept. Contact Marie Daley at 704-507-6806 to lift suspension when in compliance. Other items to verify: flow meter operable and set at 120 gpm, inlet fitting replaced, light fixture secured to wall and records
#2 · Water quality: disinfectant residual provided by −6
Chlorine 0 ppm at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm. Immediate suspension item.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records not being kept on weekend at time of visit. .2535 (11) The pool operator shall inspect the pool at least daily and maintain written records. Will check on return visit.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Chairs blocking body hook and buoy at time of inspection. Keep accessible. .2530(a) Lifesaving equipment should be conveniently located. Operator moved chairs for accessibility and corrected. Rope detached from buoy and not correct length. .2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Operator reattached and cut to 35’. Corrected
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs within 6' of pool and 5’ of handrails at time of inspection. .2522(a) Provide 6 ft of clear walking space around the pool at all times. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. Operator moved and corrected.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Lighting fixture detached from pool wall, protruding causing hazard., .2524(c) Lighting fixtures shall not present a hazard to the public. Will verify at return visit
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operable at time of inspection. Flow restriction on pump must be at least 120 gpm for permit restriction. .2518(g) Keep flow meter operational. Inlet fitting missing by stairs. .2518 Replace missing inlet fittings. *Will verify at return visit
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large plastic pieces outside. No walking space/clearance. Chemicals stored in garage with no ventilation. Pump not locked at time of inspection. Pool built '99. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No backflow prevention device on spigot at shower. Provide backflow prevention device

View this inspection on the county portal ›

Jun 13, 2022 26 demerits · 8 violations
Inspector comments: Permit restriction flow meter must remain operable and at least 120 GPM. Contrasting color bands more than 1 inch from pool wall in some areas. This is permissible per pool seniors Christopher Sells at this time, but if changes are made must bring up to code. Lack of severity does not warrant permit action at this time. No night swimming. If Night swimming is requested send verification of lighting that matches on site visit previously made. Issued local permit sticker. Changed status to “A” open for business. Inspection with Lucy Bullock and Mark McCaskill
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Main drain checks not on records at time of inspection. Missing weekly total alkalinity and cyanuric acid. Records missing daily records. Pool closed at time of inspection., .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added column for main drain check and corrected other readings.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir stuck at time of inspection. Keep in good repair. .2518(k) Replace missing weirs. Operator corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Brick wall less than 30"in height creating horizontal by restroom door. Brick wall and outlet box by garage less than 30" in height. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010). Door from clubhouse onto pool deck not self-latching or alarmed at time of inspection. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Operator adjusted and corrected.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs within 6' of pool and 5’ of handrails at time of inspection. .2522(a) Provide 6 ft of clear walking space around the pool at all times. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. Operator moved and corrected.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operable at time of inspection. Flow restriction on pump must be at least 120 gpm for permit restriction. .2518(g) Keep flow meter operational. Operator corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large plastic pieces outside. No walking space/clearance. Chemicals stored in garage with no ventilation. Pump not locked at time of inspection. Pool built '99. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Shower spraying out side of pipe. Keep in good repair.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No backflow prevention device on spigot at shower. Provide backflow prevention device

View this inspection on the county portal ›

Feb 2, 2022 32 demerits · 9 violations
Inspector comments: ITS for records/cyanuric acid checks and reagent. Main drains expire 2/20/2022. Failure to submit updated PDSC for approval and change covers prior to expiration will result in IMMEDIATE SUSPESNION of permit. Operator stated there are plans to replaster pool. Advised a general In-Field plan review application should be submitted with LRV information and scope of work for approval. Also, plugging and disabling equalizer lines per State recommendations is an option during this process, but MUST be reflected on updated and approved PDSC form. VFD was changed out in 2021. There is not an electrical permit pulled for this project. Referring to Code Enforcement for approval of work. VFD was set at 50 HZ at time of inspection. Permit restriction requires 60 HZ. Flowmeter over 120 gpm. Operator manually adjusted to 55 HZ, but it would not go further (to reach 60 HZ). Flow meter reading 160 gpm at 55 HZ. Following up with Katie Rudisill to possibly change permit restriction on required speed to required turnover. Chlorinator sometimes shuts off due to electrical issue (gfci switch). Advised monitoring issue to address. No Night Swimming (lights not verified). Changed to "W" Intent to Suspend Inspection with Antoine Caldwell No signature due to COVID
#2 · Water quality: disinfectant residual provided by −6
Chlorine 0.2 ppm at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm. Operator turned on chlorinator and corrected to 1.5 ppm.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Cyanuric acid checks missing on records. No cyanuric acid reagent or test strip to test. .2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. *Intent to Suspend (ITS) item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some skimmers with debris at time of inspection. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator emptied baskets and corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Bottom tread missing slip resistant strip on ladder. .2521(b) Ladders shall have slip-resistant tread.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Chairs blocking body hook at time of inspection. Keep accessible. .2530(a) Lifesaving equipment should be conveniently located. Operator moved chairs for accessibility and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One gate not latching at time of inspection. .2537(b) All gates and doors shall be self-closing, self-latching. Operator adjusted to self-close, self-latch. Corrected. Brick wall less than 30"in height creating horizontal by restroom door. Brick wall and outlet box by garage less than 30" in height. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010). Landscaping shortening height of old fence by restroom entrance corner less than 48. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large plastic pieces outside. No walking space/clearance. Chemicals stored in garage with no ventilation. Pool built '99. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Women's restroom out of order at time of inspection. No supplies at handsink and toilet out of order. .2526(f) At least two sinks and two toilets required for women's restroom. .2526(j) Provide soap and soap dispenser, no glass, at each sink. .2526(m) Keep restrooms and fixtures clean and in good repair.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No backflow prevention device on spigot at shower. Provide backflow prevention device

View this inspection on the county portal ›

Oct 4, 2021 24 demerits · 7 violations
Inspector comments: ITS for records and fence 48" in height. "W" Status. General Comment: Pool signage with "Adults should not swim alone." and "Children should not use the swimming pool without adult supervision" 1" in height, starting to peel. Recommended replacing before illegible. Ensure all signage rules and letting height/exact wording are in compliance for sign. Send to Marie Daley at marie.daley@mecknc.gov if there are questions for approval Another sign still meets compliance. The VFD remains at 58 HZ and flow meter reading about 190 gpm at time of inspection. Pump meeting minimum turnover and no apparent suction hazard. Permit restriction outlines 60 HZ. Advised adjusting, but did not take permit action. Main drains expire Feb 2022. Replace and submit updated PDSC form prior to expiration to avoid permit action CPO updated to Antoine Caldwell Unable to verify lighting. No Night Swimming unless verification is sent to Marie Daley at 704-507-6806 Inspection with Julius Dennis No signature due to COVID
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Main drain check not on records at time of inspection. Records missing daily records. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added column for main drain check and corrected. *Issued 30 Day Intent to Suspend (ITS) Will return to verify daily records
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Bottom tread missing slip resistant strip on ladder. .2521(b) Ladders shall have slip-resistant tread.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope detached from buoy at time of inspection. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator tied rope onto buoy, secured and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Brick wall less than 30"in height creating horizontal by restroom door. Brick wall and outlet box by garage less than 30" in height. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010). Landscaping shortening height of fence by grill area less than 48. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. *ITS item
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs within 6' of pool at time of inspection. .2522(a) Provide 6 ft of clear walking space around the pool at all times.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large plastic pieces outside. No walking space/clearance. Water under pump. Chemicals stored in garage with no ventilation. Pool built '99. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft..2533(d) Pump room floor shall be kept dry and free of standing water. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. Dry chemicals in same area as liquid vats of acid and chlorine. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Operator moved dry chemicals. Corrected.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No backflow prevention device on spigot at shower. Provide backflow prevention device

View this inspection on the county portal ›

Apr 6, 2021 10 demerits · 3 violations
Inspector comments: 18) Pool signage with "Adults should not swim alone." and "Children should not use the swimming pool without adult supervision" 1" in height, starting to peel. Recommended replacing before illegible. Ensure all signage rules and letting height/exact wording are in compliance for sign. Send to Marie Daley at marie.daley@mecknc.gov if there are questions for approval Unable to verify all lighting. One pool light not coming on. Some outer lights not able to come on due to sensor. Send lighting of pool at night for Night Swimming verification to Marie Daley at 704-507-6806 to approve Night Swimming for permit. Onsite visit was made 2020 with documentation. Issued local permit sticker Variable speed drive must remain at 60 HZ with required 120 gpm for turnover. Keep flow meter operational. No Night Swimming. Inspection with Bechord Walcott No signature due to COVID
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Main drain check not on records at time of inspection. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added column for main drain check and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Brick wall less than 30"in height creating horizontal by restroom door. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010).
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large plastic pieces outside. No walking space/clearance. Chemicals stored in garage with no ventilation. Pool built '99. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.

View this inspection on the county portal ›

Aug 12, 2020 16 demerits · 5 violations
Inspector comments: 30 Day Intent to Suspend (ITS) for doors onto pool deck self-closing, self-latching or audible alarm. Contact Marie Daley at 704-507-6806 when corrected to lift ITS. CPO updated to Bechord Walcott, expires 2023 No signature due to COVID-19 Report to: Plantation Park Maintenance ; Plantation Park Assistant Manager
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Main drain check not on records at time of inspection. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added column for main drain check and corrected.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Overflow grate cracked on pool wall. Keep in good repair.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Bottom tread missing slip resistant strip on ladder. .2521(b) Ladders shall have slip-resistant tread.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door onto pool deck by restrooms not self-latching or alarmed at time of inspection.* Door also propped open for restroom entry at time of inspection. Brick wall less than 30"in height creating horizontal. One gate swinging in toward pool due to stairs. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool..2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010). *ITS item-doors onto pool deck
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large plastic pieces outside. No walking space/clearance. Chemicals stored in garage with no ventilation. Pool built '99. .2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.

View this inspection on the county portal ›

Mar 10, 2020 8 demerits · 3 violations
Inspector comments: ITS for doors self-closing, self-latching or audible alarm. Night Swimming will NOT be permitted without visit before dawn or after dusk to verify adequate lighting. Contact Marie Daley at 704-507-6806 to schedule. "W" Intent to Suspend status.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Bottom tread missing slip resistant strip on ladder. .2521(b) Ladders shall have slip-resistant tread.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Doors onto pool deck not self-latching or alarmed at time of inspection. Brick wall less than 30"in height creating horizontal. One gate swinging in toward pool. Pool built 99. .2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. .2528(b) Maintain between 30" or greater between bottom horizontal and next horizontal on fence and/or gate (pre-May 2010). *30 Day Intent to Suspend (ITS) item. Contact Marie Daley at 704-507-6806 when corrected to lift ITS.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large plastic pieces outside. Dry chemicals on ground by lagre vats of liquid chemicals. Store and maintain chemicals and equipment as outlined in .2533 and .2534. Pool built prior to 2010. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up.

View this inspection on the county portal ›

Jul 30, 2019 16 demerits · 5 violations
Inspector comments: CPO updated, Michael David (Dave) Belue, certificate #:631710/1
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Cyanuric acid not recorded weekly at time of inspection (some calcium checks). .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator checked and recorded. Corrected.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One weir missing at time inspection. .2518(k) Replace missing weirs. Lack of severity did not warrant permit action. Operator is purchasing and sending verification to Marie Daley at 704-507-6806.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not working at time of inspection. .2518(g) Keep flow meter operational. Operator repaired to work. Corrected.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Pipes missiing some labels. .2518(d) Piping and valves shall be labeled with color codes or labels.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No backflow prevention device on spigot at shower. Provide backflow prevention device

View this inspection on the county portal ›

Feb 26, 2019 22 demerits · 5 violations
Inspector comments: Immediate suspension for skimmer equalizer cover missing (suction hazard) and water quality. Contact Marie Daley at 704-507-6806 to lift suspension when corrected to lift suspension. Pool may not open until suspension lifted by EHS. Deck amenities may remain open and available to residents. Placed in "E" Immediate Suspension status. CPO updated, Santiago Hernandez Diaz Expires 4/10/23 Unable to check lighting for night swimming at time of inspection. Will follow up on this item.
#3 · Water quality: pool water pH −6
pH less than 6.8 at time of inspection. .2535(1) Maintain pH at 7.2 to 7.8. **Immediate suspension item. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records in online system show entries for pool data days after due. Records inconsistent with observed pool water quality and drains on day of inspection (pH less than 6.8, records display 7.5, records indicate main drain checks, cover missing) .2535 (11) The pool operator shall inspect the pool at least daily and maintain written records. *Intent to Suspend item
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Skimmer equalizer cover missing at time of inspection. (Aquastar 8 HP, no longer manufacturered. Operator stated he would replace with 6 HP in mudring. Contact Katie Wilson or Chris Sells to discuss options for approval and replacement. .2537(7) Drain covers shall be in good condition and securely attached. Submit paperwork. .2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7. .2539(d) All drain covers shall be kept in good condition. Missing, broken, or cracked fittings shall be replaced or reattached before the pool should be used. **Immediate suspension item. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Variable speed set at 49 HZ at time of inspection. Permit restriction "Variable Speed Drive Set At 60 Hz" .2518(h) Provide approved pump in good repair. Flow meter not operable at time of inspection. .2518(g) Keep flow meter operational. **Intent to Suspend items
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No backflow prevention device on spigot at shower. Provide backflow prevention device

View this inspection on the county portal ›

Aug 20, 2018 20 demerits · 5 violations
Inspector comments: ITS items chairs 6', doors/gates self-closing self latching and records. Immediate suspension for water quality.
#3 · Water quality: pool water pH −6
pH 7.0 at time of inspection. Maintain pH between 7.2 and 7.8. Immediate Suspension. Contact Marie Daley at 704-507-6806 to lift IS when water quality is within range.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Establishment now using online records. No field for Total Alkalinity or Cyanuric Acid checks. Provide record keeping including daily records of disinfecant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. **30 Day ITS item
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Single door from clubhouse onto pool deck not self-latching. Ground level doors shall be self-closing, self-latching or child protected by audible alarm. **30 Day ITS item Gaps greater than 4" under fence by basketball court side and between fencing by mesh fence and pool fence. .2528(b) Maintain no greater than 4" under fence and/or gate (pre-May 2010). .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Pool built prior 2010.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs within 6' of pool. .2522(a) Provide 6 ft of clear walking space around the pool at all times. **30 Day ITS item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large pastic pieces outside. Store and maintain chemicals and equipment as outlined in .2533 and .2534. Pool built prior to 2010. Pump under plastic piece, unlocked. Keep locked.

View this inspection on the county portal ›

May 10, 2018 28 demerits · 7 violations
Inspector comments: Permit issued. No Night Swimming (close at dusk)
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Daily records missing main drain checks. Provide record keeping including daily records of disinfecant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added main drain column and checked. Corrected.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope 37'. Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Corrected length 35'. Corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Single door from clubhouse onto pool deck not self-latching due to sensor on inside allowing door to freely open. Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Operator turned off sensor to allow door to self-close, self-latch. Corrected. **Note: New fencing has been installed with mesh 2.25"X2.25" (inside measurement) over old fence behind grill area. Renovation completed at time of May 2018 visit. This fencing must continue to meet compliance with .2528.
#22 · Premises: emergency telephone provided −6
Emergency telephone phone number posted was incorrect at time of inspection. Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Operator corrected number.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Provide spare pump basket (Whisperflo XFK-20 5HP). Operator ordered at time of inspection and sending verification.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Equipment and chemicals stored under large pastic pieces outside. Store and maintain chemicals and equipment as outlined in .2533 and .2534. Pool built prior to 2010.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Piping not clearly labeled at time of inspection. Keep clearly identified. Operator corrected.

View this inspection on the county portal ›

Oct 30, 2017 26 demerits · 6 violations
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Construction has been done. New pump installed (Pentair Whisperflo XFK-20 5HP) and piping, no paperwork available. Submit PDSC form and ensure no suction hazard exists.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One weir missing. Replace with functional weir.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One gate opens toward pool (appears to have been changed from opening outward). Gates should open away from pool. Stairs may be reason why this is installed this way. Will verify. Construction was done, remvoing fencing and putting in brick wall 34" in height with gas lines creating footholds on end less than 45". Must maintain 48" in height from ground up/from footholds. ** 30 Day Intent to Suspend item
#22 · Premises: emergency telephone provided −6
Emergency telephone not working at time of inspection. Construction is being done and has lines out. **Immediate Suspension issued. Contact Marie Daley at 704-507-6806 when corrected to lift immediate suspension. Pool closed signs posted.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not working at time of inspection. Install functioning flow meter. No spare pump basket. Provide spare pump basket.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
New construction done and no labeling on pipes. Keep clearly identified with main drain, skimmer, vaccum lines and direction of flow.

View this inspection on the county portal ›

Mar 1, 2016 10 demerits · 2 violations
Inspector comments: Immediate suspension issued for number 22.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed minor chipping in deck near ladder. Repair,
#22 · Premises: emergency telephone provided −6
Emergency phone inoperable.

View this inspection on the county portal ›

Oct 16, 2015 8 demerits · 2 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 1 of 4 skimmer baskets in poor repair. Replace.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed minor chipping on pool deck. Repair.

View this inspection on the county portal ›

Jun 4, 2015 0 demerits · 0 violations

No violations were recorded for this inspection.

View this inspection on the county portal ›

Oct 28, 2014 12 demerits · 3 violations
Inspector comments: Immediate suspension issued for #3
#3 · Water quality: pool water pH −6
Pbserved pH at 6.8. pH must be betweeh 7.2 and 7.8
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Maintain daily written records for water quality. Observed past several days missing.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed two ladders missing tread. Replace missing tread.

View this inspection on the county portal ›

Jun 4, 2014 22 demerits · details not yet loaded

Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.

Jul 18, 2013 26 demerits · details not yet loaded

Violation details for this inspection are not yet loaded on this site. We're still importing older records — check the official county portal for the full report.

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “SAGEWOOD, THE” or State ID 2060530115). Inspection type (routine vs. follow-up) is not published in the county's data.