‹ Back to search

20demerits

QUALITY SUITES

9840 PINEVILLE-MATTHEWS ROAD, Pineville, NC 28134
Year-Round Swimming Pool · NC permit/State ID 2060530125
Latest result20 demerits
Last inspectedFeb 10, 2026
Inspections on record25
On record sinceOct 7, 2013

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01938 Oct 7, 2013: 2Feb 5, 2014: 6Nov 4, 2014: 12Feb 19, 2015: 18Feb 25, 2016: 8Dec 16, 2016: 12Jun 22, 2017: 0Nov 8, 2017: 28Jan 31, 2018: 38Nov 7, 2018: 36Mar 27, 2019: 16Nov 19, 2019: 16Mar 23, 2020: 4Nov 3, 2020: 8Jan 13, 2021: 12Sep 21, 2021: 16Jan 20, 2022: 16Nov 8, 2022: 20Mar 21, 2023: 12Nov 7, 2023: 36Mar 27, 2024: 8Oct 10, 2024: 22Mar 10, 2025: 12Nov 6, 2025: 16Feb 10, 2026: 20
Oct 7, 2013Lower is betterFeb 10, 2026

Inspections & violations

Feb 10, 2026 20 demerits · 6 violations
Inspector comments: Issued immediate suspension for water quality. Pool MUST REMAIN CLOSED with signage posted until suspension is lifted by Health Dept. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension. Will verify chlorinator and records at return visit “E” Immediate Suspension status Permit restrictions: Maintain flow between 30-80 gpm. Note: Aquastar dummy cover in place on pool wall Inspection with Ketan Patel
#2 · Water quality: disinfectant residual provided by −6
Chlorine 0 ppm at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm. *Immediate Suspension item
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records missing maintenance when water out of compliance, inconsistent records with actual water quality. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Will check at return visit
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Feeder has been replaced with salt generator and not using tab feeder at time of inspection. Salt generation is not approved as primary chlorination. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. *Permit item Must use approved chlorinator for feeding to pool. The reason tab feeder is no being used per CPO is because of high cyanuric acid levels for indoor pool. Pool using trichloro-s-triazinetrione. Reading label on tablets showed stabilizer in tablets. Discussed using appropriate chlorine tablets (unstabilized,no cyanuric acid) for indoor pool.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Water on floor in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(d) Pump room floor shall be kept dry and free of standing water.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms over 110 degrees F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No floor drains in restrooms. Pool built 2000. .2526(c) Floor drains shall be provided in restrooms.

View this inspection on the county portal ›

Nov 6, 2025 16 demerits · 5 violations
Inspector comments: Issued immediate suspension for water quality. Pool MUST REMAIN CLOSED with signage posted until suspension is lifted by Health Dept. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension. “E” Immediate suspension status Will check records at return visit. At time of visit, old sand filter, Hayward model S244S has been removed and replaced with cartridge filter Hayward W3C3030, pump is same, Hayward SP2607X10. The new cartridge filter design flow is greater than the max flow of pump. This filter better than the previous filter. Heater appears new. Ensure electrical permits have been pulled. Heater should remain off until proper permits are pulled, and heater is approved to avoid electrical hazard. Per owner, permits have been pulled for electrical. Inspection with Ketan Patel
#3 · Water quality: pool water pH −6
PH 8.4 at time of inspection. .2535(1) Maintain pH at 7.2 to 7.8. *Immediate Suspension item.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records missing maintenance when water out of compliance. Total alkalinity should be a number in increment of 10 with correct testing, inaccurate. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Will check at return visit
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Water on floor in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(d) Pump room floor shall be kept dry and free of standing water.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms over 110 degrees F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No floor drains in restrooms. Pool built 2000. .2526(c) Floor drains shall be provided in restrooms.

View this inspection on the county portal ›

Mar 10, 2025 12 demerits · 4 violations
Inspector comments: Verified PDSC information. 2 SDX Retros and equalizer plugged with dummy cover, 6HPHA. Filter changed from Hayward S2445 to Hayward W3C3030 (122gpm). Permit Restriction: Pool flow must be at least 30 gpm for turnover and cannot exceed 80gpm for number of returns. Flow meter must remain operational. Inspection with Aru and Pratik Naik
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records missing maintenance when water out of compliance and daily maintenance of pool. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Lack of severity does not warrant permit action at this time.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
A few chairs within 5' of pool. Moved and corrected. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms over 110 degrees F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F.

View this inspection on the county portal ›

Oct 10, 2024 22 demerits · 6 violations
Inspector comments: Immediate suspension issued for chlorine and PDSC information. Correct items and contact Marie Daley at 704-507-6806 to lift suspension. Pool must remain closed with signage posted until suspension is lifted by Health department. Will verify weirs on return visit Submit PDSC to pdsc@mecknc.gov “E” Immediate suspension item
#2 · Water quality: disinfectant residual provided by −6
Chlorine 0 ppm at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm. *Immediate Suspension item
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Pump on file Hayward Superpump SP2605X7 3/4 pump in equipment room is Hayward W3SP2607X10, 1.1 HP. Submit updated PDSC form for approval. 2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. *Immediate suspension item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir not installed. .2518(k) Provide functional weirs.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms over 110 degrees F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F.

View this inspection on the county portal ›

Mar 27, 2024 8 demerits · 3 violations
Inspector comments: Pool inspection conducted with CPO Patrik Naik. Main drains and equalizer line cover expires 2-12-2025. Prior to expiration, replace with VGBA approved covers and provide updated PDSC form to our office for approval.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir not installed correctly. .2518(k) Provide functional weirs. - Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Heater installed by piping. Must step over pipes to access pump and valves. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Some bags of chemicals stored on the pump room floor. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.

View this inspection on the county portal ›

Nov 7, 2023 36 demerits · 9 violations
Inspector comments: Immediate Suspension (IS) issued for water quality and temperature. Ensure feeder is operating correctly, do NOT hand feed chlorine and contact Marie Daley at 704-507-6806 when in compliance. Pool MUST REMAIN CLOSED with signage posted until suspension is lifted by Health Dept. “E” Immediate Suspension item Other permit items to verify at return visit: records, CPO, doors self-closing, self-latching or alarmed, feeder turns off with pump
#2 · Water quality: disinfectant residual provided by −6
Chlorine 0 ppm at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm. *Immediate Suspension item
#3 · Water quality: pool water pH −6
PH 8.0 at time of inspection. .2535(1) Maintain pH at 7.2 to 7.8. *Immediate Suspension item.
#4 · Water quality: water temperature of heated pool −6
Temperature of pool 99.5 F at time of inspection. .2535(12) Maintain pool temperature at 90 F or below. *Immediate Suspension item
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No active certified pool operator (CPO) for establishment at time of inspection. Per a manger, there is a CPO, but is not on property daily. CPO should be responsible for training staff to ensure pool is maintained daily, including weekends and days CPO is absent. Records not being kept at time of inspection. .2537(c) Pool owner shall provide for the operation and maintenance of the pool by a trained pool operator..2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. .2535 (11) The pool operator shall inspect the pool at least daily and maintain written records *30 Day Intent to Suspend (ITS) item.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Unable to check back door at time of inspection. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. *Will check on return visit. *Permit item
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Feeder not working properly at time of inspection. Also unable to verify feeder shuts off with pump. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. .2535 Automatic acid and chlorine feeders shall be automatically prevented from operating when the circulation pump is not in operation. *30 Day ITS item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms over 110 degrees F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No floor drains in restrooms. Pool built 2000. .2526(c) Floor drains shall be provided in restrooms.

View this inspection on the county portal ›

Mar 21, 2023 12 demerits · 4 violations
Inspector comments: 30 Day Intent to Suspend (ITS) for flow meter. Contact Marie Daley at 704-507-6806 when operational to lift ITS. Note: Records have a line through main drains, but should be a check (as in check main drains are clear and in tact daily). Operator understands and is checking drains, will use correct marking in future. ‘ Inspection with Rudy Dela Torre
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
A few chairs within 5' of pool. Operator moved and corrected. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operational at time of inspection. .2518(g) Keep flow meter operational. *ITS item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Small leak at pipe in pump room. No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(d) Pump room floor shall be kept dry and free of standing water.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No floor drains in restrooms. Pool built 2000. .2526(c) Floor drains shall be provided in restrooms.

View this inspection on the county portal ›

Nov 8, 2022 20 demerits · 6 violations
Inspector comments: Intent to Suspend (ITS) for records, CPO certification, flow meter. Unable to verify door onto pool deck from outside at time of inspection. Will check buoy and door on 11/15. Note: Pump had wire that was not grounded. Operator stated this is not needed for pool. When following other grounded electrical casing, from pump motor, it lead to switch. Unable to verify grounding. Referring to Code Enforcement for further enforcement. Inspection with Hannah Howard and Rudy Ze La Torre
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No certified pool operator (CPO) for establishment at time of inspection. .2537(c) Pool owner shall provide for the operation and maintenance of the pool by a trained pool operator. No records available at time of inspection. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. .2535 (11) The pool operator shall inspect the pool at least daily and maintain written records *30 Day Intent to Suspend (ITS) item. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Beckets around buoy have detached, but are still in working order. .2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. *Allowing 7 days for replacement due to lack of severity. Will verify item on Tues 11/15. Failure to correct will result in permit action.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operational at time of inspection. .2518(g) Keep flow meter operational. *ITS item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms over 110 degrees F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No floor drains in restrooms. Pool built 2000. .2526(c) Floor drains shall be provided in restrooms.

View this inspection on the county portal ›

Jan 20, 2022 16 demerits · 4 violations
Inspector comments: Inspection with Luis Lopez No signature due to COVID
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Buoy rope too long at time of inspection (30'). .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator cut and corrected to 23'.
#22 · Premises: emergency telephone provided −6
Emergency phone not operable at time of inspection. .2530(f) Emergency phone shall remain operable. Operator replaced phone. Phone was coming off hook and busy due to positioning. Operator corrected. Recommended checking emergency phone routinely.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. No backflow prevention on hose bib in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms over 110 degrees F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F.

View this inspection on the county portal ›

Sep 21, 2021 16 demerits · 4 violations
Inspector comments: General comment: Bell outside of back door starting to rust. Ensure bell remains audible to avoid permit action in future. Doors must self-close, self-latch or have audible alarm. Inspection with Luis Lopez No signature due to COVID
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Buoy rope tangled and not long enough at time of inspection. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator untangled and corrected to 23'.
#22 · Premises: emergency telephone provided −6
Phone number from 911 was 704-835-1421, not what was listed at emergency phone. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Operator corrected number on signage. *Note: 911 called back and stated there was a hang up call when 911 was not dialed, but receiver picked up to test phone call back. Advised ensuring emergency phone only dials out for emergency calls.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. No backflow prevention on hose bib in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms over 110 degrees F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F.

View this inspection on the county portal ›

Jan 13, 2021 12 demerits · 4 violations
Inspector comments: Intent to Suspend (ITS) for trained pool operator and door self-closing, self-latching or audible alarm. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS. 22) When emergency phone was called back line was busy for a few minutes before audibly ringing back to phone. Phone still operable and meets compliance. Advised adjusting phone to allow immediate call back in case of emergency. No signature due to COVID-19. Inspection with Adam Allen and Amber Artis Report to General Manager NC384 Changed to "W" Intent to Suspend status.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No certified pool operator (CPO) for establishment at time of inspection. .2537(c) Pool owner shall provide for the operation and maintenance of the pool by a trained pool operator. *30 Day Intent to Suspend (ITS) item. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Back door that remains locked, not self-latching or alarmed. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. *30 Day Intent to Suspend (ITS) item. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping and equipment in pump room. Chemicals stored and in use in pump room. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Main drain piping has faded and no longer labeled. .2518(d) Piping and valves shall be labeled with color codes or labels. Manager labeled and corrected.

View this inspection on the county portal ›

Nov 3, 2020 8 demerits · 3 violations
Inspector comments: No signature due to COVID-19. Inspection with John Dolan Report to gm.nc384@choicehotels.com Note: Rope length for buoy 23'
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
A few chairs within 5' of pool and towel holder within 5' of handicap chair. Operator moved and corrected. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No clearance around piping in equipment room. Chemical vat in use in pump room, chemicals in side room of pump room. Pool built '00. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms over 110 degrees F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F.

View this inspection on the county portal ›

Mar 23, 2020 4 demerits · 2 violations
Inspector comments: Confirmed drain covers: 2 SDX Retro 2, 1 Aquastar 6HPHA. Pool closed for coronavirus (COVID-19) concerns, but being maintained so conducted inspection and left in "A" Open for Business status.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
New feeder equipment installed in pump room. No clearance around system. Chemicals stored in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Pool built 2000
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water over 110 degrees F. .2526(i) Water in restrooms shall not exceed 110 F.

View this inspection on the county portal ›

Nov 19, 2019 16 demerits · 5 violations
Inspector comments: ITS for records, flow meter and inlet fitting. Unable to verify chlorinator, will verify on return visit. New feeder system installed, **Main drains (SDX Retro) and skimmer equalizer cover (Aquastar 6 HP) expires May 2020. Replace and update PDSC form for approval prior to expiration to avoid permit action.** 22) When emergency phone was tested, emergency operator could not hear first statement. Emergency operator repeated self and phone connected. Recommended replacing phone for connection immediately.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records missing weekly total alkalinity, has cyanuric acid records (but do not think pool is using stablizier). Daily reading missing for day before inspection (11/19). .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. **ITS item
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Inlet fitting missing ring cover. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. **ITS item
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not working at time of inspection. .2518(g) Keep flow meter operational. **ITS item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
New feeder equipment installed in pump room. No clearance around system. Chemicals stored in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Pool built 2000
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms above 110 degrees F. .2526(i) Water in restrooms shall not exceed 110 F.

View this inspection on the county portal ›

Mar 27, 2019 16 demerits · 3 violations
#2 · Water quality: disinfectant residual provided by −6
Chlorine 0.4 ppm at time of visit..2535(4) Maintain chlorine at least 1.0 ppm. Operator asked to place chlorine tablets in pool. Educated operator this is not acceptable and considered imminent hazard. Must use chlorinator to adjust. Corrected to 1.0 ppm
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records missing weekly alkalinity readings. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator tested alkalinity and recorded. Corrected.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Buoy rope tangled at time of inspection. Keep accessible. Operator untangled. Corrected.

View this inspection on the county portal ›

Nov 7, 2018 36 demerits · 8 violations
#4 · Water quality: water temperature of heated pool −6
.2535(12) Maintain pool temperature at 90 F or below. Pool temperature 91.4. **Immediate suspension item. Contact Marie Daley at 704-507-6806 to lift suspension when corrected. Pool may not operate until suspension is lifted by Health Dept.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Records missing maintenance and inconsistent (same reading for months in row, no maintenance). *30 Day Intent to Suspend (ITS) item.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Replace missing inlet fitting. **30 Day ITS item
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide at least 12 ft. long pole with body hook securely attached. .2530(a) Pole for body hook must be non-telescoping, non-adjustable, and non-collapsible. *Immediate Suspension item.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Operator moved chairs and tables. Corrected.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. *Immediate Suspension item
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. .2518(e) Provide a spare basket for pump. (Hayward SuperPump SP 2605X7) *30 Day Intent to Suspend item
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2626(i) Water shall not exceed 110 F.

View this inspection on the county portal ›

Jan 31, 2018 38 demerits · 10 violations
Inspector comments: ITS items for records, lighting and inlet fittings. Ring buoy glue starting to peel. Recommended replacing. Rope length 23'.
#2 · Water quality: disinfectant residual provided by −6
Free chlorine 0.0 ppm at time of inspection. Maintain free chlorine at least 1.0 ppm. Chlorinator turned off at time of inspection. Chlorinator needs to function properly at all times. Rechecked at multiple times chlorine only reaching 0.1 ppm maximum. **Immediate Suspension item. Pool Closed sign posted Contact Marie Daley at 704-507-6806 to lift Immediate Suspension when corrected.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Daily records were recorded by someone not currently working for times that have not been reached yet with exact copied values throughout month. Ensure adequate records are being kept, by testing water quality then recording findings including pH, free chlorine (disinfectant residual), main drain checks, temperature, activities pertaining to pool maintenance and weekly TA and CA. ** 30 Day Intent to Suspend item.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer basket with debris. Keep clean. Operator cleaned. Corrected.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Inlet fittings missing. Keep in good repair. Replace. **Intent to Suspend item.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs and tables within 5' of pool. Maintain 5' deck Clearance. Operator moved. Corrected.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Underwater light not working at time of inspection. Keep in good repair to illuminate main drains. **Intent to Suspend item.
#22 · Premises: emergency telephone provided −6
Emergency phone had multiple phone numbers listed. Emergency phone must provide correct address and phone number. Operator removed extra number, corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Leak causing standing water in the pump room. Keep area dry. Chemicals stored around pump equipment. Keep chemicals stored separately and maintain 3' clearance around equipement.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water over 110 degrees F in restroom. Maintain hot water at 110 degrees F and below.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Provide backflow prevention device for hose bibb at shower in pool area.

View this inspection on the county portal ›

Nov 8, 2017 28 demerits · 8 violations
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Some inlet fittings missing. Keep in good repair. Replace.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope tangled, not easily accessible at time of visit. Keep easily accessible. Operator untangled. Corrected during inspection (CDI). Holders starting to separate from buoy which voids US Coast Gaurd Approval, still attached at time of inspection. Replace.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs and table at entrance within 5' of pool. Maintain 5' deck clearance. Operator moved. CDI
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Underwater light not working at time of inspection. All other lighting works and adequate. Keep in good repair.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Pump leaking at time of inspection. Pan has been placed under pump to catch water, so the area is dry. Keep in good repair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals in pump room. Keep in separate room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms 124 degrees F. Maintain at 110 degrees and below.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
Provide backflow prevention device for hose bibb at shower.

View this inspection on the county portal ›

Jun 22, 2017 0 demerits · 0 violations

No violations were recorded for this inspection.

View this inspection on the county portal ›

Dec 16, 2016 12 demerits · 4 violations
Inspector comments: #12 One inlet fitting missing component. ** Replace fitting. GC #25 Forced air vent in chemical "room" operates off of equipment room light switch. ** Forced air vent fan should run continuously.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed residue/ scum on pool wall tiles. ** Clean.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Pool wall light inoperable. ** Repair/ replace. (Pool enclosure has additional lights.) See .2524(e)
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water at least 117F @ shower inside pool enclosure & ~129F @ lavatories in restrooms. ** Maximum temperature allowed is 110F.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
-- Hose bib on pool deck does not have any backflow prevention device. ** Install vacuum breaker on this hose bib (& also on the hose bib in the equipment room). - Hotel owner & hotel manager both report that water is added to the pool via the hose bib on the pool deck. ** Pool was designed with fill spout/ fill spout has been removed at deck level.

View this inspection on the county portal ›

Feb 25, 2016 8 demerits · 3 violations
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Pool wall light inoperable. ** Replace/ repair. (Pool enclosure has additional lights.)
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water ~123F @ shower within pool enclosure. Hot water ~130F @ lavatories in hall restrooms. ** Maximum temperature allowed is 110F. * Maximum temperature allowed is 110F.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
- Hose bib on pool deck does not have backflow prevention. ** Install vacuum breaker. - Owner reports that water is added to the pool via hose bib on pool deck. ** Pool was designed with fill spout/ fill spout has been removed at deck level.

View this inspection on the county portal ›

Feb 19, 2015 18 demerits · 5 violations
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed throw rope on ring bouy to be 22'. It is required to be 23'. Rope was corrected to 23'
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Observed pool wall light non-functional. Pool enclosure has additional lights. Replace/repair pool wall light.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed leak at pump system controlled with a bucket. Repair the leak.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed shower hot water to be at 115F. Hot water shall be no higher than 110F.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
Provide backflow prevention to the hose bibb on the deck.

View this inspection on the county portal ›

Nov 4, 2014 12 demerits · 3 violations
Inspector comments: Issued immediate suspension for # 15.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed throw rope knotted and only 21 feet long. Throw rope must be 23 feet long.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed deck chairs w/in 5' of pools edge. Maintain 5' of deck clearance at all points.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed leak in pump room. Repair leak.

View this inspection on the county portal ›

Feb 5, 2014 6 demerits · 2 violations
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed deck chairs within 5ft of pools edge. Maintain 5ft of deck clearance at all points. Observed pitting in pool deck near towel rack. Repair pitting.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed hot water. in restrroms at 117 degrees. Hot water should not exceed 110 degrees.

View this inspection on the county portal ›

Oct 7, 2013 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed hot water n restrooms at 116 degrees. Hot water should not exceed 110 degrees in restrooms.

View this inspection on the county portal ›