4demerits
LEVINE SENIOR CENTER
1050 DEVORE LN, Matthews, NC 28105
Year-Round Swimming Pool · NC permit/State ID 2060530187
Latest result4 demerits
Last inspectedJan 21, 2026
Inspections on record25
On record sinceOct 29, 2013
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Oct 29, 2013Lower is betterJan 21, 2026
Inspections & violations
Jan 21, 2026 4 demerits · 1 violation
Inspector comments: Inspection completed with Dahn Jenkins present.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 1 out of 2 total weirs missing.
Jul 15, 2025 4 demerits · 1 violation
Inspector comments: Inspection completed with Dahn Jenkins present.
Note: equalizer line coverings expire December, 2025. Ensure covers are replaced and a new PDSC form is submitted prior to expiration date or permit may be suspended.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 1 weir detached from skimmer and floating inside skimmer basket. Reattach.
Jan 7, 2025 4 demerits · 1 violation
Inspector comments: Inspection completed with Dahn Jenkins present.
Inspection completed by Maddie Denoncour with Eli Freese present.
Note - equalizer line covers expire December, 2025. Replace and submit a pool drain suction compliance form (PDSC) to the health department to verify.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter non operational.
Jul 23, 2024 4 demerits · 1 violation
Inspector comments: Inspection completed with Dahn Jenkins present.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 1 damaged weir. Replace.
Jan 10, 2024 6 demerits · 1 violation
Inspector comments: Inspection completed with Christiana Walters present.
Note: ensure spare pump basket is on site.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed ring buoy in poor repair (beckets deteriorating). CDI- buoy replaced with new buoy.
Feb 2, 2023 0 demerits · 0 violations
Inspector comments: Inspection completed with Christiana Walters and Dahn Jenkins present.
No violations noted.
No violations were recorded for this inspection.
Nov 1, 2022 0 demerits · 0 violations
Inspector comments: NO VIOLATIONS NOTED.
No violations were recorded for this inspection.
Mar 3, 2022 0 demerits · 0 violations
Inspector comments: NO VIOLATIONS NOTED.
STAFF AGREED TO EMAIL COPY OF REPORT
NO SIGNATURE DUE TO COVID-19 PRECAUTIONS.
CONTINUE TO FOLLOW ALL RELEVANT COVID RULES
No violations were recorded for this inspection.
Nov 3, 2021 0 demerits · 0 violations
Inspector comments: NO VIOLATIONS NOTED.
STAFF AGREED TO EMAIL COPY OF REPORT
NO SIGNATURE DUE TO COVID-19 PRECAUTIONS.
CONTINUE TO FOLLOW ALL RELEVANT COVID RULES
No violations were recorded for this inspection.
Mar 10, 2021 0 demerits · 0 violations
Inspector comments: NO VIOLATIONS NOTED
CONTINUE TO FOLLOW ANY CURRENT COVID-19 RULES
NO SIGNATURE DUE TO COVID PRECAUTIONS
RESPONSIBLE PARTY AGREED TO EMAIL REPORT FORM.
No violations were recorded for this inspection.
Oct 27, 2020 0 demerits · 0 violations
Inspector comments: NO VIOLATIONS NOTED. HEATER WAS OFF. POOL HAS NOT HAD USE SINCE MARCH, BUT MAY REOPEN FOR SWIMMING SOON.
Observed 2 8HP Aquastar EQ line covers in use. These will expire January 2021. The 8HP has been discontinued by Aquastar so a different model cover may be required. Ensure that new covers have a flow rate suitable for this system. Alternately the EQ lines may be plugged as per State recommendations. A new updated PDSC form must be sent to the Health Department for approval when the changes are made.
“issuance of a permit by this department does not negate closure required by Executive Order No. 120, 138, 141, 147, or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.”
NO SIGNATURE WAS OBTAINED DUE TO COVID-19 SOCIAL DISTANCING
No violations were recorded for this inspection.
Feb 10, 2020 0 demerits · 0 violations
Inspector comments: NO VIOLATIONS NOTED.
POOL STILL HAS NOT FINALED CODE ENFORCEMENT PERMIT #E3651058. THIS MUST BE DONE BEFORE NEW PERMIT WILL BE ISSUED.
No violations were recorded for this inspection.
Nov 4, 2019 4 demerits · 1 violation
Inspector comments: Observed evidence of repairs/replacement for pump, pump parts, and motor in the pump room. If the pump characteristics are changed from what is recorded with the Health Department, new information and/or a new PDSC form may have to be submitted to ensure correct flow rate for the system.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed gaps in the record where the temperature was not recorded on the log sheet entry line for temperature. Record the water temperature of the pool everyday the pool is open as this is required for every heated pool. Maximum temperature allowed for this type of pool is 90.0F. Today temperature is 89.5F No permit action taken.
Feb 22, 2019 0 demerits · 0 violations
Inspector comments: NO VIOLATIONS NOTED.
No violations were recorded for this inspection.
Nov 28, 2018 4 demerits · 2 violations
Inspector comments: Verified PDSC information
Christiana Walters present during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed chemicals stored in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed water temperature at hand sinks over 114 degrees F.
.2626(i) Water in restrooms shall not exceed 110 F.
Feb 15, 2018 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed hot water to be 118F at bathroom sink. Hot water in fixtures shall be no more than 110F.
Nov 17, 2017 4 demerits · 1 violation
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed Total Alkalinity and Cyanruic Acid not checked and recorded on the November log record. These items must be checked and recorded at least once a week. Cyanuric Acid shall not be allowed to exceed 100ppm.
Mar 23, 2017 0 demerits · 0 violations
Inspector comments: NO VIOLATIONS NOTED
No violations were recorded for this inspection.
Sep 26, 2016 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed hot water in sink to be at least 114F. Hot water shall be 110F in fixtures.
Mar 10, 2016 6 demerits · 2 violations
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter to be stuck. Repair flow meter.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed hot water in bathroom fixtures to be at least 114F. Hot water at all bathroom fixtures shall be no hotter than 110F.
Sep 30, 2015 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed hot water to be at least 113F. Hot water shall be no hotter than 110F at bathroom fixtures.
Feb 19, 2015 2 demerits · 1 violation
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed non pool items stored in pump room. Eliinate storage in pump room.
Dec 3, 2014 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms 113°F. Maintain at 110°F or less.
Mar 24, 2014 2 demerits · 1 violation
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water > 110°F. Maintain at 110°F or less.
Oct 29, 2013 8 demerits · 2 violations
#2 · Water quality: disinfectant residual provided by −6
Cl 0.3. Corrected to 1.0. Maintain at least 1ppm. Heavy user load at some classes. Recommend maintaining Cl at a higher level.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restroom > 110°F. Maintain at 110°F or less.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “LEVINE SENIOR CENTER” or State ID 2060530187). Inspection type (routine vs. follow-up) is not published in the county's data.