6demerits
DRURY INN AND SUITES
6920 NORTHLAKE MALL DR, Charlotte, NC 28216
Year-Round Swimming Pool · NC permit/State ID 2060530213
Latest result6 demerits
Last inspectedAug 6, 2026
Inspections on record28
On record sinceSep 12, 2013
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Sep 12, 2013Lower is betterAug 6, 2026
Inspections & violations
Aug 6, 2026 6 demerits · 2 violations
Inspector comments: OBSERVED POOL LIGHTS ON.
MAIN DRAIN COVERS EXPIRE 2/3/2030
OBSERVED EMERGENCY PHONE CALL-BACK NUMBER TO GO TO AN OFF-SITE CALL CENTER IN MISSOURI TO BE CONNECTED TO THE MAIN DESK. THE CALL BACK NUMBER IS TO GO BACK TO THE PHONE ITSELF, OR TO AN ON-SITE PHONE THAT IS MONITORED 24 HOURS A DAY, 365 DAYS A YEAR. THIS REQUIRES CORRECTION. C. ELMORE WILL FOLLOW-UP TO EVALUATE CORRECTION.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Missing one of two weirs. .2518(k) Provide functional weirs. No permit action taken.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed a leak in the pipe system. Correct the leak.
.2533(d) Pump room floor shall be kept dry and free of standing water.
Mar 3, 2026 18 demerits · 5 violations
Inspector comments: Inspection conducted with CPO Rodney Searcy.
No label on pool pump. Observed Pentair Challenger pump with 2 HP motor.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Missing one of two weirs. Other weir not functioning. .2518(k) Provide functional weirs.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
All ladders loose. .2521 Install ladders per manufacturer instructions.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Eyeball fitting missing. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Both ring buoys new with 60 foot throw ropes. .2530(a) Provide USCG approved ring buoy with attached 33 foot throw rope at least 1/4 inch in diameter. - Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items stored directly beside or on top of equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Dec 15, 2025 18 demerits · 6 violations
Inspector comments: CPO Rodney Searcy not present for today’s inspection.
Went over inspection with manager Katherine Conrad.
Pool permitted for night swimming. Not able to verify that outdoor lighting works. Will check on a future visit.
No label observed on pool pump. Verified Pentair Challenger pump with 2 HP motor.
Electrical whip to pool motor not fully installed, wiring exposed. Ensure wiring is properly installed by a licensed electrician.
Intent to suspend issued
8)
12)
17)
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Missing one of two weirs. Other weir not functioning. .2518(k) Provide functional weirs. - Intent to suspend item.
Both skimmers full of leaves. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
All ladders loose. .2521 Install ladders per manufacturer instructions.
One handrail loose. .2521 Install handrails per manufacturer instructions.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Eyeball fitting missing. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Intent to suspend item.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Table and chairs too close to handrail. .2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. - Intent to suspend item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items stored directly beside or on top of equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Chemical storage room very cluttered. Lots of chemicals stored on top of each other. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
Jan 9, 2025 12 demerits · 3 violations
Inspector comments: Observation was made on one pool ladder and two hand rails slightly loose but could not be removed by hand.
During inspection VIOP configuration calls 911 operator to only see the out of state number on the screen. This configuration can delay 911 response time. The number on the sign is correct but 911 operator can not verify the front desk number.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed missing weir for outdoor skimmer however, no debris was observed in pool. CDI - CPO replaced weir during inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage for emergency phone displayed two phone numbers one which dialed to another state for hotel reservations. CDI - Out of state number was taped overed by CPO. The front desk number only remains which is monitored 24/7.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(f) At least one sink, one toilet, one urinal is required for men's restroom. Observed hand washing sink not turning on. CPO may need to changing batteries for automatic faucet.
Dec 4, 2024 16 demerits · 4 violations
Inspector comments: Inspection conducted with CPO Rodney Searcy and Chris Palladino. Inspection led by inspector Maddie Denoncour.
Emergency phone calls back to front desk. Ensure someone is at the front desk whenever the pool is open.
Pool has a permit for night swimming. Verified all lights on night swimming from were in good working order.
Screws for main drains discolored. Ensure main drains are secured with stainless steel screws installed per manufacturer’s instructions.
No label observed on pool pump. Verified Pentair Challenger pump with 2 HP motor.
Observed motor for pool pump recently changed out. Electrical permit E4521713 passed inspection 11-6-2023.
Electrical whip to pool motor not fully installed, wiring exposed. Ensure wiring is properly installed by a licensed electrician.
Intent to suspend issued
8)
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir missing. .2518(k) Provide functional weirs - Corrected.
Outdoor skimmer lid damaged. .2518(k) Replace damaged skimmer lid. - Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders loose. .2521 Install ladders per manufacturer instructions.
Some steps loose. .2521 Install ladders per manufacturer instructions.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
One ring buoy damaged. .2530(a) Provide USCG approved ring buoy with attached 33 foot throw rope at least 1/4 inch in diameter. - Corrected. Damaged ring buoy removed, still have one ring buoy.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some chairs too close to pool on outdoor pool portion. .2522(a) Provide 6 ft of clear walking space around the pool at all times. - Corrected.
Jan 31, 2024 14 demerits · 4 violations
Inspector comments: Inspection conducted with inspector Anglecia Askew and Chris with maintenance.
Pool recently re-plastered. Equalizer lines plastered over on pool wall, equalizer line valves installed in the skimmer. Will need to replace equalizer line valves with permanent plugs. Facility is working to properly abandon equalizer line per state guidelines.
Pump not labeled. Observed Pentair Challenger pump with 2 HP motor installed.
One outdoor gate damaged at the bottom. Recommend repairing.
Pool has a night swimming permit. Verified outdoor lighting is still functional.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders loose. .2521 Install ladders per manufacturer instructions.
Handrails loose. .2521 Install handrails per manufacturer instructions.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
One ring buoy with 31 foot throw rope.. .2530(a) Provide USCG approved ring buoy with attached 33 foot throw rope at least 1/4 inch in diameter. - Corrected.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some chairs too close to pool on outdoor pool portion. .2522(a) Provide 6 ft of clear walking space around the pool at all times. - Corrected.
One indoor chair too close to pool edge. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times. - Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items stored beside spa equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Some bags of chemicals on the floor. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Dec 20, 2023 12 demerits · 4 violations
Inspector comments: Flow meter numbers faded - CPO has new flow meter on order.
Pool coping on outside portion of pool starting to deterioriate - EHS recommends repair.
Screws on inside body hook rusting - EHS recommends replacing.
Inspection conducted by Devon Moeller under supervision of Stacie Rhea.
CPO signed paper copy of inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Missing one of two weirs. .2518(k) Provide functional weirs - CPO corrected onsite by installing weir
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Provide at least one handrail on steps. Both step handrails loose. Tighten loose handrails.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Indoor/outdoor design does not provide adequate deck space all around pool. Renovation not required. No permit action.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Chemicals not stored in an orderly fashion. Organize chemical storage room and raise bags on ground off the floor.
Mar 14, 2023 14 demerits · 4 violations
Inspector comments: Inspection conducted with CPO Rodney Searcy.
One no diving marker cracked. Maintain in good condition.
Flow meter numbering worn and difficult to read. Recommend replacing.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Missing one of two weirs. .2518(k) Provide functional weirs.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders loose. .2521 Install ladders per manufacturer instructions.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Both ring buoys have new 60 foot throw ropes. .2530(a) Provide USCG approved ring buoy with attached 33 foot throw rope at least 1/4 inch in diameter. - Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
Some chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Aug 10, 2022 8 demerits · 2 violations
#3 · Water quality: pool water pH −6
Observed pH level at the pool of 6.8 .2535(1) Maintain pH at 7.2 to 7.8. Corrected to 7.3 during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed wet floor in the pump room .2533(d) Pump room floor shall be kept dry and free of standing water.
Mar 7, 2022 20 demerits · 5 violations
Inspector comments: Inspection conducted with Cary Amey. Due to COVID-19 precautions, inspection not signed by the operator.
911 has the correct address, but a different phone number than what is posted. Ensure 911 has the correct phone number for the emergency phone so they can call back in the event of a dropped call. - Will follow up in the next few days.
Verified outdoor and underwater lights work. Pool permitted for night swimming for 2022 operating season. Lights must remain operational whenever the pool is open after dark.
#3 · Water quality: pool water pH −6
pH 7.0. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.2.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer baskets with leaves and debris. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders loose. One ladder missing an endcap. .2521 Install ladders per manufacturer instructions.
Handrails loose. .2521 Install handrails per manufacturer instructions.
#22 · Premises: emergency telephone provided −6
Emergency phone not functioning. .2530(f) Emergency phone shall remain operable. - Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Nov 3, 2021 36 demerits · 9 violations
Inspector comments: Inspection conducted with inspector Naly Lor and manager Katherine Conrad. Due to COVID-19 precautions, inspection not signed by the manager.
Pool permitted for night swimming. Maintenance was not there today to verify that outdoor lighting works after dark. Will verify on a future visit.
No label on filtration pump. Motor appears to be recently replaced with a 2 HP motor. No record that motor had a passing electrical inspection. G.S. 130A-2(3) Pump motor replacement shall be done by a licensed electrician and an electrical permit obtained and inspected by Code Enforcement. - Immediate suspension item.
Operator attempted to correct pH. Efforts were reversed by automatic feeder. Recommend recalibrating automatic chemical controller.
Immediate suspension issued.
3)
4)
6)
Pump motor not inspected by Code Enforcement
#3 · Water quality: pool water pH −6
pH 6.8. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item.
#4 · Water quality: water temperature of heated pool −6
Temperature 90.8F. .2535(12) Maintain pool temperature at 90 F or below. - Immediate suspension item.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No Main Drain checks observed. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for and total alkalinity. - Intent to suspend item.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Aquastar 6 HP drain covers installed with 2 screws, rather than 4 screws as per manufacturer's instructions. One of the screws is loose. .2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions. - Immediate suspension item.
New 2HP motor installed on unlabeled Pentair Challenger Pump. Provide pump documentation (invoice, photo of impellor serial number, or equivalent) and updated PDSC form if pump is different than the pump we have on file. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Immediate suspension item.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer baskets with leaves and debris. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders loose. Some ladders missing endcaps. .2521 Install ladders per manufacturer instructions.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some chairs too close to the pool deck. .2522(a) Provide 6 ft of clear walking space around the outdoor portion of the pool. .2522(b) Provide at least 5 ft of clear walking space around the indoor portion of the pool. - Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items stored beside pool equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Some chemicals in the pump room. Observed loose bromine briquets on the floor. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Some pipe labeling worn off. .2518(d) Piping and valves shall be labeled with color codes or labels.
Jan 26, 2021 2 demerits · 1 violation
#26 · Equipment room: valves and pipes identified by color codes or labels −2
.2518(d) Piping and valves shall be labeled with color codes or labels. Piping needs to be touched up. Needs more directional arrows.
Jul 13, 2020 14 demerits · 5 violations
Inspector comments: Inspection conducted with maintenance. Due to COVID-19 precautions, inspection was not signed by the operator.
Some lights operate on a timer and a photocell. Will make a site visit tomorrow at 7 AM to verify lighting.
“Executive Order No. 141 or subsequent Orders are in effect unless such Orders are rescinded or superseded by another applicable
Order.”
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No Total Alkalinity checks for July. No Main Drain checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator that normally checks TA was off, will start checking again. No place for Main Drain checks on sheet. Will start using CYA column for Main Drain checks.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Baskets with debris and wads of hair. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders loose, or missing endcaps. .2521 Install ladders per manufacturer instructions.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
Light in pump room burned out. .2533(b) Provide sufficient lighting in pump room.
Bag of dry chemicals on the ground in the chemical storage room. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Some labeling worn off of the piping. .2518(d) Piping and valves shall be labeled with color codes or labels.
Mar 4, 2020 12 demerits · 3 violations
Inspector comments: *NOTE: Pool Inspection was completed for Alexis Welch Authorization. NC State Regional Heather Misenheimer was present during time of inspection.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.0. Corrected during inspection to 7.2
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed both skimmers with debris.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed loose ladder on the outside portion of pool located just outside door on spa side of pool. Observed end cap missing on same ladder as mentioned above.
Jan 22, 2020 30 demerits · 7 violations
#3 · Water quality: pool water pH −6
pH 7.0. .2535(1) Maintain pH at 7.2 to 7.8. Corrected to 7.2.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmers with debris, especially outdoor ones. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders loose. Some with loose steps. One missing an endcap. Maintain steps secure and in good condition.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Throw rope heavily knotted. .2530(a) Provide ring buoy for 33 foot throw rope. - Corrected.
#22 · Premises: emergency telephone provided −6
Incorrect dialing instructions posted. Phone automatically dials 911 when lifting the handset. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. - Temporary signage posted. Will order a new permanent sign.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. .2518(g) Keep flow meter operational.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Shower sign not posted. .2526(a) Post a shower sign visible upon entrance to the pool.
Oct 17, 2019 16 demerits · 4 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no records for daily main drain checks or weekly checks for cyanuric acid/ total alkalinity.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed deck chair with in six feet of pools edge at out side section of pool. Maintain 6 feet of clearance around out side section of pool deck.
.2522(a) Provide 6 ft of clear walking space around the pool at all times.
#22 · Premises: emergency telephone provided −6
Observed emergency phone inoperable. Corrected on site. 911 operator had different phone number than what was posted on sign. Corrected onsite. Advised that emergency phone has to have a dedicated phone line.
.2530(f) Emergency phone shall remain operable.
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed bags of backing soda on chemical room floor. Store bags off of the ground.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Jan 16, 2019 4 demerits · 1 violation
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed deck chari on outside section of pool within 6 feet of pools edge. Maintain 6 feet of deck clearance at all points on outside section of pool and 5 feet of deck clearance at all points around inside section of pool. Corrected on site.
Nov 27, 2018 10 demerits · 2 violations
Inspector comments: Issued intent to suspend for #8 (weirs).
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 1 of 2 weirs missing. Replace missing weirs. Intent to suspend issued.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Two bouys present. One bouy had no throw rope attached. The other bouy had a 50 foot rope attached. Removed buoy with nw rope and shortened rope to 33' on other bouy. Throw rope must be kept at 33' at all times.
Jan 29, 2018 18 demerits · 6 violations
Inspector comments: Notice of intent to suspend permit for flow meter and audible alarm on door.
Call Chris Sells when repairs are complete at 704 576 8678
Pool will be closed by the department in 30 days if repairs are not complete
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed 2 ladders missing end caps in outside area of pool. Observed one ladder in outdoor area missing slip resistant tread cover.
Keep all ladders in good repair and slip resistant.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed one eye ball fitting missing. Replace
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed door release on motion sensor. Install an audible alarm or disable motion sensor.
**Intent to Suspend
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck.
**Intent to Suspend
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed vent to chemical closet disabled. Provide mechanical ventilation to chemical room.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Observed no flow marked on piping. Mark flow
Nov 15, 2017 26 demerits · 7 violations
Inspector comments: Posted permits are from last year. Post current permits in the pool area. Permits can be found at Meckpools.Charmeck.org.
Intent to suspend issued.
7)
8)
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Algae growing on pool walls and ladders. Maintain pool free of algae. Brush regularly. - Intent to suspend item.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Both weirs missing. Install functional weirs. - Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders loose. One ladder missing an endcap and non-slip step tread. Maintain ladders secure and in good condition.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Inlet fitting missing. Install directional eyeball fitting.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
One ring buoy damaged with 30 foot throw rope. Other ring buoy missing throw rope. Proved U.S. Coast Guard approved ring buoy with 33 foot throw rope. Corrected by operator.
Body hook on inside pool area missing screws. Corrected by operator.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck chair too close to the pool. Maintain at least 5 feet clear walkway on inside part of pool, at least 6 feet clear walkway around outside of pool. Corrected by operator.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some leaks in the pump room. Fix leaks.
Chemicals stored in the pump room. Store chemicals in the chemical storage room.
Exhaust fans for pump room and chemical storage room not working. Provide either continuous forced air ventilation or cross ventilation.
Mar 2, 2017 26 demerits · 7 violations
Inspector comments: Inspection conducted by AJ Denicola and Stacie Rhea
Observed PDSC form without correct drain cover data.
#3 · Water quality: pool water pH −6
Observed pH at 7. Operator brought pH back to 7.2 during inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed one missing weir on outside of the pool. Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed several caps on ladders missing.
Observed some rails on the inside pool loose. Also observed slip resistant rubber pulling off inside ladder.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed several inlets missing eyes/cups - intent to suspend item.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed a stand and chair less than 6 feet from pool edge. Operator corrected during inspection.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Missing spare pump baskets. Replace items.
Also observed flow meter stuck.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed leaks in pump room. Repair.
Oct 27, 2016 38 demerits · 10 violations
Inspector comments: Posted permits have expired. Print and post copy of current permit. Permit can be found at Meckpools.Charmeck.org.
Immediate suspension issued.
2)
Will be back out early tomorrow morning to reinspect.
#2 · Water quality: disinfectant residual provided by −6
Bromine at 0.4 ppm. Maintain at least 2ppm free bromine. Operator added pucks, was able to adjust to 1ppm after at least an hour of waiting. - Immediate suspension item.,
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Green algae growing in corners and ladders. Maintain proper water chemistry and maintain pool algae free.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Both weirs missing. Install functional weirs. - Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Most ladders loose and missing endcaps. Maintain ladders secure and in good condition.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Missing a few inlet fittings. Install functional inlet fittings.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
One ring buoy with throw rope too short. Provide 33 foot throw rope for ring buoy. Removed from deck by operator.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
One chair too close to pool. Maintain at least 5 feet clear walkway on indoor part and 6 feet clear walkway on outdoor part of pool deck. Corrected by operator.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair or replace.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Leaks in pump room. Fix leaks.
Fan not working for chemical storage room. Provide proper ventilation.
Light in chemical storage room not working. Provide proper lighting.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Main drain piping not labeled. Ensure all pipes are labeled.
Jan 28, 2016 28 demerits · 7 violations
Inspector comments: Verified that approved PDSC forms match installed equipement. Waterway 640-470 main drain covers are recalled. Install retrofit cover to make A112 compliant or replace with approved A112 covers.Immediate suspension issued.6)Contact WIll Harrison (704-507-6824) for reinspection once issues have been corrected.
#3 · Water quality: pool water pH −6
pH 7.0. Maintain between 7.2 and 7.8. Corrected to 7.4.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Recently used pool logs do not have a place for main drain checks. Check daily main drains.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Waterway 640-470 covers recalled. Either replace with A112 approved covers or install retrofit kit to make covers A112 approved. - Immediate suspension item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Some ladders loose. Maintain secure and in good condition.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some deck chairs too close to edge of pool. Maintain at least 6 feet clear walkway around pool in outside section, and at least 5 feet clear walkway around inside section.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair or replace.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Maintain at least 3 feet clear walking space around pool equipment in pump room.
Aug 28, 2015 18 demerits · 5 violations
#3 · Water quality: pool water pH −6
pH < 6.8. Maintain between 7.2 and 7.8. Corrected to 7.2.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmers turned off in the pump room. Corrected by operator.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders loose. Maintain secure and in good condition.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair or replace.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Unable to get faucet in restroom to work. Provide functional faucet.
Mar 16, 2015 26 demerits · 6 violations
#3 · Water quality: pool water pH −6
pH 6.8. Maintain between 7.2 and 7.8. Corrected to 7.3.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer baskets with wads of hair. Clean baskets regularly.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Some ladders loose. Tighten.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Missing one inlet fitting. Install functional inlet fitting.
#22 · Premises: emergency telephone provided −6
Unable to reach 911. Corrected by operator.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair or replace.
Sep 30, 2014 18 demerits · 4 violations
Inspector comments: Note: Verify if bulbs are shatterproof. If not, recommend replacing with shatterproof.
#3 · Water quality: pool water pH −6
Observed pool pH at 6.9. Raised to 7.2 during inspection.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some algea on pool walls and ladders. Keep clean.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One of two weirs missing. Replace.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One inlet fitting missing. Replace.
Mar 24, 2014 20 demerits · 5 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Missing one weir. Install weir.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder missing end cap. Install endcap.
#22 · Premises: emergency telephone provided −6
No signage at emergency phone. Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Leak in pumproom. Fix leak
#3 · Water quality: pool water pH −6
pH 7.1. Maintain between 7.2 and 7.8. Corrected to 7.2.
Sep 12, 2013 14 demerits · 4 violations
Inspector comments: 9 - General Comment: Observed 4 1/2 ft with ft next to 4 and not 1/2. When repaired, repalce after 4 1/2.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no total alkalinity records. Record weekly.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed green algae on pool walls and one light not completely flush. Keep clean and repair light flush to wall.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed one skimmer without weir. Replace weir.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Observed some labeling worn off pipes. Relabel pipes.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “DRURY INN AND SUITES” or State ID 2060530213). Inspection type (routine vs. follow-up) is not published in the county's data.