SKYE CONDOMINIUMS

222 S CALDWELL ST, Charlotte, NC 28202
Year-Round Swimming Pool · NC permit/State ID 2060530303
Latest result32 demerits
Last inspectedApr 8, 2024
Inspections on record18
On record sinceJun 25, 2014

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

02346 Jun 25, 2014: 6Sep 18, 2014: 14Apr 13, 2015: 20Oct 12, 2015: 14Jun 22, 2016: 6Sep 28, 2016: 14Jun 26, 2017: 40Oct 3, 2017: 26Apr 26, 2018: 0Aug 21, 2018: 34Apr 22, 2019: 12Aug 14, 2019: 32Jun 5, 2020: 12Aug 20, 2020: 42Apr 29, 2021: 38May 30, 2023: 4Sep 13, 2023: 46Apr 8, 2024: 32
Jun 25, 2014Lower is betterApr 8, 2024

Inspections & violations

Apr 8, 2024 32 demerits · 7 violations
Inspector comments: Inspection conducted with operator Stoney. Immediate suspension of permit issued due to missing emergency phone signage and pH greater than 7.8. Once items are corrected, call Hope McIntosh at 980-229-7549 for re-inspection. At that time, other items noted as intent to suspend items will be re-evaluated and if remain non-compliant, a 30 day intent to suspend the permit may be issued. Note: Metal gate post becoming loose - needs to be tightened to prevent issues with gate closure/latching.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Pool water pH at 8.0. *Immediate suspension item
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Missing numerous days of record checks over past 6 months. Multiple days missing cl readings. No main drain checks being documented. Pool records being maintained digitally- recommend written documentation until records are consistent.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Water level shall be maintained to assure skimmers are operable. Water level low - skimmer not operable. Raise water level to allow skimmer operation. Intent to suspend item.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment should be conveniently located. Ring buoy rope coiled/tangled and fixed to wall mount rendering buoy inaccessible. Operator corrected.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed chairs less than 6' from pool edge. .2522(a) Provide 6 ft of clear walking space around the pool at all times. - Intent to suspend item.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Emergency phone information signage removed. Immediate suspension item.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526(a) Provide restrooms at all pools except for hotels, motels, condominiums and apartments where pool use is restricted to guests and residents. Both restroom doors locked - operator does not have key. Restrooms currently inaccessible/unusable.

View this inspection on the county portal ›

Sep 13, 2023 46 demerits · 11 violations
Inspector comments: Immediate Suspension issued for: .2535 - maintain chlorine at least 1.0 ppm through chlorinator .2539 - pump could not be verified due to access to pump room .2530 - secure body hook to pole .2530 - phone shall be operable - correct address and phone number posted Stoney Lopez present during the inspection. Meck Co Pool Closed sign posted on restaurant gate. Facility provided sign on door into hall outside of pool which is main entry point. Viewed public access while still on deck. Moved sign to main door. Once items corrected, contact Katie to reopen the pool. The pool shall remain closed until a return visit has been made.
#2 · Water quality: disinfectant residual provided by −6
No chlorine in pool. Maintain chlorine in pool through chlorinator at least 1.0 ppm. Immediate Suspension issued.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Some expired reagents. Log books not accessible. If keeping electronic logs, they must be accessible to EHS. Daily record keeping required for main drains, chlorine and pH. Weekly record keeping for total alkalinity and cyanuric acid. Provide new test kit.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
No access to pump room to verify VGB. Per deed, entry to pump room shall be accessed through condominium door due to confined space entry. Could not reach chef who has ownership of condo. No access to pump room. Could not verify pump to verify no suction hazard. Immediate Suspension issued.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
No weir in skimmer. Provide weir. Water level high. Lower water level to ensure skimmers are operable. Minor damage to skimmer basket. Replace as needed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Step handrail loose. Tighten.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
No nut on screw in body hook. Not secure. Body hook shall be secured to pole so not to be removed. Immediate Suspension issued.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Audible alarm installed on door into pool deck. Not on at time of inspection. Door originally approved to self-close, self-latch. Requires repair prior to 2024 operating permit. Restaurant entry gate not secure. Secure post.
#22 · Premises: emergency telephone provided −6
Phone not operable. Cannot hear 911. Ensure 911 has address and phone number. 911 shall be clearly audible. Phone shall audibly ring back when number is dialed. Immediate Suspension issued.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Could not access pump room at time of inspection. Pump, flow meter, filter, pump room, chemical storage room will be verified on the return visit.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Could not verify chemical storage room due to access. Will verify on return visit.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No soap in restrooms. Provide soap in restrooms.

View this inspection on the county portal ›

May 30, 2023 4 demerits · 1 violation
Inspector comments: Observed items from previous visit corrected. Spare filters provided. Gate and fence repaired as required. Deck tiles repaired and gaps removed.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed door to pool deck not self latching or alarmed. Corrected during inspection. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.

View this inspection on the county portal ›

Apr 29, 2021 38 demerits · 8 violations
Inspector comments: Inspection conducted with property manager Sarah Hadley and CPO Venyett Smith. Due to COVID-19 precautions, inspection was not signed by the CPO. Body hook held in place with one screw, wingnut facing hook. Recommend using two screws and having bolt head facing the hook to prevent injury when used. Immediate suspension issued 2) 3) 6) 15) 22) A $100 reinspection fee will need to be paid prior to reopening the pool. This can be done by calling our office (980-314-1620) and paying with a credit card.
#2 · Water quality: disinfectant residual provided by −6
No free chlorine in the pool. .2535(4) Maintain chlorine at least 1.0 ppm. - Operator added liquid chlorine directly to the pool. Unable to determine if chlorinator is working. - Immediate suspension item.
#3 · Water quality: pool water pH −6
Pool pH below 6.8. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate Suspension item
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Main drains recently replaced with new Aquastar A10RCFRxxx covers. Updated PDSC form has not been submitted. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Immediate suspension item.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy damaged. .2530(a) Provide USCG approved ring buoy with 15 ft. rope. - Immediate Suspension item.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed chairs less than 6' from pool edge. .2522(a) Provide 6 ft of clear walking space around the pool at all times. - Intent to suspend item.
#22 · Premises: emergency telephone provided −6
Emergency phone number posted does not match what 911 has. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Posted information must match what 911 has. - Immediate suspension item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Leaks from the ceiling in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water. Fan in the chemical storage room not working. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No soap in men's restroom. .2626(j) Provide soap and soap dispenser, no glass, at each sink. Sink faucet not running continuously and shutting off immediately in the men's restroom. Adjust so handwashing can occur as required. .2626(m) Keep restrooms and fixtures clean and in good repair.

View this inspection on the county portal ›

Aug 20, 2020 42 demerits · 9 violations
Inspector comments: Immediate Suspension issued for pool pH, access to pump room (pump verification), ring buoy with 15 ft. rope and emergency phone. Once items have been corrected and access to pump room is provided, please contact Katie at 704-309-5494 to schedule a return inspection. Venyett Smith present during inspection. No signature due to covid restrictions. Pool is not approved for night swimming. After hour visit required for night swimming approval.
#3 · Water quality: pool water pH −6
Pool pH below 6.8. Maintain at 7.2 to 7.8. Immediate Suspension issued.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Could not view log book due to pump room being inaccessible. Ensure daily record keeping for main drain checks, chlorine, and pH. Weekly alkalinity and acid checks. Cyanuric acid reading above 100 ppm. May be affecting pool pH. Max level for cyanuric acid required at 100 ppm or less. Some reagents expired in test kit. Provide new reagents.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Could not verify pump in pump room due to no access to pump room. Immediate Suspension issued.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some damage to plaster at bench and steps. Repair damage/plaster.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Damaged ring buoy and rope. Replace with USCG approved ring buoy and 15 ft. rope. Immediate Suspension issued.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Plant outside of gate entry provided foothold. Moved during inspection.
#22 · Premises: emergency telephone provided −6
Phone not operable. Busy signal. Per operator, flood knocked out phone line. Phone shall be operable and capable of dialing 911. 911 shall have correct phone number and address. Immediate Suspension issued.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
No access to pump room. Per deed agreements, pump room shall be accessible at all times. Permit will be suspended if not accessible.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Faucet handle in men's restroom not staying engaged to properly handwash. Repair spring so that water runs continuously for proper handwashing.

View this inspection on the county portal ›

Jun 5, 2020 12 demerits · 3 violations
Inspector comments: Verified PDSC information No signature due to Covid19 social distancing requirements. Venyett Smith present during inspection.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed plaster worn at steps and small area damaged at deep end. .2537 Keep pool floor in good repair.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed gate not closing, corrected during inspection. .2537(b) All gates and doors shall be self-closing, self-latching.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed chairs less than 6' from pool edge, corrected during inspection. .2522(a) Provide 6 ft of clear walking space around the pool at all times.

View this inspection on the county portal ›

Aug 14, 2019 32 demerits · 8 violations
Inspector comments: Note: Access to pump room was not provided immediately to room beside pump room. Had to get permission from resident. Pump room access through room must be accessible at all times or permit will be suspended. Door into pump room baricaded shut with stopper. Removed during inspection and kept locked. Ring buoy damaged. Replace within 30 days. Intent to suspend issued for record keeping for CYA and main drains, paver damage, and flow meter replacement.
#3 · Water quality: pool water pH −6
Pool pH at 6.8. Corrected to 7.6 during inspection. .2535(1) Maintain pH at 7.2 to 7.8.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Log book is digital. Does not show Cyanuric acid or main drain checks. Intent to Suspend issued. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Pool plaster on steps and bench beginning to wear/etched. .2537(14) Keep pool surface and pool floor free of debris.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope at 13.5 ft. Required at 15 ft. Corrected to 15 ft. during inspection. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Damaged paver next to pool. Cracked in multiple locations. Intent to Suspend issued. Damaged paver near shower outside of required decking. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter numbers worn off. Provide operable flow meter. Intent to Suspend issued. .2518(g) Flow meter be capable of measuring 1.5 times the design flow rate.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Soda ash on chemical storage room floor. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No soap in restrooms. .2626(j) Provide soap and soap dispenser, no glass, at each sink. Sink faucet not running continuously and shutting off immediately in the men's restroom. Adjust so handwashing can occur as required. .2626(m) Keep restrooms and fixtures clean and in good repair.

View this inspection on the county portal ›

Apr 22, 2019 12 demerits · 2 violations
Inspector comments: Night Swimming is approved.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH of the pool around 7.0. Operator corrected during inspection and raised the pH to 7.2.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed the pool phone number incorrect on sign. Operator corrected during inspection by covering the numbers with the correct phone number.

View this inspection on the county portal ›

Aug 21, 2018 34 demerits · 8 violations
Inspector comments: 15 - General Comment - Ring buoy rope beginning to degrade. Replace rope with 15 ft. rope. Will be given 30 days. Pool not approved for Night Swimming. An additional site visit must be made to verify sufficient lighting present. Immediate Suspension issued for chlorine and for emergency phone. Once corrected, contact Katie at 704-309-5494 to schedule a return inspection.
#2 · Water quality: disinfectant residual provided by −6
Pool chlorine at 0 ppm. Per operator, salt system is not in use due to broken pipe. Maintain chlorine at least 1.0 ppm at all times. Immediate Suspension issued.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed days missing from logs and no acid readings recorded. Record chlorine, pH and main drain checks daily. Cyanuric acid and alkalinity checks record weekly.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some plaster damaged on steps and bench. Keep plaster in good repair.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer lid cracked. Replace lid.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Paver offsets at pavers directly next to pool. Repair to that pavers are level to pool coping.
#22 · Premises: emergency telephone provided −6
Emergency phone number posted does not dial back to phone. Number goes to a Verizon number that is not connected. Phone number that 911 has must go direct to 911 phone. Immediate Suspension issued.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Salt chlorination down. Liquid acid feeder used for pH regulation. Could not verify at time of inspection since system was not operable. Automated system must be set up to detect flow of pump and turn off when pump flow stops.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No soap in restrooms on pool deck. Provide soap in restrooms.

View this inspection on the county portal ›

Apr 26, 2018 0 demerits · 0 violations
Inspector comments: 7. Observed plaster damaged on bench corner and on corners of steps. Keep pool floor in good repair. PDSC information verified.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Oct 3, 2017 26 demerits · 7 violations
Inspector comments: 5 - General Comment - Acid recorded at 70 ppm since July 2017. Assure acid recorded weekly. Permit Restriction - Re-wrap caution tape around pipe at entry to pump room.
#3 · Water quality: pool water pH −6
Pool pH at 8.2. Corrected to 7.8 during inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Step hanrdail loose. Keep tightened.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door on to pool deck not self-latching. Repair to self-latch. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some chipping coating on deck pavers. Keep deckin in good repair.
#22 · Premises: emergency telephone provided −6
Phone not operable. Corrected during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Floor in pump room wet and fan in chemical storage room not operable. Keep dry and provide continuous forced ventilation. Sodium bicarb bag stored on floor. Store chemicals up off the floor.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No soap in restrooms. Provide soap.

View this inspection on the county portal ›

Jun 26, 2017 40 demerits · 9 violations
Inspector comments: General Comment - Observed pump operating normal. No loud noises noted. Once chlorine corrected and drain covers replaced, provide updated PDSC form and contact Katie Wilson at 704-309-5494 to re-open pool. Pump Hayward SP2615x20
#2 · Water quality: disinfectant residual provided by −6
Pool chlorine at 0.4 ppm. Maintaint at least 1.0 ppm. Immediate Suspension issued.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Cyanuric acid greater than 100 ppm. Maintain at 100 ppm or less. Record book indicates less than 100 ppm. Tested during inspection.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Drain cover damaged. Replace drain cover. Immediate Suspension issued. Pump Hayward SP2615x20. Not original pump. Submit updated PDSC form with new pump. Previously installed 1 hp pump. Works with piping installed, drain covers and filter currently installed. Field review done during inspection.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Etching on steps and bench where plaster has worn off to show gunite. Repair steps and bench where needed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail into pool loose. Keep tight and in good repair.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy tied to railing and not accessible. Rope too long. Corrected to 15 ft during inspection and untied.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Opening around skimmer >1/2". Fill opening to prevent hazard. Deck paver loose at entrance to steps. Repair paver.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Could not verify light in pool. Light must be operational for night swimming. Will verify on return visit.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Acid feeder could not be veriifed. Will verify on return visit or after 30 day Intent is issued. Must turn off when pump turns off.

View this inspection on the county portal ›

Sep 28, 2016 14 demerits · 4 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
CPO not present on weekends. CPO must visit property on a daily basis. Intent to Suspsned issued.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door to pool with pushbar not at 54". Must measure from ground to bottom of pushbar at 54". Intent to Suspend issued. Gate from restaurant not self-closing, self-latching. Repair to self-close. Intent to Suspend issued.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Acid feeder could not be verified. Intent to Suspend issued. Feeder must turn off when pump is turned off.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room floor wet due to leak around piping coming from pool. Keep pump room floor dry. Fan in chemical storage room not operable. Provide continuous forced ventilation or cross ventilation.

View this inspection on the county portal ›

Jun 22, 2016 6 demerits · 1 violation
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Oserved 59ft. buoy rope. Rope corrected to 15ft. as required.

View this inspection on the county portal ›

Oct 12, 2015 14 demerits · 3 violations
Inspector comments: 29 - General Comment: Faucet handle in women's turns off directly after pushing. Adjust so that it remains on so hands can be washed properly. Note: HVAC unit for adjacent condo is now operational.Immediate Suspension issued for chlorine. Once corrected, contact Katie to schedule a return visit. Pool to remain closed until return visit made.
#2 · Water quality: disinfectant residual provided by −6
Chlorine in pool at 0.3 ppm. Maintain at least 1.0 ppm. Immediate Suspension issued.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records for alkalinity and acid not recorded from one week. Record weekly.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Acid feeder installed on system. Could not verify whether acid feeder turns off when pump turns off. Return visit required.

View this inspection on the county portal ›

Apr 13, 2015 20 demerits · 5 violations
Inspector comments: Immediate Suspension issued for #2 Once corrected, contact Katie at 704-309-5494 to re-open pool.
#2 · Water quality: disinfectant residual provided by −6
No chlorine in pool. Records show previous day at 0 ppm also. Immediate Suspension issued.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records not maintained daily. Record chlorine, pH, drain check and temp daily.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
New fence installed. >2" under. >4" between post and picket.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Pump leaking. Repair leak.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room floor wet. Keep dry.

View this inspection on the county portal ›

Sep 18, 2014 14 demerits · 3 violations
#3 · Water quality: pool water pH −6
Pool pH at 8.2. Corrected to 7.4.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records not maintained on some days. Keep records daily.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One gate not self-latching. Repair to self-latch. Intent to Suspend issued.

View this inspection on the county portal ›

Jun 25, 2014 6 demerits · 1 violation
Inspector comments: General Comments: Lighting added to chemical storage room. No electrical inspection completed. If not passed by June 30, 2014 permit will be suspended. Skimmer built without equalizer line. Pool has functional autofill. Be sure autofill is functional. Permit will be issued online. Go to Meckpools.Charmeck.org to print permit. Post copy of permit in pool area.
#3 · Water quality: pool water pH −6
pH 7.1. Corrected to 7.2. Maintain between 7.2 and 7.8.

View this inspection on the county portal ›