12demerits
AURORA TOWNHOMES
1347 BRIAR CREEK RD, Charlotte, NC 28205
Year-Round Swimming Pool · NC permit/State ID 2060530317
Latest result12 demerits
Last inspectedOct 15, 2026
Inspections on record18
On record sinceMay 21, 2015
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 21, 2015Lower is betterOct 15, 2026
Inspections & violations
Oct 15, 2026 12 demerits · 3 violations
Inspector comments: Inspection completed with Keith Howard present.
Permit conditions - Flow meter must remain operable. Flow required at 3450 RPM with flow meter reading no greater than 104 GPM to meet flow restriction of the return pipe. Turnover required at 100 GPM. Pump is not meeting turnover. If clarity issues occur, a pump change may be required in the future. If the flow meter exceeds 119 GPM this is a suction hazard due to drain cover flow restriction.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Observed some organic growth on pool walls (algae). Minimal amount therefore no permit action taken. Maintain clean.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Provide no openings in fence and/or gate that allows passage of a four inch diameter sphere. Observed one section of vertical bars near pool gate where a 6 inch gap existed. CDI- repaired.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep the flow meter operational. Observed non operational flow meter. CDI- repaired.
May 18, 2026 12 demerits · 3 violations
Inspector comments: MAIN DRAIN COVERS EXPIRE 5/9/2030
EQUALIZER LINE COVERS EXPIRE 9/30/2029
POOL IS NOT APPROVED FOR NIGHT SWIMMING.
Permit Restriction: Flow meter must remain operable. Flow required at 3450 RPM with flow meter reading no greater than 104 gpm to meet flow restriction of the return pipe. Turnover required at 100 gpm. Pump is not meeting turnover. If clarity issues may require change in the future. If flow meter exceeds 119 gpm suction hazard due to drain cover flow restriction.
POOL IS CLOSED TO SWIMMING BY ORDER OF THE HEALTH DEPARTMENT. CONTACT C. ELMORE AT 704-507-6814 WHEN CORRECTIONS ARE MADE.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed 2 eyeball return fittings missing. All others were in place. No Permit Action taken. Replace the fittings.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed gaps in the fence greater than 4 inches. Fence builit prior to 2010. No Permit Action taken.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed filter system to have a leak such that the pump cannot run without draining/discharging water through the leak. This must be corrected in order for the pool to be open for swimming. Immediate Suspension issued.
Sep 10, 2025 8 demerits · 2 violations
Inspector comments: POOL IS NOT APPROVED FOR NIGHT SWIMMING. OBSERVED SIGN THAT STATED POOL HOURS WERE 10AM TO 8PM. POOL HOURS CANNOT REFLECT ALLOWING THE POOL TO BE OPEN AFTER SUNSET OR BEFORE SUNRISE. IF YOU WISH TO HAVE THE POOL EVALUATED FOR NIGHT SWIMMING, CONTACT C. ELMORE AT 704-507-6814 TO SCHEDULE EVALUATION. WITHOUT NIGHT SWIMMING APPROVAL, POOL CANNOT BE OPEN AFTER DUSK OR BEFORE DAWN.
PERMIT RESTRICTIONS:
FLOW METER MUST REMAIN OPERABLE. FLOW REQUIRED AT 3450 RPM WITH FLOW METER READING NO GREATER THAN 104 GPM TO MEET FLOW RESTRICTION OF THE RETURN PIPE. TURNOVER REQUIRED AT 100 GPM. PUMP IS NOT MEETING TURNOVER. IF CLARITY ISSUES MAY REQUIRE CHANGE IN THE FUTURE. IF FLOW METER EXCEEDS 119 GPM SUCTION HAZARD DUE TO DRAIN COVER FLOW RESTRICTION.
MAIN DRAIN COVERS EXPIRE 5/9/2030
EQUALIZER LINE COVERS EXPIRE 9/30/2029
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Observed 2 eyeball return fittings missing. All others were in place. No Permit Action taken. Replace the fittings.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Pre-2010 fence with gaps > 4" through the fence due to bent /damaged vertical members. .2528(a) Provide no openings in fence and/or gate greater than 4"x4".
Jun 17, 2025 6 demerits · 1 violation
Inspector comments: Permit Restriction: Flow meter must remain operable. Flow required at 3450 RPM with flow meter reading no greater than 104 gpm to meet flow restriction of the return pipe. Turnover required at 100 gpm. Pump is not meeting turnover. If clarity issues, may require change in the future. If low meter exceeds 119 gpm, suction hazard, due to drain cover flow restriction.
POOL HAS PASSED INSPECTION AND BEEN ISSUED PERMIT DECAL. POST PERMIT DECAL AND PAPER POOL PERMIT DOCUMENT AT THE POOL. THE PAPER PERMIT SHOULD BE AVAILABLE WITHIN 1-3 BUSINESS DAYS ON THE HEALTH DEPARTMENT POOL WEBSITE.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Observed KINGS III call box not accepting call-back to the posted number. KINGS III was contacted and was able to make the box function to accept incoming calls. Check the call-back function of the box regularly and ensure that it works properly. If the box is found to be malfunctioning in any way, close the pool until it is corrected. -CDI.
Apr 26, 2024 2 demerits · 1 violation
Inspector comments: Pool does not have night swimming approval. Open Dawn to Dusk.
Observed tiles to be repaired with caulk.
Observed new structures on the deck, they are more than 6 feet away from the water.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladders to have loose treads. Items were repaired.
Oct 10, 2023 4 demerits · 1 violation
Inspector comments: SOME DEPTH AND NO DIVE MARKERS ARE CRACKED. REPLACE THEM PRIOR TO NEXT SEASON.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed gaps in the fence greater than 4 inches. Fence builit prior to 2010. No Permit Action taken.
Jun 6, 2023 38 demerits · 11 violations
Inspector comments: Inspection conducted with Mike Spah. Permit will be issued and available for printing from the website health.mecknc.gov/envhealth/pools. Sticker provided during inspection.
Verified pump system Pentair Intelliflow set at 3110 RPM.
No night swimming. Modify posted hours to indicate that swimming ends at dusk as pool operates year round and 9 pm is after dark during some seasons.
Cracks present in no diving markers and depth markers on pool deck. Replace prior to next season or if deterioration observed.
Repair or replace rusty / loose ladders prior to next inspection as was noted on last inspection.
#3 · Water quality: pool water pH −6
pH 8.0. .2535(1) Maintain pH at 7.2 to 7.8. - Pool water pH at 8.0. Corrected to 7.6 during inspection.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed no recordkeeping for pool since fall 2022. Operator noted pool closed for significant time and turnover of maintenance for conducting checks. No permit action at this time, however, all records must be maintained and in compliance going forward. If pool is closed, documentation should be available noting that.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Ladders shall be corrosion-resistant. Both ladders showing signs of rust/corrosion need repair or replacement as noted on previous inspection. Correct prior to next inspection in order to avoid permit action.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Missing one return fitting on side wall. Corrected during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Pre-2010 fence with gaps > 4" through the fence due to bent /damaged vertical menbers. .2528(a) Provide no openings in fence and/or gate greater than 4"x4".
Pre-2010 fence with wire meshing installed on one section of fencing creating hand/footholds. Mesh with openings > 1.75". .2528(b) Decorative cut-outs on fence and/or gate shall not exceed 1.75 inches.
.2537(b) All gates and doors shall be self-closing, self-latching. One entry gate not sefl-closing and latching. Corrected during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Chairs on side of pool less than 6’ from pool edge. Corrected during inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Kings III phone number call back incorrect due to transition to cellular. Both Kings III operator and Charlotte 911 have 681-393-2676. Posted number at Kings III box corrected to match this. EHS verified phone number does call back Kings III box as required. All other emergency phone requirements in compliance.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Inadequate ventilation in the pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Some items stored up against filter and piping. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Some water on pump room floor. .2533(d) Pump room floor shall be kept dry and free of standing water.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for the backwash line. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526 Glass globes on light fixtures in both restrooms - unable to determine shatterproofing. Replace with shatterproof globes and bulbs or provide documentation that are shatterproof.
Jul 20, 2022 26 demerits · 8 violations
Inspector comments: Inspection conducted with inspector Grace Rutledge and CPO Mike Spah.
Mike Spah is the new CPO for this pool. Updated CDP with his CPO information.
Issues from previous inspection have been corrected.
Pool is a saltwater pool. Observed ladder rusting. Ensure ladders, handrails, and other equipment installed are rated for saltwater use.
Painted contrasting color band starting to fade. Recommend repainting before next pool season if it continues to deteriorate.
Permit issued
No Night Swimming
Paper permit will be available on our website, Meckpools.Charmeck.org, for your records.
#3 · Water quality: pool water pH −6
pH 8.0. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.3.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One eyeball fitting missing in the corner of the pool. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Pre-2010 fence with gaps > 4" through the fence. .2528(a) Provide no openings in fence and/or gate greater than 4"x4".
Pre-2010 fence with wire meshing installed on one section of fencing creating hand/footholds. Mesh with openings > 1.75". .2528(b) Decorative cut-outs on fence and/or gate shall not exceed 1.75 inches.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Pump basket cracked, gap between lip and basket. .2518(e) The circulation system shall include a strainer to prevent hair, lint, and other debris from reaching the pump with openings not more than ¼ inch.
No spare pump basket provided. .2518(e) Provide a spare basket for pump.
Eyeball fitting installed on second vacuum line. .2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. - Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Inadequate ventilation in the pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Some items stored up against filter and piping. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Some piping not labeled. .2518(d) Piping and valves shall be labeled with color codes or labels.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap for the backwash line. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No soap in women's restroom. .2526(j) Provide soap and soap dispenser, no glass, at each sink.
No toilet paper in men's or women's restroom. .2526(l) Provide toilet paper and dispensers in restrooms.
Oct 12, 2021 28 demerits · 6 violations
Inspector comments: POOL IS CLOSED BY ORDER OF THE HEALTH DEPARTMENT. CONTACT C. ELMORE WHEN CORRECTIONS ARE MADE. 704-507-6814. POOL CANNOT REOPEN UNTIL HEALTH DEPARTMENT VERIFIES ALL CLOSURE ITEMS CORRECTED.
pH, chlorine, and main drains must be checked once a day and recorded every day the pool is open. Total Alkalinity and Cyanuric Acid (if Cyanuric Acid is in use) must be checked once a week, 100ppm maximum for Cyanuric Acid. Keep proper records for all daily and weekly requirements.
STAFF AGREED TO EMAIL COPY OF REPORT
NO SIGNATURE DUE TO COVID-19 PRECAUTIONS.
CONTINUE TO FOLLOW ALL RELEVANT COVID RULES
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH to be 8.1 upon arrival. Corrected to 7.3. -CDI
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 4 skimmers total with 1 skimmer missing the weir. Replace the weir.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed ring buoy to have the becket lines torn off. Observed rope to be 35 feet long rather than the required 38 feet for this pool. I.S. Issued. Replace the buoy with a proper ring buoy and attach a line exactly 38 feet long.
.2530(a) Lifesaving equipment includes body hook and pole and USCG approved ring buoy with required rope length.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed fence to have a large gap due to damage, gap 12" wide and more than 2 foot long. Repair the gap as this is an easy entry point for children. Fence built prior to 2010.
#22 · Premises: emergency telephone provided −6
Observed call box to not receive call back. Call out functioned properly. Call back number and address must be both properly posted on the sign and on file with local 911. Call back number must ring back the call box for voice communication with the box. Pool cannot open back up until after the Health Department verifies corrections. I.S. Issued.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at the backwash line.
Apr 28, 2021 14 demerits · 4 violations
Inspector comments: CONTINUE TO FOLLOW ALL RELEVANT COVID RULES
POOL HAS PASSED INSPECTION AND BEEN ISSUED THEIR PERMIT STICKER.
PAPER PERMIT WILL BE AVAILABLE ON-LINE FOR DOWNLOAD AND PRINTING AT OUR POOLS WEBSITE.
POST PERMIT AND STICKER WERE VISIBLE AT POOL AREA.
CPO AGREED TO EMAIL COPY OF REPORT
NO SIGNATURE DUE TO COVID-19 PRECAUTIONS.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 1 weir missing out of 4 total. No Permit action. Replace the weir.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed 1 missing eyeball fitting. Replace the fitting.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed damage to fence bars resulting in gaps greater than 4" inches. Repair the gaps in the fence. No Permit Action, fence built prior to 2010.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed the no air gap at the backwash.
Jul 15, 2020 10 demerits · 3 violations
Inspector comments: POOL HAS PASSED INSPECTION.
STICKER ISSUED. POOL IS NOT APPROVED FOR NIGHT SWIMMING.
IF NIGHT SWIMMING IS DESIRED, A NIGHT SWIMMING EVALUATION MUST BE PERFORMED. CONTACT C. ELMORE AT 704-507-6814 FOR THIS EVALUATION IF NIGHT SWIMMING IS DESIRED.
“issuance of a permit by this department does not negate closure required by Executive Order No. 120, 138, 141 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.”
PAPER PERMIT WILL BE AVAILABLE ON-LINE SO THAT IT CAN BE PRINTED OUT BY THE FACILITY MANAGEMENT. IT MUST BE PRINTED OUT AND POSTED WHERE IT IS VISIBLE FROM THE POOL DECK AREA.
NO SIGNATURE WAS OBTAINED DUE TO COVID-19 SOCIAL DISTANCING
C . ELMORE VERIFIED THE IN-FIELD PLAN REVIEW ITEMS.
1. PUMP IS AN INTELLIFLO VSF 011056, 3HP PUMP SET TO 3110RPM, SPEED 4. IT IS NOT 2HP AS LISTED IN THE PDSC SPREADSHEET. THIS MAY REQUIRE CORRECTION ON THE PDSC FORM. IT WAS NOT TAKEN AS A VIOLATION.
2. MAIN DRAIN, SKIMMER, AND RETURN LINES ARE ALL 2" PIPE.
3. MAIN DRAIN COVERS ARE TWO PARAMOUNT SDX2 COVERS.
4. EQ LINE COVERS ARE FOUR AQUASTAR 6HPHAXXX COVERS.
5. FILTER IS A TR140C, NOT A TR100C. AFTER DISCUSSION WITH SENIOR SPECIALIST OF MCHD IT WAS DETERMINED THAT THIS WAS ACCEPTABLE.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 1 weir missing out of 4 total skimmers. No Permit Action taken.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed gaps in the fence greater than 4 inches. Fence builit prior to 2010. No Permit Action taken.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap in backwash line.
Nov 5, 2019 10 demerits · 3 violations
Inspector comments: Verified PDSC information.
Main Drains and equalizers must be changed prior to installation date May 2020.
Call Chris Sells with questions at 704 476 8678
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed pickets bent on fence allowing for more than 4" between verticals.
.2528(a) Provide no openings in fence and/or gate greater than 4"x4".
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed no diving and depth marker tiles cracked in several locations.
.2537(2) Decks shall be kept in good repair.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Observed men's restroom faucet leaking.
.2526(m) Keep restrooms and fixtures clean and in good repair.
Jun 4, 2019 4 demerits · 1 violation
Inspector comments: Observed painted contrasting colorbands on pool steps not extending to side wall.
Painted contrasting bands must cover the edge of the step all the wall.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed dpeth and no diving tiles cracked.
.2537(2) Decks shall be kept in good repair.
Sep 12, 2018 10 demerits · 2 violations
Inspector comments: Intent to suspend issued.
PDSC information verified.
Facility has 30 days to correct flow meter and pressure gauge or pool permit will be suspended.
Contact Chris Sells with questions or when repairs are complete at 704 567 8678
Observed painted contrasting color bands on steps not going to wall.
Facility is to repaint lines next time the water is drained from the pool
Observed address changed from 1510 Green Oaks Ln to 1337 Briar Creek Rd
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed ring buoy rope over 38 feet.
Corrected during inspection.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed pressure gauge on filter and flow meter not functioning.
.2518(g) Keep flow meter operational.
.2519(k) Provide operational pressure gauge on filter.
May 30, 2017 8 demerits · 2 violations
Inspector comments: G.C. Observed deck to have spots of wear and disrepair. Deck should be repaired before damage becomes worse.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed damage to the fence. Repair such damage
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed vacuum port to be missing the plug. Provide plug within 30 DAYS. ITS ISSUED
Oct 4, 2016 28 demerits · 6 violations
Inspector comments: Observed deck worn in some places. Plan on repairing the deck soon before it gets into worse condition.
#2 · Water quality: disinfectant residual provided by −6
Observed 0.0ppm chlorine. Observed salt system not functioning properly at the time of arrival.
#3 · Water quality: pool water pH −6
Observed pH to be 8.0. pH must be 7.2-7.8
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed some days in September and October to be missing from the log book. Proper daily records must be kept.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed fence and gate damage resulting in gaps >7" and 1 gate not self-closing/self-latching. Repair the fence and gate. Gate and fence fixed. -CDI
#18 · Premises: lifeguards present or warning signs posted −4
Observed warning sign improperly worded and to have lettering smaller than 1 inch.
Apr 26, 2016 24 demerits · 5 violations
Inspector comments: POOL CLOSED TO SWIMMING
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no daily records kept, last records were from February. Observed no records for weekly Cyanuric Acid/Total Alkalinity checks. pH, cl2, and main drains must be checked and recorded daily. This was noted on inspection marked 5/21/15.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed 2 vacuum ports left uncapped. Cap them.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed ring buoy rope to be 35ft. It shall be 38ft. Correct role length to 38ft.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed some bars damaged to allow for gaps greater than 4" wide. Repair fence gaps.
#22 · Premises: emergency telephone provided −6
Observed phone to give 1414 Briar Creek Rd. as the 911 address. This address is not correct. Phone #980-207-0024 was given. This was not listed on the sign. Address and phone # must be correct with 911 and posted at the pool.
May 21, 2015 8 demerits · 2 violations
Inspector comments: 22.) GENERAL COMMENT: Kings III operator had address as 1337 Briar Creek Rd. CMPD operator had address as 1414 Briar Creek Rd. MCHD records indcate address as 1510 Green Oaks Ln. Advised that permanent address will need to be assigned. Once address is assigned, CPO will be notified.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no weekly recordings for cyanuric acid. Maintain weekly records.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed minor pitting in pool deck. Repair.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “AURORA TOWNHOMES” or State ID 2060530317). Inspection type (routine vs. follow-up) is not published in the county's data.