10demerits
MARQUIS AT CARMEL COMMONS
6818 NORTHBURY LANE, Charlotte, NC 28226
Year-Round Swimming Pool · NC permit/State ID 2060530342
Latest result10 demerits
Last inspectedAug 5, 2026
Inspections on record22
On record sinceJun 30, 2016
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jun 30, 2016Lower is betterAug 5, 2026
Inspections & violations
Aug 5, 2026 10 demerits · 3 violations
Inspector comments: Conducted inspection with CPO. Pool remains in good standing and on A status.
PERMIT RESTRICTION - FLOW METER MUST REMAIN OPERABLE WITH A MINIMUM FLOW OF AT LEAST 137 GPM FOR TURNOVER. 3450 RPM SET POINT. NIGHT SWIMMING APPROVED WITH VERIFICATION - 3/2/2023 - REVISIT DUE 2026. NIGHT SWIMMING APPROVED - 3/2/2023
Const. Date: 1/1/2000 Rope Length: 24' Night Swim?: Y
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Weekly total alkalinity and cyanuric acid sporadically not recorded for a few records. Current record up to date. Ensure CA and TA is recorded consistently every week. No permit action.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for
cyanuric acid and total alkalinity weekly.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder missing one end cap.
.2521 Install ladders per manufacturer instructions.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operating and must remain at least 137 gpm. Operator re installed and corrected. No permit action.
.2518(g) Keep flow meter operational.
May 11, 2026 2 demerits · 1 violation
Inspector comments: Conducted inspection with CPO. Pool remains on A status and in good standing.
PERMIT RESTRICTION - FLOW METER MUST REMAIN OPERABLE WITH A MINIMUM FLOW OF AT LEAST 137 GPM FOR TURNOVER. 3450 RPM SET POINT.
NIGHT SWIMMING REVISIT DUE 2026
Const. Date: 1/1/2000 Rope Length: 24' Night Swim?: Y
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No 3' clearance around equipment in pump room. Chemicals in pump room.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting
Oct 22, 2025 16 demerits · 5 violations
Inspector comments: Inspection conducted with CPO Mark Rosenkranz.
Pool permitted for night swimming. Verified pool and deck lighting in good working order.
Permit condition that flow meter remain functional and read at least 137 GPM to meet minimum turnover. Observed at 135 GPM, within 10% +/- accuracy of the flow meter.
Outer rope on ring buoy fraying. Replace with new US Coast Guard approved ring buoy. Will follow up with facility to replace within next two weeks.
Pool throw rope listed in our system as 24 ft. Appears to be less than 1.5x the width of the pool. Will follow up with the facility if changes are needed.
Facility has an automatic chemical feeder. Recommend having the chemical controller recalibrated.
Intent to suspend issued
8)
9)
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Leaves on pool floor and water’s surface. .2537(14) Keep pool surface and pool floor free of debris. - Corrected.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmers full of leaves. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Corrected
Missing one of five weirs. .2518(k) Replace missing weirs.
One skimmer baskets cracked. .2518(k) Replace missing or damaged skimmer basket. - Intent to suspend item.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
One depth marker on pool deck is not slip resistant. .2523(c) Depth markers shall be slip resistant. - Intent to suspend item.
Some no diving markers damaged or are peeling. .2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background. - Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder loose. .2521 Install ladders per manufacturer instructions.
Ladder missing escutcheon plates. .2521 Install ladders per manufacturer instructions.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Fan not working in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
Insufficient ventilation in the chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Bag of dry chemicals on the ground in the chemical storage room. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. - Corrected.
Mar 13, 2025 36 demerits · 8 violations
Inspector comments: Immediate suspension issued for water quality, PDSC information, screws missing in main drain covers.
Other permit items to verify on return visit include recordkeeping, skimmers clean with weirs, gates self closing self latching and openings no greater than 1/2” within 18 inches of latching mechanism, no more than 2” under gate and 6’ clearance around pool.
Pool must remain closed with ‘pool closed’ signage posted at every bather entrance until suspension is lifted by health department. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension.
Send verification of night swimming or have available at return visit
Pump must remain at 3450 RPM and at least 137 GPM
“E” suspension status
#2 · Water quality: disinfectant residual provided by −6
Chlorine 0.1 ppm at time of inspection .2535(4) Maintain chlorine at least 1.0 ppm.
*Immediate suspension item
#3 · Water quality: pool water pH −6
pH 7.0 at time of inspection.
.2535(1) Maintain pH at 7.2 to 7.8.
Immediate Suspension issued. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Weekly total alkalinity and cyanuric acid not recorded each week. No records last few days before inspection. Missing maintenance. 2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for
cyanuric acid and total alkalinity weekly.
*Permit item
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
One main drain cover observed missing 2 screws. Installation instructions require all screws in place. .2537(7) Drain covers shall be in good condition and securely attached.
.2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
Skimmer equalizer lines replaced with no documentation.
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
*Immediate suspension item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmers full of debris.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction.
*permit item
Will check weirs at return visit
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate latches have been replaced with push bars less than 54 inches in height. Side gate not latching. Also side gate stuck on sidewalk when widely opened. Gap under gate greater than 2 inches.
.2537(b) All gates and doors shall be self-closing, self-latching.
.2528(a) Maintain 2" or less under fence and/or gate (post-May 2010).
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism.
*permit item
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Furniture within 6’ of pool.
.2522(a) Provide 6 ft of clear walking space around the pool at all times.
*Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No 3' clearance around equipment in pump room.Chemicals in pump room and dry bag of chemicals on floor. .2533(c) Valves and controls
shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Aug 21, 2024 40 demerits · 9 violations
Inspector comments: Immediate suspension issued for water quality, emergency phone and rope. Pool permit suspended and pool must remain closed with signage posted at all bather entrances until suspension is lifted by health department. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension.
Other permit items to check at return visit: records, weirs, no diving markers, 6’ clearance, flow meter (at least 137 gpm).
“E” permit suspended
#3 · Water quality: pool water pH −6
pH 7.0 at time of inspection.
.2535(1) Maintain pH at 7.2 to 7.8.
Immediate Suspension issued. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Weekly total alkalinity and cyanuric acid not recorded each week. PH out of compliance, recorded, no corrective action. .2535(11) Provide record keeping including daily records of disinfectant
residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for
cyanuric acid and total alkalinity weekly.
*Permit item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir missing at time of inspection. .2518(k) Replace missing weirs.
*Permit item. Will check at return visit
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
No Diving red and black 6'X6' international symbol have been in disrepair. 2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background.
.2523(d) The distance between no diving markers shall be no more than 25 feet perimeter or as the crow flies.
**30 Day Intent to Suspend (ITS). Will check at return visit.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope replaced on buoy, too long. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Provide 24’ rope.
*Suspension item
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Table within 6’ of pool.
.2522(a) Provide 6 ft of clear walking space around the pool at all times.
*Permit item
#22 · Premises: emergency telephone provided −6
Kings III not transferring location to 911.
.2530(f) Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone.
*Suspension item
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operating and must remain at least 137 gpm, permit condition.
*Permit item
.2518(g) Keep flow meter operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No 3' clearance around equipment in pump room.Chemicals in pump room and dry bag of chemicals on floor. .2533(c) Valves and controls
shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
May 2, 2024 4 demerits · 1 violation
Inspector comments: 18.) GENERAL COMMENT -- "WARNING NO LIFEGUARD" SIGNS NEAR GRILL AREA PARTIALLY OBSCURED BY BUSHES -- MAKE VISIBLE - OTHER SIGNS PRESENT
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
"NO DIVING" STICKER NEAR GRILL AREA DAMAGED -- CPO HAS REPLACEMENT
Aug 8, 2023 22 demerits · 6 violations
Inspector comments: 30 Day Intent to Suspend (ITS) issued for deck offsets, door onto pool deck, missing weirs and spare pump basket. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
Night Swimming verified
“W” status
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Weekly total alkalinity and cyanuric acid not recorded each week. .2535(11) Provide record keeping including daily records of disinfectant
residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for
cyanuric acid and total alkalinity weekly. Operator checked and corrected.
*Permit item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 2 of 5 weirs missing at time of inspection. .2518(k) Replace missing weirs.
*Permit item. Will check at return visit
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Clubhouse door not latching at time of inspection.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm.
*Permit item
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck chipped out greater than 1/2" by 3 1/2 FT holes for poles.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
*Permit item
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Operator unable to locate spare pump basket at time of inspection. Intelliflo VSF 011056. .2518(e) Provide a spare basket for pump.
*Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No 3' clearance around equipment in pump room. Liquid chemicals above dry. One bag of dry chemicals fallen on floor. Pool built 2000. .2533(c) Valves and controls
shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up.
Feb 14, 2023 16 demerits · 4 violations
Inspector comments: Issued immediate suspension for water quality. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension. Pool closed with signage posted and must remain closed until suspension is lifted by health department.
Will verify no diving markers and replace missing weirs at return visit.
Pump set to 3450 RPM. Night swimming lights verified
#3 · Water quality: pool water pH −6
pH 7.0 at time of inspection.
.2535(1) Maintain pH at 7.2 to 7.8.
Immediate Suspension issued. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 2 of 5 weirs missing at time of inspection. .2518(k) Replace missing weirs.
*Permit item. Will check at return visit
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
No Diving red and black 6'X6' international symbol have been in disrepair. 2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background.
.2523(d) The distance between no diving markers shall be no more than 25 feet perimeter or as the crow flies.
**30 Day Intent to Suspend (ITS). Will check at return visit.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No 3' clearance around equipment in pump room. Chemicals stored on ground. Pool built 2000. .2533(c) Valves and controls
shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Jul 12, 2022 14 demerits · 4 violations
Inspector comments: 30 Day Intent to Suspend (ITS) for deck trip hazards and records. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
"W" ITS status
Lights out in pool. Must close at dusk until lighting is corrected for Night Swimming. Will verify lighting at return visit.
Inspection with Etienne Fonlon
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Weekly total alkalinity and cyanuric acid not recorded. .2535(11) Provide record keeping including daily records of disinfectant
residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for
cyanuric acid and total alkalinity weekly. Operator checked and corrected.
*Permit items
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate and door propped open at time of inspection. Must remain closed to prevent accidental entry and drowning. Shut and corrected.
Side of building creating horizontal less than 45" in height. Pool built '00.
.2528(b) Horizontals shall not be located less than 45" in height.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Coping chipped out greater than 1/2" by ladder holes, deck has sunk down, greater than 1/2".
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
*Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No 3' clearance around equipment in pump room. Chemicals stored in pump room. Pool built 2000. .2533(c) Valves and controls
shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Mar 17, 2022 20 demerits · 6 violations
Inspector comments: 30 Day Intent to Suspend (ITS) issued for CPO, records, "FT" on depth marker, offsets greater than 1/2", gates self-closing, self-latching, windows onto pool deck opening greater than 4". Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
Changed to "W" ITS status
Inspection with Mark Rosenkrantz
No signature due to COVID
Discussed restroom renovations done without approval and potential issues. Forwarding to pool seniors and will send e-mail then make return visit with more information.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Weekly total alkalinity and cyanuric acid not recorded. .2535(11) Provide record keeping including daily records of disinfectant
residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for
cyanuric acid and total alkalinity weekly.
Unable to verify active CPO for property.
.2537(c) Pool owner shall provide for the operation and maintenance of the pool by a trained pool operator.
*Permit items
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
4 FT depth marker on deck missing "FT" or "feet" .2523(c) Depth markers shall include the word "feet" or symbol "ft".
*Permit item
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One gate not latching at time of inspection. Windows from office and kitchen area of clubhouse, able to open fully, more than 4" onto pool deck.
.2537(b) All gates and doors shall be self-closing, self-latching.
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm.
*Permit items
Side of building creating horizontal less than 45" in height. Pool built '00.
.2528(b) Horizontals shall not be located less than 45" in height.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Coping chipped out greater than 1/2", holes from poles greater than 1/2" and wood slat in deck has sunk down, greater than 1/2".
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
*Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No 3' clearance around equipment in pump room. Chemicals stored in pump room. Pool built 2000. .2533(c) Valves and controls
shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Sink in men's restroom not working at time of inspection. Restrooms had been renovated. Flooring does not appear slip resistant,
could not verify mirrors being shatterproof and observed no hose bib within 50' of restrooms. No floor drains and may not be
sloped to drain.
.
Following up on this item regarding corrective action due to no plan approval and apartment community.
Sep 15, 2021 22 demerits · 6 violations
Inspector comments: Renovations being done in clubhouse. Advisied to submit in-field plan review/approval for work done that is connected to pool, such as restrooms with changes, electrical, chemical storage, equipment room etc. Per CPO, equipment room is being repaired with drywall and ceiling where it has been destroyed, but not other changes.
RPM on pump was 3110 RPM, not 3450, but flow meter was at set requirement of 137 gpm.
Night Swimming not verified. CPO sending verification to Marie Daley at 704-507-6806.
Inspection with Edward Irizarry
No signature due to COVID
#3 · Water quality: pool water pH −6
pH 7.0 at time of inspection.
.2535(1) Maintain pH at 7.2 to 7.8. Operator added chemicals and corrected to 7.2.
Calibration on feeder did not seem correct at time of inspection for water quality. Advised repair.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Weekly total alkalinity and cyanuric acid not recorded. .2535(11) Provide record keeping including daily records of disinfectant
residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for
cyanuric acid and total alkalinity weekly. Operator checked and recorded. Corrected.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 1 of 5 weirs missing at time of inspection. .2518(k) Replace missing weirs. Lack of severity does not warrant permit action.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Side of building creating horizontal less than 45" in height. Back fence behind left of spa has small area where rod is rusted out creating gap, able to move fence. Pool built '00.
.2528(b) Horizontals shall not be located less than 45" in height.
.2528(a) Provide no openings in fence and/or gate greater than 4"x4".
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No 3' clearance around equipment in pump room. Chemicals stored in pump room. Bag of chemicals on floor in chemical storage.
Liquid chemicals over dry in chemical storage. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at
all times. Maintain 3 ft. clear walking space in pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Clubhouse under construction. No sinks, handwashing fixtures available. Port-a-john outside restroom.
Provide sink, water, soap, hand drying at restrooms.
Apr 6, 2021 20 demerits · 5 violations
Inspector comments: Night Swimming lighting and photos sent via Edward Irizarry on 3/31.
Contact Marie Daley 704-507-6806 regarding main drains by 4/13. At least 50% required in place. No permit will be issued until corrected.
Verified pump Pentair IntellifoVSF (not IntellifoVS) 011056 3HP, 2 Aquastar R9MF, 5 Aquastar 6HPHA. Minimum flow must be 137 gpm with operable flow meter.
Clubhouse being remodeled. Ensure permits are pulled and Health Dept informed, if needed regarding doors/windows onto pool deck and restrooms.
Inspection with Rob Harsh
No signature due to COVID
#3 · Water quality: pool water pH −6
pH 7.0 at time of inspection.
.2535(1) Maintain pH at 7.2 to 7.8. Operator added chemicals and corrected to 7.8.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Main drain covers both observed with 3 of 8 screws in place. Covers must be secured and installed with at least 50% of screws and according to instruction. .2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions.
Allowed 7 days to correct. Failure to correct by 4/13 will result in Immediate Suspension of permit. Contact Marie Daley at 704-507-6806 when in compliance to verify.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 1 of 5 weirs missing at time of inspection. .2518(k) Replace missing weirs. Operator replaced and corrected.
Debris in skimmers at time of inspection..2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator emptied and corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No 3' clearance around equipment in pump room. Chemicals stored in pump room. Standing water on floor in pump room at time of inspection. Pool built 2000. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Showers off due to colder weather at time of inspection. .2526(h) Shower(s) shall be provided. Operator turned on water and corrected.
Jul 23, 2020 18 demerits · 5 violations
Inspector comments: ITS for No Diving markers and weirs.
Changed to "W" Intent to Suspend.
No signature due to COVID-19 safety protocol.
Inspection with: Rob Harsh
Report sent to: rharsh@cwsapartments.com; eirizarry@cwsapartments.com; jmorrison@cwsapartments.com
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed weir missing by 5' end. .2518(k) Replace missing weirs.
**30 Day Intent to Suspend (ITS). Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
No Diving red and black 6'X6' international symbol have been removed from deck when coping/deck work was done. .2523(d) No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background.
.2523(d) The distance between no diving markers shall be no more than 25 feet perimeter or as the crow flies.
**30 Day Intent to Suspend (ITS). Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladder missing rubber stopper by 5' side of pool.
.2521 Install ladders per manufacturer instructions.
#22 · Premises: emergency telephone provided −6
No callback number listed at Kings III phone at time of inspection.
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Operator added phone number to signage. Operator believes this is fax number, but when called back, number calls through to emergency phone. If fax line is tied in, ensure emergency phone stays operable at all times and has designated line.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some water in pump room. Chemicals stored in pump room. Pool built prior to 2004. Items around equipment.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Observed pump room without 3 ft clear walking space.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(d) Pump room floor shall be kept dry and free of standing water.
Feb 26, 2020 14 demerits · 4 violations
Inspector comments: Main drains and skimmer equalizer covers expire April 2020. Update covers submit updated PDSC form for approval prior to expiration to avoid permit action.
Contact Marie Daley for Night Swimming visit. Pool will not be permitted for Night Swimming until visit is made.
Note: Showers off at time of inspection
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Weekly total alkalinity and cyanuric acid not recorded. .2535(11) Provide record keeping including daily records of disinfectant
residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for
cyanuric acid and total alkalinity weekly. Operator checked and recorded. Corrected.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One of 5 weirs missing at time of inspection. .2518(k) Replace missing weirs. Lack of severity does not warrant permit action. Operator installing new weir and sending verificationto Marie Daley at 704-507-6806.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operating at time of inspection.
.2518(g) Keep flow meter operational. Opereator adjusted and corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. Pool built prior to 2004. Items around equipment.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Observed pump room without 3 ft clear walking space.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Aug 7, 2019 12 demerits · 4 violations
Inspector comments: Main drains and skimmer equalizer covers expire May 2020. Replace and send updated PDSC for approval prior to expiration to avoid permit action.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Weekly total alkalinity and cyanuric acid not recorded. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator checked and recorded. Corrected. .
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One weir missing at time of inspection. .2518(k) Replace missing weirs. Operator has piece, but is adjusting weir to operate correctly. Severity does not warrant permit action. Send verification to Marie Daley at 704-507-6806.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. Pool built prior to 2004. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Observed dry chemical storage stored in
contact with liquid chemicals.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear
walking space in pump room. Observed pump room without 3 ft clear walking space.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No paper towels in women's restroom. Provide paper towels for hand drying. Operator replaced and corrected.
Jan 31, 2019 16 demerits · 5 violations
Inspector comments: ITS for gates self-closing, self-latching. Contact Marie Daley at 704-507-6806 when corrected to lift ITS.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed no records for the weekly recordings for cyanuric acid and total alkalinity. Corrected during the inspection, pool operator tested cyanuric acid and total alkalinity and recorded records.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed debris build up in skimmers. Ensure to increase cleaning frequency. Corrected during the inspection, the pool operator emptied skimmer baskets.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Observed ladder missing rubber stoppers. Ensure to replace.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2537(b) All gates and doors shall be self-closing, self-latching. Observed two gates that were not self-latching. Ensure to repair. Issued 30 day intent to suspend. Contact Marie Daley at 704-507-6806 to lift ITS when corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. Observed dry chemical storage stored in contact with liquid chemicals.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. Observed pump room without 3 ft clear walking space.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Observed dry pool chemicals stored on the floor. Pool built prior to 2004.
Aug 14, 2018 14 demerits · 5 violations
Inspector comments: ITS for weirs.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Missing weir. Replace with functional weir.
**30 Day Intent to Suspend item. Contact Marie Daley at 704-507-6806 to lift ITS when corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder missing rubber stoppers. Keep in good repair.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Side gate not self-latching at time of inspection. Ensure all gates self-close, self-latch. Operator corrected to self-close, self-latch.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Maintain 3' clear walking space around equipment.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
.2626(d) Provide hose bib so that all parts of restroom can be reached with a 50 ft hose. (Hose bib currently on back entry of clubhouse)
Apr 11, 2018 22 demerits · 7 violations
Inspector comments: ITS for No Diving, doors and holes (offset greater than 1/2")
6) Main drains have 4 of 8 screws in screw holes. At beginning of inspection debris made main drains hard to see. Operator placed vaccumm in the pool. Cleared debris. Verified drain cover with Katie Wilson, Senior pool specialist, at least half screws are in place, drain cover is secure and some drain covers do not require fasteners in the sump to connect.
*Note: Annual permit will NOT be renewed on 5/1/18 unless items are in compliance.
Permit will not permit ‘Night Swimming’ until an onsite visit is conducted before dawn or after dusk to meet compliance with new
regulation. It can still be open during daylight hours (dawn to dusk) without an onsite visit. Lighting requirement includes: Pool illumination is sufficient to illuminate the main drains of the pool and the deck area of the pool so that it is visible at all times the pool is in use. Lighting fixtures are of such number and design to illuminate all parts of the pool, the water, the depth markers, signs, entrances, restrooms, safety equipment and the required deck area and walkways. The illumination is sufficient so that the floor of the pool can be seen at all times the pool is in use.
Please contact Marie Daley at 704-507-6806 directly to schedule a visit to verify lighting is sufficient and this condition is met to
update permit to allow ‘Night Swimming’.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer baskets with debris. Keep clean. Operator emptied. Corrected.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
'No Diving' markers are black and white international symbol. No Diving markers shall be written in four inch letters or international 6"x6" no diving in red and black on a white background. No Diving markers shall be placed at least every 25' apart.
**30 Day Intent to Suspend item. Contact Marie Daley at 704-507 -6806 when items are addressed to lift ITS.
**Note Annual permit will NOT be renewed on 5/1/18 until items are in compliance and may require a pre-permit inspection to re-open.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Rubber caps missing on ladder. Keep in good repair.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door by fitness room not self-latching at time of inspection. Windows onto pool deck able to open greater than 4" if unlocked. Operator installed permanent stopper on windows. Corrected. Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm.
**30 Day Intent to Suspend item. Contact Marie Daley at 704-507 -6806 when items are addressed to lift ITS.
**Note Annual permit will NOT be renewed on 5/1/18 until items are in compliance and may require a pre-permit inspection to re-open.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Holes in deck greater than 1/2". Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
*ITS item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Water on floor in pump room. Pump room floor shall be kept dry and free of standing water.
Maintain 3' clear walking space around equipment.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Showers not working at time of inspection due to piping issues. Keep in good repair and operational.
Nov 2, 2017 20 demerits · 5 violations
Inspector comments: Decking has been redone since last inspection. Replaced with textured material and covered with epoxy and sand.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some leaves and debris in skimmer baskets. Keep clean. Operator cleaned. Corrected during inspection (CDI).
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Rubber ladder stoppers missing on ladder by firepit side. Replace to keep in good repair. Operator ordered.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope measured 31' instead of 24'. Operator shortened. CDI
General Comment: Buoy rope starting to fray. Reccomended replacing soon.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Two gates not self-closing self-latching. Ensure gates self-close, self-latch.
**Issued 30 Day Intent to Suspend
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Two holes in decking for volleyball pole/net more than 1/2". Offsets shall be no more than 1/2". Cover holes.
Feb 14, 2017 10 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed minor amount of debris in skimmers. Keep skimmers free of debris.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed deck chairs witin 6 feet of pools edge. Maintain 6 feet of deck clearance at all points.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed lightbulbs and other non pool items being stored in pump room. Eliminate storage of non pool items in pump room.
Dec 1, 2016 6 demerits · 2 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed minor amount of debris in skimmers. Keep skimmers free of debris.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed paint being stored in chemical room. Eliminate storage of non pool items in pump room and chemical room.
Jun 30, 2016 8 demerits · 3 violations
Inspector comments: Fence is being work on to make room for a gas fire pit
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
ladder missing bumpers
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
fence needs to be repaired and compile with current rules
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
back flow preventer needed on faucet
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “MARQUIS AT CARMEL COMMONS” or State ID 2060530342). Inspection type (routine vs. follow-up) is not published in the county's data.