30demerits
FOREST AT CHASEWOOD, THE
1600 CHASEWOOD DRIVE, Charlotte, NC 28212
Year-Round Swimming Pool · NC permit/State ID 2060530351
Latest result30 demerits
Last inspectedAug 25, 2026
Inspections on record21
On record sinceOct 26, 2016
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Oct 26, 2016Lower is betterAug 25, 2026
Inspections & violations
Aug 25, 2026 30 demerits · 8 violations
Inspector comments: 30 Day Intent to Suspend (ITS) for lighting fixture affixed to wall, weirs and flow meter.
Allowing until 2027 permitting season to correct contrasting color bands at stair entry. If bands are not corrected, pool will NOT be issued permit in 2027.
“W” ITS status
Updated CPO Jonathon Montalvo
No night swimming, Pool not heated.
Pump remains at speed 3, 3110 RPM
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Multiple weirs missing.
.2518(k) Replace missing weirs.
*permit item
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladders missing rubber end caps. Replace.
.2521 Install ladders per manufacturer instructions. Keep in good repair
#13 · Pool maintenance: contrasting band on steps and benches −4
Over 3 inches from pool wall to contrasting band on stairs.
.2521(b) Provide at least 2" painted contrasting color band to edge of stair treads.
.2521(b) Tile shall be no more than one inch from the edge of the tread or adjacent tiles.
*Permit item
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope on buoy too short at time of inspection.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. New rope added and cut to 42’. Corrected.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Chairs within 6’ of pool.
.2522(a) Provide 6 ft of clear walking space around the outdoor pool at all times. Operator moved and corrected.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Lighting fixture not affixed to wall. .2524(c) Lighting fixtures shall not present a hazard to the public.
*permit item
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operation.
.2518(g) Keep the flow meter operational.
*Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals in pump room. No 3’ clearance around equipment. Pool built 1985.n .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
May 5, 2026 10 demerits · 3 violations
Inspector comments: Inspection completed with Jonathan Montalvo present.
Permit condition - Maintain pump at 3110 RPM due to restriction so filter and pipe in pump room.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 3 out of 6 weirs missing. Replace.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladders missing rubber end caps. Replace.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter non operational. CDI- repaired.
Sep 24, 2025 16 demerits · 4 violations
Inspector comments: Inspection completed with Jonathan Montalvo present.
Permit restriction- maintain pump at 3110 RPM due to restrictions of filter and pipe sizing in pump room.
Intent to suspend issued for cracked skimmer lid and cracked concrete on pool deck. Repair both within 30 days or the permit may be suspended. Contact Eli Freese at 704.621.2298 with questions.
Note- new CPO on property is Orlando Williams. He could not provide CPO number during inspection today. Provide within 30 days.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace damaged skimmer lid. Observed skimmer lid cracked with portion missing. Replace within 30 days. Intent to suspend permit issued.
.2518(k) Replace missing weirs. Observed 3 weirs missing.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladder with missing rubber end caps. Replace.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment should be conveniently located. Observed throw rope connected to ring buoy excessively tangled and not easily accessible. CDI- untangled.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Observed large piece of concrete missing on pool deck near pool ladder. Depth of missing piece is approximately 1 inch deep. Intent to suspend permit issued. Correct within 30 days.
Apr 9, 2025 2 demerits · 1 violation
Inspector comments: Inspection completed with Eric Stitt present.
Observed pump set at 3110 RPM as required by permit.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed pool ladders missing rubber end caps. Replace.
Sep 12, 2024 2 demerits · 1 violation
Inspector comments: Inspection completed with Eric Stitt and Rashad Henery present.
Note: ensure total alkalinity and cyanuric acid are recorded at least once weekly in the log book.
RPM on pump was set at 3110 today as is required by permit.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladders with missing rubber end caps. Replace.
May 1, 2024 0 demerits · 0 violations
Inspector comments: Inspection completed with Andrea Easter present.
Observed pump locked at 3110 RPM.
No violations were recorded for this inspection.
Aug 22, 2023 10 demerits · 2 violations
Inspector comments: Inspection completed with Andrea Easter present.
Observed main drains and equalizer coverings replaced but no pool drain suction compliance (PDSC) form submitted to health department. New main drain covers are (2)Waterway 640-213 and (6) Aquastar A8 (same as previous). Waterway covers have higher flow rating than previous installed covers so no suction hazard present. Submit new PDSC form to health department prior to 8/25/2023 or the pool permit may be suspended.
CPO Andrea indicated pool is being chlorinated daily through manual hand feeding. He indicated the erosion feeder is functional but does not want to use as it would raise the cyanuric acid. EHS informed Andrea that chlorination shall be done through the chlorinator for daily use and granular shall be used for shocking purposes only. EHS observed no issues with chlorine in log book.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide USCG approved ring buoy. A rescue tube with lifeguard may be substituted for ring buoy. Observed ring buoy in poor repair with deteriorated beckets. CDI- new buoy added to pool deck with rope at required length attached.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed stuck flow meter.
Mar 28, 2023 6 demerits · 2 violations
Inspector comments: Ensure that cyanuric acid in the pool is less than 100ppm. 100ppm is the maximum allowed.
OBSERVED THAT THE MAIN DRAIN COVERS ARE A10RCFR COVERS THAT EXPIRE 11/2023. THESE MUST BE REPLACED WITH APPROPRIATE COVERS AND THE PDSC FORMS SUBMITTED TO THE HEALTH DEPARTMENT AND APPROVED PRIOR TO THAT EXPIRATION DATE. IT WAS ALSO NOTED THAT THE 6 A8R EQ COVERS ON THE POOL WALL ARE GOING TO EXPIRE MAY 2024, NEXT YEAR. THEIR REPLACEMENT AND APPROVAL WILL BE REQUIRED BEFORE THAT DATE.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed one ladder missing one of the rubber bumper feet. Replace the foot.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed fence not to current spec. due to height in some places and gaps under the fence. Barrier built prior to 2010. No permit action taken.
Sep 15, 2022 6 demerits · 2 violations
Inspector comments: Ensure that cyanuric acid in the pool is less than 100ppm. 100ppm is the maximum allowed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed a ladder to be missing a rubber bumper foot. Replace rubber bumper foot.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed fence to be not constructed to current specifications relative to gaps and spacing under the fence. Fence built prior to 2010. No permit action taken.
Apr 25, 2022 4 demerits · 1 violation
Inspector comments: POOL HAS PASSED INSPECTION AND BEEN ISSUED PERMIT DECAL. PAPER PERMIT WILL BE AVAILABLE ON-LINE AT THE HEALTH DEPARTMENT PUBLIC POOL WEBSITE.
CPO AGREED TO THE EMAIL OF THE REPORT.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed fence not to current spec. due to height in some places and gaps under the fence. Barrier built prior to 2010. No permit action taken.
Oct 14, 2021 24 demerits · 6 violations
Inspector comments: CPO AGREED TO EMAIL COPY OF REPORT
NO SIGNATURE DUE TO COVID-19 PRECAUTIONS.
CONTINUE TO FOLLOW ALL RELEVANT COVID RULES
ENSURE THAT THE 911 CALL BOX SPEAKER IS EVALUATED, IT WAS SUBJECT TO REPEATED VOLUME DROPS DURING TESTING WITH 2 DIFFERENT OPERATORS.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Observed 0.0ppm chlorine at the pool. Pool must maintain 1ppm chlorine for safety. Chlorine cannot be maintained for normal operation by using shock, it must be feed in through the chlorination system. I.S. Issued. Pool is closed by order of the Health Department. Contact C. Elmore at 704-507-6814 to verify correction. Pool cannot reopen without Health Department approval.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Cyanuric Acid not to exceed 100ppm. Observed gaps in the log book. Keep the log book properly. No permit action taken.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed 1 ladder to be missing a rubber bumper foot. Replace the foot.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed throw rope to be 46 feet long. Corrected to 42 feet as is required for this pool. -C.D.I.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed fence to be built prior to 2010. Fence is not built to current spec. No permit action taken.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at the backwash line.
Jun 8, 2021 6 demerits · 2 violations
Inspector comments: CONTINUE TO FOLLOW ALL RELEVANT COVID RULES
POOL HAS PASSED INSPECTION AND BEEN ISSUED THEIR PERMIT STICKER.
PAPER PERMIT WILL BE AVAILABLE ON-LINE FOR DOWNLOAD AND PRINTING AT OUR POOLS WEBSITE.
POST PERMIT AND STICKER WERE VISIBLE AT POOL AREA.
CPO AGREED TO EMAIL COPY OF REPORT
NO SIGNATURE DUE TO COVID-19 PRECAUTIONS.
OBSERVED PHONE CALL-BACK NUMBER CORRECTED AND FUNCTIONAL.
VERIFIED ON-SITE BY C. ELMORE
1. PUMP IS 3HP INTELLIFLO VF 011056 AT 3110RPM
2. ALL PIPING 2"
3. 2 AQUASTAR A10RCFRXXX MAIN DRAIN COVERS
4. 6 AQUASTAR A8RXXX EQ LINE COVERS
5. 1 TR140 FILTER
6. 8 RETURNS AND 6 SKIMMERS
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Fence is not built to current specifications. Observed some gaps > 4 inches. No Permit Action taken, pool built prior to 2010.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at the backwash line.
Oct 8, 2020 14 demerits · 4 violations
Inspector comments: Observed call back number posted at call box (704-537-3712) to not call back the box properly. Call back number must call back to the call box such that the call can be answered by the call box. The number must then also be listed with the local 911 services as the
proper number for the call box and that number shall also be posted at the call box. The above number is posted at the box and
listed with local 911, but it does not contact the call box. This issue must be resolved. C. Elmore will follow-up on or around
10/22/2020 to verify correction. Call C. Elmore at 704-507-6814 when the issue is resolved if it is fixed earlier.
“issuance of a permit by this department does not negate closure required by Executive Order No. 120, 138, 141, 147, or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.”
NO SIGNATURE WAS OBTAINED DUE TO COVID-19 SOCIAL DISTANCING
POOL IS NOT APPROVED FOR NIGHT SWIMMING. IF NIGHT SWIMMING IS DESIRED, A NIGHT SWIMMING EVALUATION MUST BE PERFORMED. CONTACT C. ELMORE AT 704-507-6814 FOR THIS EVALUATION IF NIGHT SWIMMING IS DESIRED.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Observed pool pump changed out, but no PDSC information was given to Health Department so that VGB compliance can be confirmed. New pump is a Inteliflo VSF with 3HP motor. It is currently set on speed 1 at 3000RPM. This must be submitted for PDSC form and In Field Plan Review to the Health Department. Pool is closed until Health Department receives the informtion required and approves the change. -I.S. Issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladder to be missing rubber bumper feet. Replace the feet.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Fence is not built to current specifications. Observed some gaps > 4 inches. No Permit Action taken, pool built prior to 2010.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at the backwash line.
Jun 19, 2020 4 demerits · 2 violations
Inspector comments: PAPER PERMIT WILL BE AVAILABLE ON-LINE SO THAT IT CAN BE PRINTED OUT BY THE FACILITY MANAGEMENT. IT MUST BE PRINTED OUT AND POSTED WHERE IT IS VISIBLE FROM THE POOL DECK AREA.
PERMIT STICKER ISSUED. POOL IS NOT APPROVED FOR NIGHT SWIMMING. IF NIGHT SWIMMING IS DESIRED, A NIGHT SWIMMING EVALUATION MUST BE PERFORMED. CONTACT C. ELMORE AT 704-507-6814 FOR THIS EVALUATION IF NIGHT SWIMMING IS DESIRED.
“issuance of a permit by this department does not negate closure required by Executive Order No. 120, 138, 141 or subsequent Orders in effect unless such Orders are rescinded or superseded by another applicable Order.”
NO SIGNATURE WAS OBTAINED DUE TO COVID-19 SOCIAL DISTANCING
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladder to be missing the rubber bumper feet. Replace the bumper feet.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at the backflow line.
Sep 20, 2019 8 demerits · 3 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladder missing the rubber bumper feet. Replace the feet.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed fence to be 47 inches high in some areas. Observed gaps greater than 4 inches at some points. Fence constructed prior to 2010. No permit action taken.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at backwash line.
May 24, 2019 6 demerits · 2 violations
Inspector comments: POOL IS NOT APPROVED FOR NIGHT SWIMMING.
PERMIT WILL BE ISSUED, STICKER ISSUED BY C. ELMORE.
POOL MAY OPEN FOR SWIMMING
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
OBSERVED SOME FOOT HOLDS AT SOME AREAS OF THE FENCE. FENCE BUILT PRIOR TO 2010. NO PERMIT ACTION TAKEN.
#27 · Equipment room: filter backwash discharged through an air gap −2
OBSERVED NO AIR GAP AT BACKWASH LINE.
Nov 19, 2018 40 demerits · 11 violations
Inspector comments: Intent to Suspend issued for record keeping, test kit, doors and gate issues (self-closing, self-latching, etc.), skimmer basket and weir, deck drain and deck offsets >1/2", provide spec for salt chlorinator.
A new USCG approved ring buoy is required within 30 days.
Updated PDSC form must be submitted within one week or permit will be suspended.
Pentair Challenger CHII-NI-3FE, (2) A10RCFRxxx and (6) 8HPxxx
Note: Could not verify mirrors in restrooms as shatterproof. Mirrors must be shatterproof.
Pool is not approved for night swimming. Pool hours are posted until 8:00 pm. If wanting to utilize until 8:00 pm, a night visit will be required to permit for night swimming.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Some days missing from logs. Chlorine and pH at same value for past month. No cyanuric acid or alkalinity testing recorded. Keep daily logs. Assure cyanuric acid and alkalinity are tested and recorded weekly. Record chlorine, pH and main drain checks daily. Intent to Suspend issued.
Test kit with chlorine cylinder beginning to turn black. Replace test kit. Intent to Suspend issued.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
PDSC form with incorrect main drain covers. No suction hazard. Required updated form within 1 week or permit will be suspended.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One weir missing skimmer and one damaged skimmer basket. Replace weir and basket. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed multiple ladders >6" from pool wall from ladder rung to wall. Maintain 3" to 6" between ladder rung and wall.
One ladder missing end cap. Replace end cap.
>10 ft between ladders at step entry.
Pool built 1/1/1985.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope less than 42 ft. Corrected at time of inspection.
General Comment - Replace USCG approved ring buoy within 30 days. Current buoy is starting to degrade from sunlight. Grab rope is brittle but still intact.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door from restrooms not self-closing, self-latching when restroom hallway door is closed. All doors on to pool deck shall be self-closing, self-latching. Intent to Suspend issued.
3 of 4 gates were locked. Gates shall self-close, self-latch. Intent to Suspend issued.
One gate not closing and does not self-close, self-latch. Operator indicated that all gates except for one were NOT used by the public. If property does not intend to utilize gates and not required by Code Enforcement, gates shall be made to no longer be a gate in order to meet rule of .2528. Intent to Suspend issued.
One gate handle <40" measured from ground to handle. Eliminate foothold. Intent to Suspend issued.
Fence <48" in height in some locations. Pool built prior to 2010.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Damage to deck drain with protrusion greater than 1/2" and some damage to deck at same location. Eliminate offsets greater than 1/2". Intent to Suspend issued.
Some damage to coping near steps. No offsets >1/2". Continue to monitor.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Facility is utilizing salt as primary chlorination. Not approved for salt as primary. Provide spec sheets for salt generator. Intent to Suspend issued.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash line to pit. Pool built 1/1/1985. Provide air gap at backwash line to pit.
#30 · Dressing and sanitary facilities: approved water source, no cross connections −2
No check valve at water line hook up to fill line.
.2512(b) Water introduced into the pool, either directly or by the circulation system, shall be supplied through an air gap, anti-siphon vacuum breaker, or backflow preventer.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bib in pool equipment room or restrooms. Provide hose bib with backflow prevention in restrooms and pump room.
May 2, 2018 8 demerits · 3 violations
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladder missing rubber bumper. Needs to be added to ladder.
**15A NCAC 18A. 2521
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed return fitting cracked. Operator has replacement for return fitting but has yet to replace it due to temperature of water. Needs to be repaired.
**15A NCAC 18A. 2537
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at the backwash line.
**15A NCAC 18A. 2513
Nov 15, 2017 18 demerits · 5 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed cracked skimmer basket. Replace damaged skimmer baskets.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed ladder missing rubber foot. Replace foot.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed cracked return fitting. Replace any damged fittings.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Observed ring buoy throw rope to be almost 44 feet long. 42 foot rope is required for this pool. Rope was corrected to 42 feet.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no air gap at the backwash line.
Jun 26, 2017 6 demerits · 1 violation
#3 · Water quality: pool water pH −6
Observed pH to be 8.1. Corrected to 7.8. Keep pH at 7.2-7.8. -C.D.I.
Oct 26, 2016 22 demerits · 6 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed log book to have last written entry on 10/20/26. Daily and weekly checks must be done and recorded. I.T.S. ISSUED
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Observed vacuum attachment left on pool wall port. Observed some suction from port. Temporary plug was installed. Provide proper threaded port cap. I.T.S. ISSUED
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 2 weirs missing out of 6 skimmers. Replace them.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Observed 1 ladder missing the rubber feet.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Observed a gap on a fence gate larger than 4" within 18 inches of the latch. Block this gap and allow no openings greater than 1/2" in the barrier.
#27 · Equipment room: filter backwash discharged through an air gap −2
Observed no backwash air gap.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “FOREST AT CHASEWOOD, THE” or State ID 2060530351). Inspection type (routine vs. follow-up) is not published in the county's data.