PINEVILLE PLACE

12821 MEADOW CREEK LANE, Pineville, NC 28134
Year-Round Swimming Pool · NC permit/State ID 2060530404
Latest result10 demerits
Last inspectedAug 10, 2026
Inspections on record17
On record sinceJun 26, 2017

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

01632 Jun 26, 2017: 12Nov 15, 2017: 18Feb 21, 2018: 16Aug 29, 2018: 26Jun 13, 2019: 26Jul 31, 2019: 24Apr 27, 2020: 10Mar 30, 2021: 16Aug 10, 2021: 14Apr 12, 2022: 16Jul 20, 2022: 20Mar 6, 2023: 18Sep 18, 2023: 12Apr 11, 2024: 10Jul 2, 2025: 8Jun 1, 2026: 32Aug 10, 2026: 10
Jun 26, 2017Lower is betterAug 10, 2026

Inspections & violations

Aug 10, 2026 10 demerits · 4 violations
Inspector comments: Conducted inspection with CPO. Pool remains on A status and in good standing. Permit Restriction: Flow meter must remain operable. Flow required no greater than 150 gpm due to drain cover flow restriction. Suction Hazard.Note: EMBLEM ON POOL FLOOR APPROVED WITH LRV OF 80 - DOCUMENTATION PROVIDED Const. Date: 1/1/1985 Rope Length: 50' Night Swim?: N
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. One rubber end cap missing from one ladder. Replace
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Provide no openings in fence and/or gate that allows passage of a four inch diameter sphere. Some parts of the back fence and fence beside building bent/damaged creating openings of greater than 4 inches. Pre 2010 pool. Operator bent the rungs back into place. No permit action.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Lights out in chemical room. No 3' clearance around all equipment. Ventilation not working in chemical or pump room. Pool built '85. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No floor drains in restrooms. .2526(c) Floor drains shall be provided in restrooms.

View this inspection on the county portal ›

Jun 1, 2026 32 demerits · 8 violations
Inspector comments: Changed to “A” Open for Business and conducted inspection. Issued permit sticker. Flow meter has been changed to 5% accurate Aquastar flowstar. Manager updating and submitting PDSC form to pdsc@mecknc.gov Flow required no greater than 150 GPM due to drain cover flow restriction. Suction hazard. Inspection with Yasmani Perez and Rayshell Mullins
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Flow meter reading 180 gpm at time of inspection. Permit restriction of 150 gpm or less for suction hazard. Operator adjusted skimmer that was plugged and flow decreased to 150 gpm. Corrected. Send updated PDSC form with new 5% flow meter to pdsc@mecknc.gov
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
One depth marker missing “FT” .2523(c) Depth markers shall include the word "feet" or symbol "ft". Operator added “FT” and corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders greater than 6” from wall. Some ladders loose at time of inspection. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. .2521 Install ladders per manufacturer instructions.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Buoy rope too long at time of inspection. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator cut to 50 ft and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Front gate not latching at time of inspection. .2528(a) Gates shall be self-closing, self-latching. Operator adjusted and corrected.
#22 · Premises: emergency telephone provided −6
Emergency phone missing callback number on signage. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Operator added and corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Lights out in chemical room. No 3' clearance around all equipment. Ventilation not working in chemical or pump room. Pool built '85. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No floor drains in restrooms. .2526(c) Floor drains shall be provided in restrooms.

View this inspection on the county portal ›

Jul 2, 2025 8 demerits · 4 violations
Inspector comments: Pool permitted. No night Swimming. Flow meter must remain operational, no greater than 150 GPM, suction hazard. Verified PDSC information. Pool not heated. “A” Open for Business
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladders greater than 6” from wall. Some ladders loose at time of inspection. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. .2521 Install ladders per manufacturer instructions.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Chemicals stored in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Sink broken and not working at time of inspection. .2526(m) Keep restrooms and fixtures clean and in good repair.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No floor drains in restrooms. .2526(c) Floor drains shall be provided in restrooms.

View this inspection on the county portal ›

Apr 11, 2024 10 demerits · 3 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
POOL DIRTY WITH LEAVES -- CLEAN
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
SKIMMERS FULL OF LEAVES -- CLEAN
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
LADDERS >6" FROM WALL, MISSING END CAPS -- REPAIR

View this inspection on the county portal ›

Sep 18, 2023 12 demerits · 5 violations
Inspector comments: Buoy starting to wear, beckets starting to detach. Advised replacing (w/ USCG approved buoy) before in disrepair to avoid permit action at future inspection and in case of emergency. Inspection with Camilo Hermosillo. No Night Swimming
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Safety rope at breakpoint floats not spaced apart at time of inspection. .2523(e) Safety rope shall be marked with colored floats, 5 ft. apart or less. Operator adjusted floats and corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder missing rubber stopper. Ladder greater than 6" from wall. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. .2521 Install ladders per manufacturer instructions.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate gap greater than 4”. Some gaps in fencing and gate greater than 4" where rods are bent. Pool built '85. .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Operator bent rods and corrected gate gaps greater than 4".
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Lights out in pump and chemical room. No 3' clearance around all equipment. Ventilation not working in chemical or pump room. Pool built '85. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2533(b) Provide sufficient lighting in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. .2513(b) Filter backwash shall be discharged through an air gap. Pool built 85.

View this inspection on the county portal ›

Mar 6, 2023 18 demerits · 6 violations
Inspector comments: 30 Day Intent to Suspend (ITS) issued for contrasting color bands at steps. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension. Note: Phone connection breaking up some and address did not indicate “Pool phone”, but another apartment number. Phone still operable and correct physical address, so no permit action taken, but advised speaking with the phone company and 911 to ensure exact location is correct and clearly audible for pool, in case of emergency. Keep buoy and rope on deck. Discussed record keeping for maintenance (backwash, chemicals, vacuum, etc should be notes not “check mark”). No Night Swimming
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some debris in skimmers at time of inspection. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator cleaned and corrected.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Safety rope at breakpoint missing at time of inspection. .2523(e) Safety rope shall be marked with colored floats, 5 ft. apart or less. Operator had pool voluntarily closed at time of inspection, but rope with floats were in equipment room. Operator obtained rope and corrected.
#13 · Pool maintenance: contrasting band on steps and benches −4
Contrasting color band on stair tread over 2”, almost 3” to edge of pool wall. .2521(b) Provide at least 2" contrasting color band to edge of stair treads. .2521(b) Provide at least 2"x 2" tile for contrasting color band within 1" of adjacent tiles and edge of the stair tread. *Permit item. 30 Day Intent to Suspend (ITS) item, time was allowed from last inspection. Permit cannot be renewed without compliance on this item.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate gap greater than 4”. Some gaps in fencing and gate greater than 4" where rods are bent. Pool built '85. .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Operator bent rods and corrected gate gaps greater than 4". Back corner area of fencing still missing rod with gap over 4”.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Lights out in pump and chemical room. Chemicals stored in pump room. No 3' clearance around all equipment. Ventilation not working in chemical or pump room. Pool built '85. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(b) Provide sufficient lighting in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. .2513(b) Filter backwash shall be discharged through an air gap. Pool built 85.

View this inspection on the county portal ›

Jul 20, 2022 20 demerits · 7 violations
Inspector comments: Repair contrasting color bands prior to 2023 season. Failure to correct will result in NO PERMIT for 2023.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records missing daily main drain checks at time of inspection. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added main drain checks. Corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder missing rubber stopper. Ladder greater than 6" from wall. .2521(b) Distance between wall and ladder rung shall range 3" to 6" measured from wall. .2521 Install ladders per manufacturer instructions.
#13 · Pool maintenance: contrasting band on steps and benches −4
Contrasting color band on stair tread over 2”, almost 3” to edge of pool wall. .2521(b) Provide at least 2" contrasting color band to edge of stair treads. .2521(b) Provide at least 2"x 2" tile for contrasting color band within 1" of adjacent tiles and edge of the stair tread. *Permit item. Allowing until 2023 to correct due to maintenance required to address and not noted previously when work was completed.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Some gaps in fencing and gate greater than 4" where rods are bent. Pool built '85. .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Operator bent rods and corrected gate gaps greater than 4".
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Lights out in pump and chemical room. Chemicals stored in pump room. Water on floor in equipment room. No 3' clearance around all equipment. Ventilation not working in chemical or pump room. Pool built '85. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(b) Provide sufficient lighting in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room. .2533(d) Pump room floor shall be kept dry and free of standing water.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. .2513(b) Filter backwash shall be discharged through an air gap.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No toilet paper in restrooms. Provide toilet paper. CPO provided and corrected.

View this inspection on the county portal ›

Apr 12, 2022 16 demerits · 5 violations
Inspector comments: Intent to Suspend (ITS) issued for tiling missing on pool wall. Permit expires April 30, 2022. Correct before this date to keep active permit. Contact Marie Daley at 704-507-6806 went into compliance to lift ITS. Changed to “W” ITS status Allowing until 2023 permit to correct contrasting color bands.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Tiling of pool wall cracked out. .2537(14) Keep pool surface and pool floor free of debris and in good repair. *Permit item.
#13 · Pool maintenance: contrasting band on steps and benches −4
Contrasting color band on stair tread over 2”, almost 3” to edge of pool wall. .2521(b) Provide at least 2" contrasting color band to edge of stair treads. .2521(b) Provide at least 2"x 2" tile for contrasting color band within 1" of adjacent tiles and edge of the stair tread. *Permit item. Allowing until 2023 to correct due to maintenance required to address and not noted previously when work was completed.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate gap greater than 4”. Some gaps in fencing and gate greater than 4" where rods are bent. Pool built '85. .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Operator bent rods and corrected gate gaps greater than 4". Back corner area of fencing still missing rod with gap over 4”.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Lights out in pump and chemical room. Chemicals stored in pump room. No 3' clearance around all equipment. Ventilation not working in chemical or pump room. Pool built '85. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(b) Provide sufficient lighting in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. .2513(b) Filter backwash shall be discharged through an air gap.

View this inspection on the county portal ›

Aug 10, 2021 14 demerits · 5 violations
Inspector comments: ITS for depth marker visibility and floats on breakpoint rope. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS. "W" Intent to Suspend status Inspection with Andy Lazenby No signature due to COVID. Pool not heated
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
All depth markers not clearly visibly due to deck paint at time of inspection. 2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible. *30 Day Intent to Suspend (ITS) item. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Safety rope at breakpoint missing floats at time of inspection. .2523(e) Safety rope shall be marked with colored floats, 5 ft. apart or less. *30 Day ITS item.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Some gaps in fencing and gate greater than 4" where rods are bent. Pool built '85. .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Operator bent rods and corrected gate gaps greater than 4".
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Lights out in pump and chemical room. Chemicals stored in pump room. No 3' clearance around all equipment. Ventilation not working in chemical or pump room. Pool built '85. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(b) Provide sufficient lighting in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Shower drain not draining at time of inspection. .2526(m) Keep restrooms and fixtures clean and in good repair.

View this inspection on the county portal ›

Mar 30, 2021 16 demerits · 5 violations
Inspector comments: A new motor has been placed on pool pump (same pump). Advised CPO an electrical permit must be pulled for this work. Notifying Code Enforcement of this change. Pool shall remain voluntarily CLOSED until proper electrical permit is received. Major renovations including plumbing in clubhouse with pool restrooms have been completed since last inspection, as noted on item 29 on inspection. Contact Katie Rudisill for information on permits and in-field plan review requirements. This item is under investigation for more information. If the above items are not corrected prior to expiration of permit, 4/30/2021, the pool will NOT HAVE A VALID PERMIT TO OPERATE and MUST REMAIN CLOSED. *Note: Deck is starting to peel, but not severe enough to warrant permit action at this time. If deck work is done, an in-field plan review application must be submitted to the Health Dept for review and approval. Pool not heated. No Night Swimming. Inspection with Andy Lazenby No signature due to COVID
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records missing daily main drain checks at time of inspection. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added main drain checks. Corrected.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
All depth markers not clearly visibly due to deck paint at time of inspection. 2523(c) Depth markers shall be 4 inches in height and of a contrasting color with the background, clearly visible. Operator filled in markers with sharpie to make visible. Corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Some gaps in fencing greater than 4" where rods are bent. Pool built '85. .2528(a) Provide no openings in fence and/or gate greater than 4"x4".
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Lights out in pump and chemical room. Chemicals stored in pump room. No 3' clearance around all equipment. Ventilation not working in chemical or pump room. Pool built '85. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. .2533(b) Provide sufficient lighting in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Clubhouse has been renovated and restrooms have been removed and combined to one restroom with sink and toilet. CPO not aware of any plan review for the renovations. Mirrors have no documentation of shatterproof, did not observe hose bib or backflow prevention. Advised plan review will need to be submitted and contact Katie Rudisill at 704-309-5494 or katie.rudisill@mecklenburgcountync.gov to verify approval for plan review. Failure to provide adequate in-field plan review for major pool changes will result in NO PERMIT as of 5/1/2021. .2526(k) Provide shatterproof mirrors.

View this inspection on the county portal ›

Apr 27, 2020 10 demerits · 4 violations
Inspector comments: Advised repairing depth markers where paint is starting to fade legibility of numbers. Confirmed PDSC information: 2 Aquastar WAV12WR and 5 Aquastar A10RCFR Changed to "A" Open for Business, valid permit, with condition of staying closed to public by Executive Order-120, or other Orders, outlined in permit. Provided new annual permit sticker. No Night Swimming. Operator unable to sign due to COVID-19 protocol and safety precautions to not share equipment. Inspection completed with: Andy Lazenby Sent report to: Kimberly Bradley Andy Lazenby
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder loose at time of inspection. .2521 Install ladders per manufacturer instructions. Operator tightened and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Some gaps in fencing greater than 4" where rods are bent. Pool built '85. .2528(a) Provide no openings in fence and/or gate greater than 4"x4".
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some water on pump room floor. .2533(d) Pump room floor shall be kept dry and free of standing water.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Restrooms not in use at time of inspection due to COVID-19. No toilet paper, soap, paper towls and hot water in men's restroom over 110 degrees F. .2526(i) Water in restrooms shall not exceed 110 F. .2526(j) Provide soap and soap dispenser, no glass, at each sink. .2526(l) Provide toilet paper and dispensers in restrooms. Provide hand drying in restrooms.

View this inspection on the county portal ›

Jul 31, 2019 24 demerits · 7 violations
Inspector comments: Main drains and skimmer eqaulizer covers expire April 2020. Update drain covers and submit PDSC information for approval prior to expiration to avoid permit action. Unable to verify chlorinator at time of inspection (no flow with pump).
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Weekly total alkalinity and cyanuric acid check missing on records at time of inspection. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator checked and recorded. Corrected.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Skimmer equalizer line blocked/plugged in skimmer at time of inspection. .2539(b) All suction fittings shall be installed in accordance with the manufacturer's instructions. Operator removed and corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder loose. Keep tight and in good repair.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Some openings in fencing over 4". .2528(a) Provide no openings in fence and/or gate greater than 4"x4". Pool built in 1985.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Lighting fixture not secured to pool wall at time of inspection. .2524(c) Lighting fixtures shall not present a hazard to the public. Operator secured and corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some standing water on floor in pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No toilet paper, soap or paper towels in restroom at time of inspection. .2626(j) Provide soap and soap dispenser, no glass, at each sink. .2626(l) Provide toilet paper and dispensers in restrooms. Operator stocked and corrected.

View this inspection on the county portal ›

Jun 13, 2019 26 demerits · 7 violations
Inspector comments: Permitted pool. Placed in "A" status. Posted local permit sticker. No Night Swimming permitted. Approved logo with light reflectected value greater than 50% white. (80% LRV). Provided copy of approval to operator. Note: Main drain and skimmer equalizer covers expire April 2020 and must be replaced for 2020 permit.
#3 · Water quality: pool water pH −6
pH 7.0 at time of visit. .2535(1) Maintain pH at 7.2 to 7.8. Operator corrected to 7.4.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Pool closed at time of visit, but no cyanuric acid readings or maintenance. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added maintenance and will start weekly CA readings. Corrected.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer baskets with leaves and debris. Keep clean. Operator cleaned. Corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder loose. Keep tightened. .2521 Install ladders per manufacturer instructions.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Fencing bent creating more than 4" gaps between vertical members. Ensure 4" or less is maintained between vertical members. Pool built prior to 2010 (1985), so no permit action taken. Note: If new constrcution is done on fencing and more than 50% is altered thenn fence will no longer be grandfathered in and must meet total compliance of .2528. Contact Environmental Health at 980-314-1620 and apply for any changes/renvations made to pool area PRIOR to work.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Feeder not working properly at time of visit, not shutting off when pump off, but also not feeding. .2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. .2535 Automatic acid feeder shall be automatically prevented from operating when the circulation pump is not in operation. Operator unplugged completely and corrected. There is additional tablet chlorinator in place.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Labeling faded off vaccum line. .2518(d) Piping and valves shall be labeled with color codes or labels.

View this inspection on the county portal ›

Aug 29, 2018 26 demerits · 7 violations
Inspector comments: Establishment painted logo and lettering on pool bottom less than than required (less than 50% black, between value of 2 and 3 on grey scale and not in compliance). .2514c. Pool bottom color must meet compliance for 2019 permit. Submit plans to Katie Wilson 704-309-5494 for approval or eliminate all coloring less than 50% black. 15) Required pool rope length had been listed at 38' (derived from shortest width of pool) in deep end. Pool width (at second largest area/width on shallow end) is 52', requiring 50' rope length. Due to error in measurement, updating information and requirement. Operator purchasing new rope immediately and will verify within week. .2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Log book missing weekly Cyanuric Acid and Total Alkalinity. Provide record keeping including daily records of disinfecant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator checked and recorded. Corrected.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer baskets with leaves and debris. Keep clean. Operator cleaned. Corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Some ladders loose. Keep tightened. Ruber stoppers missing on ladders. Replace to keep in good repair.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate with gap greater than 4". Fencing bent creating more than 4" gaps between vertical members. Ensure 4" or less is maintained between vertical members. Operator corrected gaps in gate to meet compliance. Corrected. Pool built prior to 2010, so no permit action taken. Note: If new constrcution is done on fencing and more than 50% is altered then fence will no longer be grandfathered in and must meet total compliance of .2528. Contact Environmental Health at 980-314-1620 and apply for any changes/renvations made to pool area.
#18 · Premises: lifeguards present or warning signs posted −4
Signage not visile from both entrances. All pool signage shall be visible upon entrance to the pool and permanently affixed. Operator moved. Corrected.
#22 · Premises: emergency telephone provided −6
Telephone number listed on Kings III phone not matching 911 call back (911 listed two callbacks, 980-215-0296, 704-511-0266), neither directly dial back to emergency phone. Emergency notification systems must provide 24 hr monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Indentification for the phone. Phone routing information, but not able to callback. Did not issue Immediate Suspension due to phone correctly operating, but phone line needs to be verified and corrected immediately. Will verify compliance. Operator corrected signage to reflect correct number. Contact Marie Daley at 704-507-6806 when addressed.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
No paper towels in restroom. Provide paper towels. Corrected.

View this inspection on the county portal ›

Feb 21, 2018 16 demerits · 5 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer baskets with leaves and debris. Keep clean. Operator cleaned. Corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Some ladders loose. Keep tightened. Ruber stoppers missing on ladders. Replace to keep in good repair.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Fencing bent creating more than 4" gaps between vertical members. Ensure 4" or less is maintained between vertical members. Pool built prior to 2010, so no permit action taken. Note: If new constrcution is done on fencing and more than 50% is altered then fence will no longer be grandfathered in and must meet total compliance of .2528. Contact Environmental Health at 980-314-1620 and apply for any changes/renvations made to pool area.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
No spare pump basket at time of visit. Provide spare pump basket. Operator ordered during inspection and is sending verification with receipt and photo with date for corrective action.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
No paper towels or soap in restrooms. Keep stocked. Operator replaced and corrected.

View this inspection on the county portal ›

Nov 15, 2017 18 demerits · 5 violations
Inspector comments: 13) Issued 30 Day Intent to Suspend for this item. Contact Marie Daley at 704-507-6806 when corrected. **Note: Establishment may be changing ownership. If changes are made to the pool an in-field plan review may be necessary. Contact Katie Wilson at 704-309-5494 for changes made to the pool, including decking, drains, plumbing, fencing, etc.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer baskets with leaves and debris. Keep clean. Operator cleaned. Corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Some ladders loose. Keep tightened. Rubber stoppers missing on ladders. Replace to keep in good repair.
#13 · Pool maintenance: contrasting band on steps and benches −4
Contrasting band faded and not clearly visible on steps into pool. The leading edge of stair treads shall be marked with a contrasting color band or line at least 2" wide visible from above the stairs. **Issued 30 Day Intent to Suspend for this item. Contact Marie Daley at 704-507-6806 when corrected. **Note: Establishment may be changing ownership. If changes are made to the pool an in-field plan review may be necessary. Contact Katie Wilson at 704-309-5494 for changes made to the pool, including decking, drains, plumbing, fencing, etc.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate did not self-latch at time of inspection. Ensure gates are self-closing and self-latching. Operator corrected. Horizontal piece added to entrace gate creating vertical height between horizontals to create footholds less than 45". Maintain at least 45" in height between horizontals. Operator removed piece that was creating foothold. Corrected. Fencing bent creating more than 4" gaps between vertical members. Ensure 4" or less is maintained between vertical members. Operator bent back. Corrected. Reccomended adding veritcal members to ensure gaps do not exceed 4"
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Provide spare pump basket.

View this inspection on the county portal ›

Jun 26, 2017 12 demerits · 4 violations
Inspector comments: Pump=Pentair whisperflo XF 3HP MD= Aquastar WAV12WRxxx EQ= (4) Aquastar 6HPxxx (1) Aquastar A10RCFRxxx
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed debris on pool floor
#10 · Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints −2
Re-paint the steps and breakpoint in pool during closing of the pool
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Provide safety bumpers on the ladders
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed cracking and chipping on the pool decking. Recommend re-surfacing the pool deck.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “PINEVILLE PLACE” or State ID 2060530404). Inspection type (routine vs. follow-up) is not published in the county's data.