10demerits
SYCAMORE AT TYVOLA
707 SYCAMORE CENTRE DR, Charlotte, NC 28217
Year-Round Swimming Pool · NC permit/State ID 2060530494
Latest result10 demerits
Last inspectedMay 19, 2026
Inspections on record15
On record sinceMay 1, 2019
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 1, 2019Lower is betterMay 19, 2026
Inspections & violations
May 19, 2026 10 demerits · 2 violations
Inspector comments: Conducted inspection with CPO Michael. Suspension issued for chlorine. Records must be properly updated upon return visit or permit may not be issued. Pool placed on E status and must close. Call EHS Devon when corrected and ready to re open 7049981122
NOTES: 1) SEE PDSC FORM FOR DOCUMENTATION OF IMPELLER/PUMP 2) APPROVED FOR NIGHT SWIMMING 5/30/2023 - *REVIST 2026*
Const. Date: 5/1/2018 Rope Length: 50' Night Swim?: Y Night Swim Year: 2026
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm.
Chlorine at 0ppm. Immediate suspension item.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
No weekly TA or CA readings for months. Ensure CA and TA readings are captured weekly. Intent to suspend item.
Sep 22, 2025 8 demerits · 3 violations
Inspector comments: Conducted inspection with CPO Joseph Raver. Intent to suspend issued for gate. Call EHS Devon when corrected 7049981122. Items must be corrected within 30 days or intent to suspend may be issued.
Const. Date: 5/1/2018
Rope Length: 50'
New housing/motor 2024
- see PDSC form for
documentation of impeller
and pump -
2024
APPROVED FOR
NIGHT SWIMMING
5/30/2023 - needs re verification in 2026
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Ladder closest to clubhouse missing both end caps.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism.
1.5inch gap between gate and fence post. Repair to 1/2in or less. Intent to suspend item.
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present.
Gate by pump room getting stuck on concrete when opened and not self closing. Intent to suspend item.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
.2526(h) Shower(s) shall be provided.
Shower not operational
Apr 9, 2025 16 demerits · 3 violations
Inspector comments: Conducted inspection with CDP Joseph Raver. Immediate suspension issued for chlorine levels and ring buoy rope. Call EHS Devon Moeller when items are corrected and ready to reopen 7049981122.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Chlorine at 0ppm. Immediate suspension item.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy with rope more than 50’. Ensure ring buoy rope is 50’. Immediate suspension item.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile. Wood planking around skimmer by club house door approaching 1/2” offset. Address before offset becomes 1/2” or greater. No permit action.
Sep 10, 2024 14 demerits · 3 violations
Inspector comments: Inspection conducted with CPO Raver. Immediate suspension issued for switched filtration pump. Submit updated PDSC to Health Department for approval.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. No weekly CA readings for months. Ensure CA readings are captured weekly. Intent to suspend item.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. Filtration pump switched out without prior approved paperwork. Submit new PDSC for approval with new pump information. Immediate suspension item.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. Gate to left of pool not latching shut upon closure. Gate must self close and latch every time. Intent to suspend item.
Feb 8, 2024 28 demerits · 7 violations
Inspector comments: Met with Derrick Morris & Joseph Raver. Current CPO Derrick is leaving. Joseph is taking over as CPO. IMS issued for low chlorine levels. Chlorinator not operational. Manual chlorination to maintain chlorine levels is not approved. Chlorinator in pump room must be repaired. Several additional 30 day items found not in compliance. EHS recommends repairing prior to return visit. Contact Devon Moeller at 704-998-1122 once items are corrected and ready for re-inspection.
Inspection conducted by Anglecia Askew under supervision of Devon Moeller.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Chlorine at .5 ppm. Immediate suspension item.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. No records present since 1/6/2024 due to CPO change. Maintain daily and weekly records as needed.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Some debris on pool floor.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Debris buildup in skimmer baskets.
.2518(k) Replace missing or broken weirs. One weir missing. Replace.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install ladders per manufacturer instructions. Ladder closest to clubhouse missing both end caps.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
.2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. CPO indicated chlorinator is not functional. Repair or replace chlorinator.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Flow meter not operational. EHS unable to get flow reading. Repair or replace.
Sep 7, 2023 22 demerits · 5 violations
Inspector comments: Inspection conducted with operator, Derrick. 30 day intent to suspend the permit issued for missing window limiter, gate not latching upon closure, flow meter not operational and chemical feed system does not turn off when circulation system is off. Once all items are corrected, call Hope McIntosh at 980-229-7549 to request a re-visit or a return visit will happen at 30 days. If all items are not in compliance at that time, permit may be suspended. During re-visit, EHS will also review record keeping and check pool chemistry as there is some question to accuracy of records documented and consistency of appropriate water chemistry. EHS strongly recommends having chemical feed system re-calibrated.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Ph at 8.0. Operator corrected to 7.8
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Some debris on pool floor. Operator cleaned during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
.2528(a) Access gates shall swing away from the pool and be self-latching, self-closing unless an attendant AND lifeguard are present. Gate to left of pool not latching shut upon closure. Gate must self close and latch every time. *permit item
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Missing window limiter on window from fitness center onto pool deck. Repair or replace. *permit item
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
.2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation.
.2535 Automatic acid feeder shall be automatically prevented from operating when the circulation pump is not in operation.
Automatic chemical feed system does not automatically turn off when circulation system is shut down. Electrical work recently done in pump room may have disabled pressure switch system. Acid and chlorine feed system must automatically turn off when pump system shuts down. *permit item
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Flow meter not operational. EHS unable to get flow reading. Repair or replace. *permit item
Feb 21, 2023 36 demerits · 8 violations
Inspector comments: Inspection conducted with Derrick Morris and Joe Raver.
Immediate suspension of permit issued due to cl less than 1.0 and emergency phone box not operational. Pool closed and signs posted during inspection. Pool must remain closed until both items are corrected and verified by Mecklenburg County Public Health. Ensure circulation and chlorination system is operating properly. Once corrected, call Hope McIntosh at 980-229-7549 to request a return visit to open.
Once permit has been re-instated, if other permit items remain out of compliance, a 30 day intent to suspend the permit will be issued. These permit items include acid pump system that does not shut down when pump shuts down and flow meter not operational.
Pool lights verified to be operational during inspection. Night swimming will be allowed to continue once permit is re-instated.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Chlorine at .4 ppm. Immediate suspension item.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
.2537(14) Keep pool surface and pool floor free of debris. Some debris on pool floor. Maintain clean.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Some debris buildup in skimmer baskets. Cleaned during inspection
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy with rope at 47’. Corrected to 50 during inspection.
#22 · Premises: emergency telephone provided −6
.2530(f) Emergency phone shall remain operable. Emergency phone box does not connect. Phone must connect - Emergency notification systems must provide 24 hr. monitoring, be capable of routing calls to 911, and be able to electronically transfer Automatic Number and Locator Identification for the phone.
Immediate suspension of permit.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
.2535 Automatic acid feeder shall be automatically prevented from operating when the circulation pump is not in operation. Automatic acid feeder does not automatically shut off when pump circulation system is shut down. Intent to suspend ite
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Flow meter not operational.
Intent to suspend item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Water on pump room floor.
Sep 15, 2022 28 demerits · 7 violations
Inspector comments: Send verification of night lighting to Marie Daley at 704-507-6806.
#3 · Water quality: pool water pH −6
pH 8.2 at time of inspection.
.2535(1) Maintain pH at 7.2 to 7.8. Operator corrected to 7.4.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One broken weir. .2518(k) Replace missing or broken weirs. Operator repaired and corrected
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Light ring cover not in place and broken at time of inspection .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. Operator repaired and corrected.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope tangled at time of inspection.
.2530(a) Lifesaving equipment should be conveniently located. Operator untangled and corrected.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not working at time of inspection.
.2518(g) Keep flow meter operational. Operator adjusted and corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some chemical in tubs in pump room. Items around piping and equipment in pump room. No 3' clearance.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Glass soap dispensers in restroom. No toilet paper in women’s stall.
.2526(j) Provide soap and soap dispenser, no glass, at each sink.
.2526(l) Provide toilet paper and dispensers in restrooms.
Mar 24, 2022 16 demerits · 4 violations
Inspector comments: 30 Day Intent to Suspend (ITS) for 1/2” offsets. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
“W” ITS status
Grass by back gate, long starting to stop gate from closing. Advised cutting grass to allow gate to continue to self-close, self-latch.
Inspection with Chris Foggie
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Debris in skimmer baskets at time of inspection.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator cleaned and corrected.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope around buoy broke at time of inspection.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator got new buoy and attached rope. 50', corrected.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Crack/gap in tiling around skimmer basket lid creating offset greater than 1/2”
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
*Permit item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some chemical in tubs in pump room. Items around piping and equipment in pump room. No 3' clearance.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Aug 19, 2021 26 demerits · 6 violations
Inspector comments: 30 Day Intent to Suspend (ITS) for records and gates. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
Inspection with Chris Foggie
No signature due to COVID
Pool not heated.
Will verify lighting at next inspection.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Some records missing at time of inspection. Main CPO has been absent. Total alkalinity (TA) and cyanuric acid (CA) not recorded weekly.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Measured and recorded TA and CA.
*Permit item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Debris in skimmer baskets at time of inspection.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator cleaned and corrected.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Rope to buoy broke at time of inspection.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Operator got new rope and attached to buoy. 50', corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Side gate propped open, not latching every time closed at time of inspection.
.2537(b) All gates and doors shall be self-closing, self-latching.
*Permit item
#22 · Premises: emergency telephone provided −6
Emergency phone signage missing one number.
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Operator posted number and corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some chemical in tubs in pump room. Items around piping and equipment in pump room. No 3' clearance.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Feb 2, 2021 28 demerits · 8 violations
Inspector comments: ITS for fence gap greater than 4", gates self-latching, records and flow meter.
Changed to "W" Status.
No signature due to COVID.
Inspection with Chris Foggie, Derrick Morris and Ozzie Gonzalez
Report to cfoggie@sycamoreattyvola.com
Pool lights observed working, outer lights are on timer and unable to verify compliance for night swimming. Operator will send picture verification of lighting at night to go with Night Swimming form filled out with onsite visit from 2020.
Pool not heated.
#3 · Water quality: pool water pH −6
pH 8.0 at time of inspection.
.2535(1) Maintain pH at 7.2 to 7.8. Operator corrected to 7.3
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records not including daily main drain checks and maintenance.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
*30 Day Intent to Suspend (ITS) item
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Debris in skimmer baskets at time of inspection.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator cleaned and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Side gate propped open, not latching every time closed at time of inspection. Gap in fencing posts greater than 4". Pool built 2018.
.2528(a) Provide no openings in fence and/or gate greater than 4"x4".
.2537(b) All gates and doors shall be self-closing, self-latching.
*30 Day Intent to Suspend item
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not working at time of inspection.
.2518(g) Keep flow meter operational. Operator adjusted, it worked then stopped again.
*30 Day Intent to Suspend item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some chemical in tubs in pump room. Items around piping and equipment in pump room. No 3' clearance.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Showers off due to cold weather at time of inspection.
.2526(h) Shower(s) shall be provided.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water over 110 degrees F in restrooms.
.2526(i) Water in restrooms shall not exceed 110 F.
Sep 16, 2020 24 demerits · 6 violations
Inspector comments: ITS for gates self-closing, self-latching.
Motor observed changed out for another 5HP motor. Pump remains same. Advised pulling proper permits per Code Enforcement for this electrical work.
No signature due to COVID-19.
Inspection with Chris Foggie
Report to cfoggie@sycamoreattyvola.com
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Pool had been closed, missing last few days of records at time of inspection. Arrow down rather than main drain checks marked daily.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator filled in record for day of inspection. Corrected.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some skimmers observed with debris at time of inspection.
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator emptied and corrected.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Side gate observed getting caught in grass/brush, not self-closing.
.2537(b) All gates and doors shall be self-closing, self-latching.
*30 Day Intent to Suspend item. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS.
#22 · Premises: emergency telephone provided −6
Emergency phone blocked by umbrellas and unaccessible at time of inspection.
.2530(f) Emergency phone shall be accessible to all pool users. Operator moved items to make accessible. Corrected.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not working at time of inspection.
.2518(g) Keep flow meter operational. Operator adjusted and corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Items observed within 3' of equipment. Chemicals in pump room and on floor in chemical room.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Mar 24, 2020 2 demerits · 1 violation
Inspector comments: 16) Ensure grass and landscaping does not prevent gates from closing/latching.
Night Swimming will NOT be permitted without a visit before dawn or after dusk. Night Swimming scheduled for Thursday 3/26/20 at 7 a.m. Contact Marie Daley at 704-507-6806 to cancel or reschedule. Ensure main drains, emergency equipment and entrances can be seen with adequate lighting.
As of 3/24/20, Executive Order 120 mandates closure of pool by 5 p.m. 3/25/2020.
As of current guidance leaving pool in "A" Open for Business and further guidance will be provided as given from State of NC. Permit valid until 4/30/2020, but may NOT operate during time of executive order due to novel coronavirus (COVID-19)
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items stored within 3' of piping. Chemical storage door open with some items in pump room, not separated.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Aug 23, 2019 12 demerits · 4 violations
Inspector comments: ITS for gates self-closing, self-lathcing and weirs.
Operator on emergency phone stated it was hard to hear. Reccomended turning volume up.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed missing weir. .2518(k) Replace missing weirs.
**30 Day ITS item
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gates not self-closing, self-latching at time of inspection. .2537(b) All gates and doors shall be self-closing, self-latching.
**30 Day ITS item
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room observed with items around piping. Chemical room open into pump room and some chemicals observed in pump room (due to space.) .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
No paper towels in men's restroom. Provide paper towels.
May 1, 2019 12 demerits · 3 violations
Inspector comments: Window stoppers in place and windows closed. Ensure windows onto pool deck do not oopen greater than 4".
Issued local 2019 permit sticker.
No Night Swimming.
#1 · Water quality: water clear enough to clearly see bottom of pool and pool drain −6
Pollen/debris covering main drain and screws at time of inspection. .2535(2) Main drains must be clearly visible from the pool deck. Operator cleared drains. Corrected.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Pool chairs within 6' of sunshelf. .2522(a) Provide 6 ft of clear walking space around the pool at all times. Operator moved. Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items around piping and pumps. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Chemicals stored on floor and in pump room. Stored off floor and separate.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “SYCAMORE AT TYVOLA” or State ID 2060530494). Inspection type (routine vs. follow-up) is not published in the county's data.