‹ Back to search

4demerits

EASTWAY REGIONAL REC CENTER - LAP POOL

3150 EASTWAY PARK DR, Charlotte, NC 28205
Year-Round Swimming Pool · NC permit/State ID 2060530583
Latest result4 demerits
Last inspectedFeb 18, 2026
Inspections on record12
On record sinceDec 18, 2020

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

0510 Dec 18, 2020: 10Apr 13, 2021: 2Dec 7, 2021: 2Feb 9, 2022: 8Dec 7, 2022: 6Feb 28, 2023: 2Sep 20, 2023: 2Feb 8, 2024: 4Dec 10, 2024: 0Apr 2, 2025: 0Oct 9, 2025: 4Feb 18, 2026: 4
Dec 18, 2020Lower is betterFeb 18, 2026

Inspections & violations

Feb 18, 2026 4 demerits · 1 violation
Inspector comments: Dan Osucha present during inspection.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed fan within 5' of pool edge. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times.

View this inspection on the county portal ›

Oct 9, 2025 4 demerits · 1 violation
Inspector comments: Vault door not able to be opened during inspection, ensure operation for next visit.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Observed pool deck damaged near lifeguard station at 4’ area and around vault door .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.

View this inspection on the county portal ›

Apr 2, 2025 0 demerits · 0 violations
Inspector comments: Observed one missing tile on coping. Replace.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Dec 10, 2024 0 demerits · 0 violations
Inspector comments: Observed no non compliant conditions

No violations were recorded for this inspection.

View this inspection on the county portal ›

Feb 8, 2024 4 demerits · 2 violations
Inspector comments: Daniel Osucha present during inspection. Inspection led by Troy Kling under supervision of Chris Sells.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Repeat non-compliance: Fan not working in either of the chemical storage rooms. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage rooms.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(i) Water in restrooms shall not exceed 110 F. Hot water at showers in mens' restroom temped at 115 F.

View this inspection on the county portal ›

Sep 20, 2023 2 demerits · 1 violation
Inspector comments: Dan Osucha present during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Repeat non-compliance: Fan not working in either of the chemical storage rooms. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage rooms.

View this inspection on the county portal ›

Feb 28, 2023 2 demerits · 1 violation
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Fan not working in either of the chemical storage rooms. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage rooms.

View this inspection on the county portal ›

Dec 7, 2022 6 demerits · 2 violations
Inspector comments: Inspection conducted with CPO Daniel Osucha.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Permit condition for functional flow meter on backwash line to verify backwash per manufacturer’s instructions. Flow meter not functioning, clogged with lint and debris. .2519(d) Sand filters shall be designed and installed to be backwashed per manufacturer’s instructions, that is between 356 GPM - 474 GPM. Corrected - flow meter cleaned, verified at ~ 390 GPM.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Fan not working in either of the chemical storage rooms. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage rooms.

View this inspection on the county portal ›

Feb 9, 2022 8 demerits · 2 violations
Inspector comments: Inspection conducted with Daniel Osucha. Due to COVID-19 precautions, inspection not signed by the operator. Immediate suspension issued 22) Contact Will Harrison (704-507-6824) for reinspection when issue has been corrected.
#22 · Premises: emergency telephone provided −6
Emergency phone not functioning, no dial tone. .2530(f) Emergency phone shall remain operable. - Immediate suspension item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Fan not working in either of the chemical storage rooms. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage rooms.

View this inspection on the county portal ›

Dec 7, 2021 2 demerits · 1 violation
Inspector comments: Inspection conducted with Daniel Osucha and Alli Jones. Due to COVID-19 precautions, inspection not signed by staff.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Fan not working in either of the chemical storage rooms. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage rooms.

View this inspection on the county portal ›

Apr 13, 2021 2 demerits · 1 violation
Inspector comments: Inspection conducted with inspector Katie Rudisill and CPO Daniel Osucha. Due to COVID-19 precautions, inspection was not signed by the operator. Permit issued. Paper permit will be on our website in 3-5 business days. Go to Meckpools.Charmeck.org to print a copy for your records. “Executive Order No. 141 or subsequent Orders are in effect unless such Orders are rescinded or superseded by another applicable Order.”
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Fan not working in the chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.

View this inspection on the county portal ›

Dec 18, 2020 10 demerits · 3 violations
Inspector comments: Onsite visit to pool with Daniel Osucha for return construction and permit inspection. Construction final passed. Pool is not slated to open to the public until after January 1 and was currently not open to the public. 911 listed address at emergency phone was incorrect address. GIS mapping is currently in process of assigning a different address of 3150 Eastway Park Dr. Signage made to match 911 address of 423 Eastway Dr. Once address is changed with phone company and 911, signage must match. Given 30 days to correct phone address to 3150 Eastway Park Dr or permit will be suspended. Address point in polaris currently; however, when entered into gps 423 Eastway will get you to property. Comp Pool Recirculation PP1 and PP2 – PACO 10N-40957, 15 HP at 540 gpm with 2 sets of (2) Lawson MLD-GO-1818 drain covers. Gutter pool Max Depth – 7 ft. 2 in. Pool Width – 62 ft. Rope Length – 50 ft. Permit Restrictions 1) Digital flow meter must remain operational on backwash line. Backwash flow shall not exceed 474 gpm. Lock valve in place. 2) Perimeter lane lines must remain disabled so as not to block ladder steps. 3) Portable vacuum required for vacuuming of pool.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records not maintained on weekends. Pool is not open to the public yet. Ensure daily record keeping when pool is open.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Bench on pool deck by pump room within 5 ft. of pool edge. Moved during the inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Soap not provided at every sink. No toilet paper in stalls. Two toilets in women's requiring cleaning. Provide soap and toilet paper in restrooms and ensure all fixtures are clean.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “EASTWAY REGIONAL REC CENTER - LAP POOL” or State ID 2060530583). Inspection type (routine vs. follow-up) is not published in the county's data.