TRADEMARK COA

333 W TRADE ST, Charlotte, NC 28208
Year-Round Swimming Pool · NC permit/State ID 2060530600
Latest result38 demerits
Last inspectedSep 2, 2026
Inspections on record12
On record sinceApr 12, 2021

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

02346 Apr 12, 2021: 24Aug 26, 2021: 24Apr 1, 2022: 32Sep 14, 2022: 24Feb 24, 2023: 16Sep 20, 2023: 28Mar 28, 2024: 34Aug 30, 2024: 46Apr 9, 2025: 34Sep 10, 2025: 28Apr 21, 2026: 0Sep 2, 2026: 38
Apr 12, 2021Lower is betterSep 2, 2026

Inspections & violations

Sep 2, 2026 38 demerits · 11 violations
Inspector comments: Intent to Suspend issued for the following: .2535 - lower CYA to less than 100 ppm. .2528 - no access to doors on to pool deck from resident apartments - doors shall self-close, self-latch. .2524/.2537 - pool not approved for night swimming - requires approval or signage changed to reflect day swimming hours. Provide new USCG approved ring buoy and replace rusted screw on body hook within 30 days. Pool floor/chipping paint requires repair prior to 2027 operating season. Chelsea Parker, Trident Pool Group, present during the inspection.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
CYA slightly above 100 ppm. Lower to below 100 ppm. Intent to suspend issued.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Pool floor with chipping/cracking paint. Areas with larger areas of chipping paint require repair prior to 2027 operating permit. Ensure pool floor kept in good repair. No sharp edges at time of inspection.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
No Diving marker blocked by basketball hoop on deck. Moved during the inspection.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Step handrail loose at steps closest to building. Tighten handrail.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
General Comment: Grab rope on ring buoy starting to degrade. Replace with USCG approved ring buoy. One screw bolt rusted body hook. Replace bolt to ensure secure. Ring buoy rope 1 ft too short. Lengthened at tie on during inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
No access to resident doors that lead directly on to the pool deck. Doors shall self-close, self-latch or self-close with audible alarm. Intent to Suspend issued.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Pool hours indicate 5 am to 11 pm. Pool is NOT approved for night swimming. Provide documentation that property has sufficient lighting for night swimming approval or adjust hours to reflect dawn to dusk. Intent to suspend issued.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
No flow meter on chlorinator. If repaired/replaced, install flow meter per NSF approval.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room floor wet. Appears to be a leak around heater. Could not locate. Keep pump room floor dry. Eliminate leaks.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >113 F. Maintain at 110 F or below.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bibs in restrooms. Original construction. Provide hose bib with backflow prevention within 50 ft. of restrooms.

View this inspection on the county portal ›

Apr 21, 2026 0 demerits · 0 violations
Inspector comments: General Comments: -Observed chemicals stored in chemical storage room. -Observed Phone volume very low. Consider replacing phone. 911 operator was still audible at time of inspection. -Chipping on pool floor seems to have been filled in. No violations observed during inspection.

No violations were recorded for this inspection.

View this inspection on the county portal ›

Sep 10, 2025 28 demerits · 8 violations
Inspector comments: Jorge with Trident Pool Group present during the inspection. Note: CYA at 95 ppm. Ensure no greater than 100 ppm.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Chipping paint in multiple locations on bottom of pool floor. Does not appear sharp at time of inspection. Continue to monitor and repair as needed. May require repair prior to 2026 operating season if worsens.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
One depth marker chipped at 3 1/2 ft. where lettering chipped off. Filled in with sharpie during the inspection. Depth markers shall be clearly visible and 4" in lettering at least.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One step handrail loose. Tighten.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Middle door, room 709, with audible alarm on door. Door must be turned off manually. Once turned off, it does not reset. Either install a different audible alarm that stays engaged at all times or repair door to self-close, self-latch prior to 2026 operating season.
#22 · Premises: emergency telephone provided −6
Phone with buttons not operable and could not call 911. Repaired during the inspection. Verified address and phone number with 911. 911 operator faint during the inspection. Operator stated that EHS was also muffled but could still be heard. Monitor. May require replacement prior to next inspection. 911 and EHS shall be clearly audible.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
No flow meter on chlorinator. If replaced, install per mfg. specifications.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
New automated feeder installed. Chemical tanks stored in pump room. Move tanks into chemical storage room prior to next inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >113 F. Maintain at 110 F or below.

View this inspection on the county portal ›

Apr 9, 2025 34 demerits · 9 violations
Inspector comments: 6 - PDSC form shows pressure gauges in use. Pressure gauge reading higher reading and does not reflect accurate flow on the pump. Flow meter is operable. Provide updated PDSC form within 1 week reflecting use of flow meter for reduction. Granular on pool deck. Operator stated pool was shocked previous day. Advised that pool shall not be shocked while open to the public. Operator swept up granular during inspection. No granular was noted in the pool. Jack Mayo present during the inspection.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No cyanuric acid or total alkalinity records. Maintain weekly records. Operator stated that the pool had been closed throughout the winter and no records were maintained.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Old ring buoy on pool deck. New buoy provided. Rope too long. Corrected to 36 ft. during the inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Center resident door on to pool deck with audible alarm. Alarm not operable. New alarm delivered and installed while onsite.
#22 · Premises: emergency telephone provided −6
Phone not dialing 911 upon arrival. Corrected during the inspection. Emergency phone not clearly visible from all areas of pool deck. Blocked by landscaping. Provide additional signage at far side of the pool where phone not visible within 30 days. Photograph is ok for documentation. Note: Hornets nest with hornet in emergency phone. Removed during the inspection.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
No flow meter on chlorinator. If replaced, install per mfg. specifications.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Small leak at flow meter. Pump appears to have a small leak. Could not find location of leak. Repair leaks where needed. Leaks did not warrant return visit.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room floor wet due to leaks on flow meter and pump (possibly). Keep floor dry.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >113 F. Maintain at 110 F or below. Could not verify mirrors as shatterproof in restrooms. Restroom mirrors shall be shatterproof.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bib in restrooms. Original construction. Hose bib shall be provided within 50 ft. of restroom.

View this inspection on the county portal ›

Aug 30, 2024 46 demerits · 13 violations
Inspector comments: Jorge present during the inspection. Intent to Suspend issued for: .2518 - replace wall fitting .2528 - repair center patio door to self-close, self-latch or self-close with audible alarm .2530 - move warning signage so visible from all parts of the pool deck. .2530 - provide "Adults should not swim alone." and "Children should not use the swimming pool without adult supervision." in 1" lettering .2518 - replace pressure gauges on pump so permit restriction can be verified .2518 - repair leak at flow meter Contrasting color bands require repair prior to 2025 operating season. Grab rope starting to degrade. Still intact. Replace prior to next inspection with USCG approved ring buoy.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
One day missing logs in June. Week in July without CYA or TA readings. Maintain daily record keeping for chlorine, pH and main drain checks. Weekly record keeping for total alkalinity and cyanuric acid.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some algae build-up on steps and near ladders. Continue to monitor. Treat as needed and monitor.
#9 · Pool maintenance: depth markings and no diving markers or signs visible and properly located −4
Chip in depth marker at 3 1/2 ft. Depth marker chip over part of the 3. Filled in with sharpie. May require replacement in future if continued issue.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One return missing fitting. Replace fitting on right side wall by main drain. Intent to Suspend issued.
#13 · Pool maintenance: contrasting band on steps and benches −4
Contrasting color band with some chips in paint and faded. Requires repair prior to operating permit 2025. .2521(b) Provide at least 2" contrasting color band to edge of stair treads.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Center door from patio with audible alarm not operational. Repair door to self-close, self-latch or audible alarm with self-close. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Deck drains at old waterfall not evenly spaced. Opening >1/2". Corrected during the inspection. Ensure no openings/offsets >1/2" on pool deck.
#18 · Premises: lifeguards present or warning signs posted −4
Warning signage not visible from all areas of pool deck. Move so visible from all areas of pool deck. Intent to Suspend issued. Provide "Adults should not swim alone." and "Children should not use the swimming pool without adult supervision." in 1" lettering visible upon entry to the pool. Old sign in pump room. Intent to Suspend issued.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
No flow meter on chlorinator. If repaired/replaced, install with flow meter. Chlorinator not secured to ground. Recommend securing to ground.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter leaking. Repair leak. Intent to Suspend issued. PSI pressure gauge does not move when pump is turned off; Hg pressure gauge exceeding gauge max. Could not verify permit restriction. At above 30 Hg, flow does not exceed the drain covers. If gauges are used, pressure shall be capable of reading. Intent to Suspend issued.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Floor wet in pump room due to leak at flow meter. Keep floor dry. Chemicals storage in pump room. Chemical storage room provided. Store chemicals in chemical storage room.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Hot water in restrooms >113 F. Maintain at 110 F or below.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bib in restrooms. Original construction. Hose bib shall be provided within 50 ft. of restroom.

View this inspection on the county portal ›

Mar 28, 2024 34 demerits · 9 violations
Inspector comments: 25 - Emergency phone not clearly visible from all areas of pool deck due to landscaping that has overgrown. Provide additional signage on pool deck in areas where phone is not visible, directing towards emergency phone. Given 30 days. Jorge present during the inspection. Patio on far right with standing water. Eliminate standing water to eliminate mosquito hazard.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
One week with CYA/TA not recorded. Record weekly.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some build-up on pool wall tiles. Keep clean.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One fitting missing on wall at pool step. Corrected during the inspection.
#13 · Pool maintenance: contrasting band on steps and benches −4
Contrasting color band starting to fade in some areas and has small amount of chipping paint. Will require repair within the year. Provide 2" contrasting color band to edge of step or at least 2x2 tile within 1" of step edge.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope degrading. Replaced during the inspection.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
No flow meter on chlorinator. If repaired/replaced, install with flow meter.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operable. True flow required due to new 2017 Aquastar drain covers. Pressure gauges verified at 27.5 psi and 0 Hg. Flow reading off of the pump curve with measurements <119 F. Permit restriction met. Pressure gauges must remain in place.
#28 · Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted −2
Shower not operable. Shower line froze over winter. Provide shower. Shower sign beginning to fade. Will require replacement in future if worsens.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bib in restrooms. Original construction. Hose bib shall be provided within 50 ft. of restroom.

View this inspection on the county portal ›

Sep 20, 2023 28 demerits · 8 violations
Inspector comments: 22 - 911 operator faint when phone initially picked up. Had to push wiring into phone to hear clearly. Recommend replacing emergency phone prior to 2024 operating season. Main drains expire in February 2024. New main drains must be installed prior to expiration with PDSC form submitted and approved or permit will be suspended. Jorge present during the inspection. Intent to Suspend issued for: .2537 - repair pool light to wall at steps
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Contrasting color band on steps and lane line starting to chip in some areas. Monitor. May require repair prior to 2024 operating season if worsens.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Pool light at steps with gap >1/2". Secure pool light to wall. Intent to Suspend issued.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope tangled. Untangled during inspection. Keep accessible. Ring buoy stored behind chair and could not easily be seen. Corrected during the inspection.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
No flow meter on chlorinator. If repaired/replaced, install with flow meter.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Corrected during the inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room floor wet. May be leak at backwash pit. Ensure pit is sealed. Keep pump room floor dry.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >113 F. Maintain at 110 F or below. Could not verify mirrors as shatterproof.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bib in restrooms. Original construction. Hose bib shall be provided within 50 ft. of restroom.

View this inspection on the county portal ›

Feb 24, 2023 16 demerits · 5 violations
Inspector comments: No Diving markers not slip-resistant. Requires repair prior to 2023 operating season. Phone volume still very low. Replace/repair phone within 30 days. Will verify on return visit for ITS items. Jorge Oquendo present during the inspection. Intent to Suspend issued for: .2535 - provide log book with daily and weekly required logs .2537 - repair deck at right deep end of pool
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No log book. Maintain daily record keeping for chlorine, pH and main drain checks. Maintain weekly record keeping for total alkalinity and cyanuric acid. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Small chip in deck on right side of pool near skimmer and deep end. . Appears rusted metal under chip. Opening >1/2". Intent to Suspend issued.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
No flow meter on chlorinator. If repaired/replaced, install with flow meter.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >110 F. Maintain at 110 F or below.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bib in restrooms. Original construction. Hose bib shall be provided within 50 ft. of restroom.

View this inspection on the county portal ›

Sep 14, 2022 24 demerits · 7 violations
Inspector comments: 9 - No Diving markers not slip-resistant on pool deck in multiple locations. PC with State regional confirmed should be slip-resistant. Replace No Diving with slip-resistant 6"x6" tile prior to 2023 operating permit. 15 - Ring buoy rope fraying near ball. Provide new rope within 30 days. 36 ft. Ring buoy requires replacement prior to 2023 operating season. 22 - 911 operator faint when contacted 911. EHS also faint per 911 operator. Monitor. May require repair if worsens. 28 - Shower signage beginning to fade. May require replacement prior to 2023 operating season. Note: Contrasting color band beginning to fade on steps. May require repair prior to 2023 operating season. If repaired, ensure bands go to edge of steps to side wall. Intent to Suspend issued for: .2535 - maintain daily record keeping for temp and weekly record keeping for TA and CYA .2518 - door shall self-close, self-latch on to pool deck .2530 - trip landscape and move chairs/table so that warning signage is clearly visible from all areas of the pool deck. Jorge Oquendo present during the inspection.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No records for temperature. Maintain daily record keeping for temperature. Cyanuric acid and total alkalinity not recorded weekly. Record weekly. Intent to Suspend issued for temperature record keeping and CYA/TA.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some debris under the skimmer baskets. Keep clean.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One door not accessible to verify door self-closes, self-latches. Furthest door to the left. Intent to Suspend issued. Door shall self-close, self-latch.
#18 · Premises: lifeguards present or warning signs posted −4
Warning signage blocked on wall by landscape and signage blocked by tables/chairs near step entry. Warning signage must remain clearly visible from all areas of the pool deck. Intent to Suspend issued.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
No flow meter on chlorinator. If repaired/replaced, install with flow meter.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >110 F. Maintain at 110 F or below.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bib in restrooms. Original construction. Hose bib shall be provided within 50 ft. of restroom.

View this inspection on the county portal ›

Apr 1, 2022 32 demerits · 8 violations
Inspector comments: 6 - Viewed photograph of impeller during site visit - Impeller 071130. 2.60 THP motor installed. New motor installed. Permit e4173985. Finaled March 29th. Operator will provide letter identifying impeller model number for pump identification. Housing for Whisperflo. Impeller coordinates to WFE-8, 2 hp. 15 - Minor damage to ring buoy. May require replacement mid-season. Note - Contrasting color band painted but not to edge of wall. If repainted, ensure 2" contrasting band to edge of step all the way across to wall. Intent to Suspend issued for record keeping, door to self-close, self-latch, repair decking, repair leak in pump room, and installing operable flow meter. Brian Yarmon present during the inspection. Once items are repaired above, a return visit will be made to verify completion of ITS items. Pool will not be permitted for night swimming due to insufficient lighting on pool deck.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No log book. Provide log book with daily record keeping for chlorine, pH and VGBA checks. Total alkalinity and CYA testing weekly. Intent to Suspend issued.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Two skimmers with weirs stuck. Repaired during the inspection.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Emergency phone blocked by trash can. Phone shall be clearly visible from all areas of pool deck. Trash can moved during the inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Could not verify one door as self-closing, self-latching. Door to far left. Video ok to show self-closing, self-latching. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Damage to concrete near drain cover side of pool deck. Repair concrete to ensure piece does not pop out. Concrete loose. Intent to Suspend issued.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
No flow meter on chlorinator. If repaired/replaced, install with flow meter.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Coupling leaking after pump near chlorinator. Repair leak. Intent to Suspend issued. Flow meter not replaced. Required to replace, per previous inspection, due to reading of flow meter not meeting design flow of pump. Install per mfg. instructions. Operator will install new Blue White which ranges as low as 40 gpm. Intent to Suspend issued.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bib in restrooms. Original construction. Hose bib shall be provided within 50 ft. of restroom.

View this inspection on the county portal ›

Aug 26, 2021 24 demerits · 7 violations
Inspector comments: Pool does not appear to have sufficient lighting for night swimming. Verify lighting is sufficient prior to scheduling a night swimming visit. Photograph provided of decking at night which does not appear to have sufficient lighting for night swimming approval. Shawn Ready present during the inspection. Permit Restriction 1) Salt not approved as primary chlorination. Note - no placard on pump. 2 hp pump. Appears to be Whisperflo WFE-8, 2 hp pump.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Cyanuric acid and total alkalinity not recorded weekly. Missing some weeks. Record weekly. No pH indicator reagent. Provided during the inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
One of four skimmer weirs sticking. Keep operable.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One fitting at steps missing. Fitting not threaded. All other returns have fittings. Repair to ensure flow throughout pool.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
No flow meter on Pentair 300-29x chlorinator. Provide flow meter per NSF requirement on chlorinator. Original installation.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operable. Design flow of pump is at 100 gpm. Flow meter only begins at 100 gpm. Ensure correct flow meter installed on the return line. Requires repair prior to 2022 operating permit. Flow meter not installed per mfg. instructions. Install per mfg. instructions if replaced. Flow meter must be capable be capable of at least 150 gpm. Small leak at filter. Repair leak.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Bicarb bags on floor in pump room. Store in chemical storage room up off floor.
#33 · Dressing and sanitary facilities: hose bibbs and floor drains provided −2
No hose bib in restrooms. Provide with backflow prevention device. Original construction.

View this inspection on the county portal ›

Apr 12, 2021 24 demerits · 6 violations
Inspector comments: Intent to Suspend issued for door on to pool deck. If not repaired prior to May 1, a permit for 2021 operating season will not be issued. Shawn Ready present during the inspection. Permit issued for no night swimming. Pool does not appear to have sufficient lighting for night swimming. Verify lighting is sufficient prior to scheduling a night swimming visit. Permit Restriction 1) Salt not approved as primary chlorination. Note - no placard on pump. 2 hp pump. Appears to be Whisperflo WFE-8, 2 hp pump.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One fitting on pool wall nearest to steps without return fitting. Fitting not threaded. All other returns have fittings. Repair to ensure flow throughout pool. Vacuum line cover not flush to wall. Corrected during the inspection.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Ring buoy rope too long. Corrected to 36 ft.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
One door from middle condo not self-closing, self-latching. Repair to self-close, self-latch or self-close with audible alarm. Intent to Suspend issued. Permit will not be issued on May 1 if not corrected prior to. Windows could not be verified as opening 4" or less due to access. Ensure windows open no greater than 4" on to pool deck from condos.
#18 · Premises: lifeguards present or warning signs posted −4
Adults should not swim alone and Children should not use the swimming pool without adult supervision missing some of the lettering so not a full 1" in height. Corrected with black permanent marker during the inspection.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operable. Corrected during the inspection. Design flow of pump is at 100 gpm. Flow meter only begins at 100 gpm. Ensure correct flow meter installed on the return line. Flow meter not installed per mfg. instructions. Install per mfg. instructions if replaced.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water in restrooms >110 F. Maintain at 110 F or below.

View this inspection on the county portal ›