26demerits
STILLWATER APARTMENTS
8242 RUNAWAY BAY DRIVE, Charlotte, NC 28212
Year-Round Swimming Pool · NC permit/State ID 2060530790
Latest result26 demerits
Last inspectedAug 27, 2026
Inspections on record4
On record sinceMay 21, 2025
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
May 21, 2025Lower is betterAug 27, 2026
Inspections & violations
Aug 27, 2026 26 demerits · 8 violations
Inspector comments: Noes indicate 2350 RPM with 74 gpm for turnover. Pump is set at 2355, but flow meter displays 74 gpm.
No NIght Swimming. Pool not heated.
Inspection with Raul Ortiz
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records missing daily maintenance and chemical changes when out of compliance. 2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
Discussed with operator. Lack of severity does not warrant permit action at this time.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
2 of 3 weirs missing a time of inspection.
.2518(k) Replace missing weirs.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One ladder loose at entry.
.2521(b) Ladders shall be installed rigidly.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
Hook of body hook bent straight. Keep in good repair and bent in case of emergency. Operator corrected form to be body hook.
.2530(a) Provide at least 12 ft. long pole with body hook securely attached.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Gate latch locked open at time of inspection.
.2537(b) All gates and doors shall be self-closing, self-latching. Operator adjusted and closed to self-close and self-latch. Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
No 3’ clearance around equipment. Chemicals in pump room. One bag of chemicals on floor. Original construction. 1985.
.2534(4) Provide provisions for dry storage in waterproof containers or above the floor on shelves, pallets or dollies.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#27 · Equipment room: filter backwash discharged through an air gap −2
No air gap at backwash. Original construction. .2513(b) Filter backwash shall be discharged through an air gap.
#31 · Dressing and sanitary facilities: sewage disposed of in a properly operating sewage system −2
No backflow prevention device on hose bib in pump room. Original construction. .2513(b) Provide backflow preventor on fill line to protect the swimming pool from cross contamination.
May 5, 2026 18 demerits · 3 violations
Inspector comments: Inspection completed with Raul Ortiz and Guadalberto Planes present.
Permit conditions - Flow meter must remain operable. Flow required at 2350 RPM. Flow required at 74 GPM to meet turnover. Flow greater than 119 GPM exceeds main drains and is a suction hazard.
#2 · Water quality: disinfectant residual provided by −6
.2535(4) Maintain chlorine at least 1.0 ppm. Observed chlorine at 0ppm. CDI- adjusted to 1.5ppm through use of automatic feeder.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed the pH at 8.4. CDI- adjusted to 7.3.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment should be conveniently located. Observed ring buoy throw rope tangled and not readily accessible. CDI- untangled.
Jul 30, 2025 8 demerits · 2 violations
Inspector comments: Inspection completed with Guadalberto Planes and Raul Ortiz.
PERMIT RESTRICTION - INTELLIFLO PUMP REQUIRED LOCKED AT SPEED 3 AT 2350 RPM DUE TO PUMP ROOM RESTRICTIONS ON SIZING # OF RETURNS AND DRAIN COVER FLOW RESTRICTION. FLOW METER MUST REMAIN OPERABLE. FLOW SHALL READ 74 GPM.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.8. CDI- adjusted to 7.4.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(j) Provide soap and soap dispenser, no glass, at each sink. Observed no soap in mens restroom.
May 21, 2025 10 demerits · 2 violations
Inspector comments: Inspection completed with Guadalberto Planes, Francisco Caba, Raul Ortiz, Camila Hernandez present.
PERMIT RESTRICTION - INTELLIFLO PUMP REQUIRED LOCKED AT SPEED 3 AT 2350 RPM DUE TO PUMP ROOM RESTRICTIONS ON SIZING # OF RETURNS AND DRAIN COVER FLOW RESTRICTION. FLOW METER MUST REMAIN OPERABLE. FLOW SHALL READ 74 GPM.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed the pH at 8.4. CDI- adjusted to 7.6.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed no area in log book to record main drain safety checks. CDI- emailed new log and edited existing log to provide spot for main drain safety checks.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “STILLWATER APARTMENTS” or State ID 2060530790). Inspection type (routine vs. follow-up) is not published in the county's data.