‹ Back to search

10demerits

LINEA SOUTH END

2161 HAWKINS ST, Charlotte, NC 28203
Year-Round Swimming Pool · NC permit/State ID 2060530798
Latest result10 demerits
Last inspectedAug 24, 2026
Inspections on record4
On record sinceMay 16, 2025

This facility type is scored in demerits: lower is better (0 = no violations found).

Score history

0816 May 16, 2025: 4Oct 21, 2025: 10Apr 23, 2026: 16Aug 24, 2026: 10
May 16, 2025Lower is betterAug 24, 2026

Inspections & violations

Aug 24, 2026 10 demerits · 2 violations
Inspector comments: Inspection conducted with CPO Destiny Dawson. All out of compliance items corrected during inspection. Permit Restrictions: 1) Flow meter shall remain operable and valve locked in place to limit flow of pump at no greater than 138 gpm due to flow restriction of suction piping. Flow greater than 150 gpm exceeds the main drains. Suction Hazard. 2) Handle at back gate must stay locked in place down so not to become a latching mechanism Const. Date: 5/10/2024 Rope Length: 30' Night Swim?: N
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Lifesaving equipment should be conspicuously and conveniently located. Ring buoy and body hook were located behind bushes. Moved to a more conspicuous and convent location. CDI
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Tables, chairs, and some loungers too close to pool edge. Operator corrected and pulled back furniture to minimum 6ft. No permit action.

View this inspection on the county portal ›

Apr 23, 2026 16 demerits · 3 violations
Inspector comments: Conducted inspection with CPO. Pool remains in good standing and on A status. 5% accurate flow meter required by June 1st 2026 or permit may not be issued. Submit updated paperwork to health department for approval. Permit Restrictions: 1) Flow meter shall remain operable and valve locked in place to limit flow of pump at no greater than 138 gpm due to flow restriction of suction piping. Flow greater than 150 gpm exceeds the main drains. Suction Hazard. 2) Handle at back gate must stay locked in place down so not to become a latching mechanism Const. Date: 5/10/2024 Rope Length: 30' Night Swim?: N
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. PH observed at 8.0. Operator corrected to 7.2. No permit action.
#15 · Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located −6
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. Ring buoy rope exceeds 30’. Operator corrected to 30’. No permit action.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Tables, chairs, and some loungers too close to pool edge. Operator corrected and pulled back furniture to minimum 6ft. No permit action.

View this inspection on the county portal ›

Oct 21, 2025 10 demerits · 3 violations
Inspector comments: Conducted inspection with CPO Destiney Dawson. Pool heated but heater not currently operating. Intent to suspend issued for inoperable flow meter. Item must be corrected within 30 days or permit may be suspended. Call EHS Devon when corrected 7049981122. Const. Date: 5/10/2024 Rope Length: 30' No night swimming. Permit Restrictions: 1) Flow meter shall remain operable and valve locked in place to limit flow of pump at no greater than 138 gpm due to flow restriction of suction piping. 2) Handle at back gate must stay locked in place down so not to become a latching Mechanism.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
.2522(a) Provide 6 ft of clear walking space around the pool at all times. Tables, chairs, and some loungers too close to pool edge. Operator corrected and pulled back furniture to minimum 6ft. No permit action.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter not functioning. Intent to suspend item. .2518(g) Keep flow meter operational.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(d) Pump room floor shall be kept dry and free of standing water. Water on pump room floor

View this inspection on the county portal ›

May 16, 2025 4 demerits · 1 violation
Inspector comments: Pool not approved for night swimming. Permit restriction. Flow meter shall remain operable and pump shall remain locked to limit flow no greater than 138 gallons per minute. Rear gate handle not at 54 inches must remain locked. Permit issued.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter not functioning. Repaired during inspection. .2518(g) Keep flow meter operational.

View this inspection on the county portal ›

Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “LINEA SOUTH END” or State ID 2060530798). Inspection type (routine vs. follow-up) is not published in the county's data.