6demerits
ALEXAN LOSO
3305 SOUTH BLVD, Charlotte, NC 28209
Year-Round Swimming Pool · NC permit/State ID 2060530810
Latest result6 demerits
Last inspectedAug 13, 2026
Inspections on record4
On record sinceJun 9, 2025
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jun 9, 2025Lower is betterAug 13, 2026
Inspections & violations
Aug 13, 2026 6 demerits · 2 violations
Inspector comments: Conducted inspection with CPO.
Pool has heater but heater not in use.
Permit Restriction: Pool pump flow must be at least 74gpm for turnover, not to exceed 138gpm for skimmer and main drain piping limitation.
Note: Pump room clearance 6’10” does not meet minimum required height. Pool will lose points for not meeting clearance for ceiling height. Const. Date: 2/25/2025 Rope Length: 40' No night swimming
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs.
Weir near tanning ledge handrail. One out of five weirs missing. Replace. No permit action.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft.
.2534(1) Chemical storage room shall be weatherproof with a minimum ceiling height of 7 ft.
Mar 10, 2026 16 demerits · 4 violations
Inspector comments: Conducted inspection with CPO. Pool remains in good standing and on A status.
Pool has heater but heater not in use.
Permit Restriction: Pool pump flow must be at least 74gpm for turnover, not to exceed 138gpm for skimmer and main drain piping
limitation.
Note: Pump room clearance 6’10” does not meet minimum required height. Pool will lose points for not meeting clearance for ceiling
height.
Const. Date: 2/25/2025
Rope Length: 40'
No night swimming
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8.
PH observed exceeding 7.8. Operator corrected to 7.6. No permit action.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs.
Weir near tanning ledge handrail. One out of five weirs missing. Replace. No permit action.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational.
Flow meter bobber stuck at bottom. Operator corrected. Digital flow meter and flow vis also present. 90gpm
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft.
.2534(1) Chemical storage room shall be weatherproof with a minimum ceiling height of 7 ft.
Aug 7, 2025 10 demerits · 3 violations
Inspector comments: Follow-up inspection. Conducted inspection with CPO Mike Campbell. New CPO has taken over pool maintenance from TCR. Intent to suspend issued for lack of records. Correct with daily and weekly records within 30 days. Text EHS Devon when compliant 7049981122
Permit Restriction: Pool pump flow must be at least 74gpm for turnover, not to exceed 138gpm for skimmer and main drain piping
limitation.
Note: Pump room clearance 6’10” does not meet minimum required height. Pool will loose points for not meeting clearance for ceiling height.
Const. Date: 2/25/2025
Rope Length: 40'
No night swimming
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
No records available. Maintain daily and weekly records. Intent to suspend item.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. One out of five weirs missing. Replace. No permit action.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(a) Pump room shall be weatherproof with a minimum ceiling height of 7 ft.
.2534(1) Chemical storage room shall be weatherproof with a minimum ceiling height of 7 ft.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. Chemicals stored in pump room. Move to designated chemical storage room.
Jun 9, 2025 0 demerits · 0 violations
Inspector comments: Permit Restriction: Pool pump flow must be at least 74gpm for turnover, not to exceed 138gpm for skimmer and main drain piping limitation.
Note: Pump room clearance 6’10” does not meet minimum required height. Pool will loose points for not meeting clearance for ceiling height.
Permit Approved
No violations were recorded for this inspection.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “ALEXAN LOSO” or State ID 2060530810). Inspection type (routine vs. follow-up) is not published in the county's data.