26demerits
HAMBRIGHT JUNCTION
11122 HAMBRIGHT JUNCTION DR, Huntersville, NC 28078
Year-Round Swimming Pool · NC permit/State ID 2060530826
Latest result26 demerits
Last inspectedOct 8, 2026
Inspections on record3
On record sinceNov 17, 2025
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Nov 17, 2025Lower is betterOct 8, 2026
Inspections & violations
Oct 8, 2026 26 demerits · 7 violations
Inspector comments: POOL IS NOT APPROVED FOR NIGHT SWIMMING. POOL CANNOT BE OPEN AFTER SUNSET OR BEFORE SURISE.
MAIN DRAIN COVERS EXPIRE 8/6/2030
NOTE: Pump should be at 3450 RPM or Flow meter must remain operable with flow at 132 gpm to 196 gpm to meet turnover and flow restriction of the filters.
PUMP WAS SET AT 3450 RPM.
INTENT TO SUSPEND ISSUED FOR LOG BOOK IMPROPERLY KEPT AND FOR MISSING WARNING SIGNS
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering.
.2530(c) Provide "Adults should not swim alone." in 1" lettering.
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Observed no records since 9/28/2026. The pool log book checks must be made and recorded every day the pool is open. This includes weekends and holidays, no exceptions.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed 1 weir missing out of 5 total skimmers.
.2518(k) Replace missing weirs.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521(b) Ladders shall be installed rigidly. Observed 2 stair rails to have come out of the sun shelf and present hazards due to the hole in the shelf, and the unsecured railing. Items were corrected during the inspection.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Back gate does not latch. .2528(a) Access gates shall swing away from the pool and be self-latching, self-closing. - Corrected.
#18 · Premises: lifeguards present or warning signs posted −4
.2530(c) Provide "Children should not use the swimming pool without adult supervision." in 1" lettering.
.2530(c) Provide "Adults should not swim alone." in 1" lettering.
These warning signs are not present and must be provided with proper wording and letter height.
#22 · Premises: emergency telephone provided −6
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Observed the call back number of the pool not to be working. Number was incorrect. Correct number was determined and posted. -Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Jan 8, 2026 24 demerits · 6 violations
Inspector comments: Inspection conducted with CPO Rob Bromstrup.
Permit restriction that flow meter must read between 132 and 196 GPM or pump be set at 3450 RPM. Verified at 145 GPM.
Chlorine 1ppm, pH 7.1. Recommend having automatic chemical controller recalibrated.
Lots of air in Flo Vis flow meter. Recommend having it serviced.
Last cyanuric acid check on 12/1 was at 100ppm. This is the state maximum. Ensure cyanuric acid is no more than 100ppm.
Intent to suspend issued
5)
7)
#3 · Water quality: pool water pH −6
PH 7.1. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.4.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No main drain checks, pool only checked a few times a week. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity. - Intent to suspend item.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Pool floor dirty. .2537(14) Keep pool surface and pool floor free of debris. - Intent to suspend item.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer baskets full of leaves. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Corrected.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail from deck to sun shelf loose. .2521 Install handrails per manufacturer instructions.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Back gate does not latch. .2528(a) Access gates shall swing away from the pool and be self-latching, self-closing. - Corrected.
Nov 17, 2025 6 demerits · 2 violations
Inspector comments: OSV to pool with Ryan Price, Aquarian Pools, Brandon Underwood, GC and CPO. All items from previous site visit corrected except for handrail on sun shelf. Repair handrail prior to follow-up inspection. Construction final passed. Holds released in system. Local permit issued while onsite. State permit will be posted online by end of business. Pool not permitted for night swimming.
Pool Width 36 ft.; Rope Length 50 ft.; Max Depth 5 ft.
Permit Restriction: Pump required at 3450 RPM or Flow meter must remain operable with flow at 132 gpm to 196 gpm to meet turnover and flow restriction of the filters.
Note: Facility provided signage does not meet height or wording requirements. If generic signage is removed, signage provided must meet rule requirement.
Pentair WhisperfloXF VS, 022035 5 hp pump with (2) Aquastar 2017 12MFxxx drain covers. EQ lines plugged in skimmer and capped on underside.
An unannounced follow-up inspection will be completed within 30 to 60 days of permit issuance.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No log book provided. CPO had not taken over the property. Provide log book with daily record keeping for chlorine, pH and main drain checks. Total alkalinity and cyanuric acid records weekly.
CPO certification expired. Operator signed up for two day class December 11th and 12th.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail loose on sun shelf. Tighten prior to follow-up inspection.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “HAMBRIGHT JUNCTION” or State ID 2060530826). Inspection type (routine vs. follow-up) is not published in the county's data.