8demerits
AVALON CARMEL COMMONS
11303 CARMEL COMMONS BV, Charlotte, NC 28226
Year-Round Swimming Pool · NC permit/State ID 2060530862
Latest result8 demerits
Last inspectedJul 1, 2026
Inspections on record2
On record sinceJun 3, 2026
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Jun 3, 2026Lower is betterJul 1, 2026
Inspections & violations
Jul 1, 2026 8 demerits · 2 violations
Inspector comments: Pool not heated. No Night Swimming. Flow meter must remain operable between 87 gpm to 138 gpm for turnover and flow restriction. At time of inspection flow observed slightly below 87, around 85 gpm. ,Operator adjusted diverter valve and corrected to 90 gpm. Salt not approved as primary chlorination. Discussed sizing of salt cell vs chlorinator and usage, volume and bather load. Minimum chemical standards must be maintained through pump system.
22) Emergency phone is Kings III, did not connect to 911 on first call, dropped call on 2nd attempt. Worked correctly on 3rd and 4th attempt. Monitor emergency phone and ensure it is operable at all times.
Inspection with Joe Savino and Josiah Fowler
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Main drain checks missing on records.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added check and corrected.
Discussed logs and what is required.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Two gates not self-closing or latching at time of inspection.
.2537(b) All gates shall be self-closing, self-latching. Operator corrected to self-close, self-latch. Continue to monitor and repair when out of compliance.
Jun 3, 2026 16 demerits · 4 violations
Inspector comments: Issued local permit and changed to “A” Open for Business.
No Night Swimming.
Pool not heated.
Flow meter must remain operable for filtration pump. Maintain flow between 87 to 138 gpm for turnover and flow restriction.
Salt not approved as primary chlorination.
Approved restrooms are in hallway by emergency phone.
Approved hose bibs on perimeter of building and in pool restroom.
Verified signage made from establishment meets code.
*Note: Emergency phone operator stated hard to hear on receiving end. Monitor and repair/correct to avoid permit action in the future.
Inspection with Joe Savino
#3 · Water quality: pool water pH −6
PH 8.0 at time of inspection.
.2535(1) Maintain pH at 7.2 to 7.8. Operator corrected to 7.6.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Main drain checks missing on records.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator added check and corrected.
Discussed logs and what is required.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Two gates not self-closing or latching at time of inspection.
.2537(b) All gates shall be self-closing, self-latching. Operator corrected to self-close, self-latch. Continue to monitor and repair when out of compliance.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Door into hallway from equipment room open at time of inspection for construction worker entry. .2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. Operator corrected to latch and lock.
One bag of dry chemicals on the floor.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Operator moved onto shelf and corrected.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “AVALON CARMEL COMMONS” or State ID 2060530862). Inspection type (routine vs. follow-up) is not published in the county's data.