4demerits
DRURY INN AND SUITES
6920 NORTHLAKE MALL DR, Charlotte, NC 28216
Year-Round Spa · NC permit/State ID 2060550160
Latest result4 demerits
Last inspectedAug 6, 2026
Inspections on record28
On record sinceSep 12, 2013
This facility type is scored in demerits: lower is better (0 = no violations found).
Score history
Sep 12, 2013Lower is betterAug 6, 2026
Inspections & violations
Aug 6, 2026 4 demerits · 1 violation
Inspector comments: OBSERVED SPA LIGHTS ON.
MAIN DRAIN COVERS EXPIRE 2/3/2030
OBSERVED EMERGENCY PHONE CALL-BACK NUMBER TO GO TO AN OFF-SITE CALL CENTER IN MISSOURI TO BE CONNECTED TO THE MAIN DESK. THE CALL BACK NUMBER IS TO GO BACK TO THE PHONE ITSELF, OR TO AN ON-SITE PHONE THAT IS MONITORED 24 HOURS A DAY, 365 DAYS A YEAR. THIS REQUIRES CORRECTION. C. ELMORE WILL FOLLOW-UP TO EVALUATE CORRECTION.
OBSERVED SPA TIMER TO RUN 15 MINUTES AND 4 SECONDS. THE JETS SHOULD RUN NO LONGER THAN 15 MINUTES. CORRECT THE JET TIMER TO RUN NO LONGER THAN 15 MINUTES. C. ELMORE WILL FOLLOW UP.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
.2518(k) Replace missing weirs. Observed 1 weir missing. Weir was replaced. -CDI
Mar 3, 2026 8 demerits · 2 violations
Inspector comments: Inspection conducted with CPO Rodney Searcy.
No label on spa filtration pump. Observed Pentair Challenger pump with 2 HP motor.
#2 · Water quality: disinfectant residual provided by −6
0.6ppm free bromine. .2535(5) Maintain bromine at least 2.0 ppm. - Corrected to 2ppm.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items stored directly beside or on top of equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Dec 15, 2025 30 demerits · 7 violations
Inspector comments: CPO Rodney Searcy not present for today’s inspection.
Went over inspection with manager Katherine Conrad.
5 gallon buckets of liquid chemicals in the pump room not labeled appropriately. Ensure chemicals are stored in containers that are designed for that product and reflect the product stored inside.
Observed spa with heavy foam when the jets are running. Defoamer added to help.
Emergency phone number posted goes to a reservation call center. Recommend rerouting so calls go to front desk.
2HP motor in spa jet pump moved to unlabeled Pentair Challenger filtration pump. Our records show that this is a 1 HP pump, but without the label, will need to provide pictures of the impeller serial number to verify that this is a 1 HP pump.
Bonding wire not attached to filtration or jet pump motors. G.S. 130A-(2)3 Bonding wire shall be attached to the pump motor by a licensed electrician.
New 2HP motor installed on jet pump. Jet pump motor moved to filtration pump, back of filtration motor removed, wires exposed. Will need work completed by a licensed electrician and an electrical permit and passing inspection from Mecklenburg County Code Enforcement prior to 2026 pool permit being issued.
Immediate suspension issued
3)
6)
G.S. 130-A(2)3
#3 · Water quality: pool water pH −6
Spa pH < 6.8. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
New 2HP motor installed on unlabeled pump. Need to verify that it is indeed a 1 HP pump with impeller documentation or install 1 HP motor on pump. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. - Immediate suspension item.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer basket broken. .2518(k) Replace missing or damaged skimmer basket. - Intent to suspend item.
Skimmer turned off in the pump room. .2518(k) The flow through rate for any one skimmer shall be between 20 GPM and the max flow certified under NSF 50. - Intent to suspend item.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One eyeball fitting missing. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Intent to suspend item.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Underwater light partially popped out of the light niche. .2537(9) Underwater light niches shall be maintained or covered so not to present a hazard. - Intent to suspend item.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Acid feeder fed continuously during inspection. Control board reading 8.0, pH < 6.8. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Intent to suspend item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items stored directly beside or on top of equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Chemical storage room very cluttered. Lots of chemicals stored on top of each other. .2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up.
Jan 9, 2025 26 demerits · 6 violations
Inspector comments: *original inspection report signed by CPO and REHS Chad Gambill attached to this report due to accidental deletion of original inspection report in smartforms prior to uploading*
Strongly recommend no spa use with Bromine level of 22.5ppm, may have adverse effect on bathers. Level should be maintained 8.0ppm or below.
During inspection VOIP configuration caused the 911 operator to only see the out of state telephone number on their screen. This configuration could delay 911 response times, the 911 operator should see the front desk number that is visible on the sign, and not the out of state number. Hotel IT indicated they are working on getting this resolved
Printed copy of inspection form emailed to operator during visit.
#2 · Water quality: disinfectant residual provided by −6
.2535(5) Maintain bromine at least 2.0 ppm. Observed bromine with a concentration of .675ppm. CDI- Bromine added to spa directly and concentration read above 22.5
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed spa ph with a concentration of 6.8. CDI- CPO added soda ash directly to spa and ph was 7.8.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
.2521 Install handrails per manufacturer instructions. Observed handrail going into spa removable without tools. Repair.
#22 · Premises: emergency telephone provided −6
Emergency phone sign has two numbers listed, one number to hotel front desk and one number that goes out of state to reservation customer service. CDI- CPO covered telephone number to out of state reservation customer service, front desk number is monitored 24/7.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
.2535(6) When chlorine or bromine are used as the disinfectant, automatic chemical feeders shall be used. Through conversation with CPO, CPO stated that automatic bromine feeder has damaged solenoid and therefore is putting bromine into spa by hand. ITS issued, repair within 30 days (by 2/8/25).
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
.2526(m) Keep restrooms and fixtures clean and in good repair. Observed automatic faucet for hand sink not operable. Repair.
Dec 4, 2024 2 demerits · 1 violation
Inspector comments: Inspection conducted with CPO Rodney Searcy and Chris Palladino. Inspection led by inspector Maddie Denoncour.
Emergency phone calls back to front desk. Ensure someone is at the front desk whenever the pool is open.
Coping chipped. Maintain coping in good condition.
No label on spa filtration pump. Verified Pentair Challenger pump with 1 HP motor.
Bonding wiring not installed on spa jet pump. G.S. 130A-2(3) Bonding wire shall be attached to the pump motor. - Corrected.
Observed motor for spa jet pump recently changed out. Electrical permit E4521713 passed inspection 11-6-2023.
Electrical whip to pool motor not fully installed, wiring exposed. Ensure wiring is properly installed by a licensed electrician.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail loose. .2521 Install handrails per manufacturer instructions.
Jan 31, 2024 6 demerits · 2 violations
Inspector comments: Inspection conducted with inspector Anglecia Askew and Chris with maintenance.
Pool recently re-plastered. Equalizer line plugged in the skimmer, eyeball fitting installed on equalizer line on pool wall. Facility is working to properly abandon equalizer line per state guidelines.
Spa filtration pump not labeled. Observed Pentair Challenger pump with 1 HP motor.
One eyeball fitting on spa jets damaged. Recommend replacing.
Intent to suspend issued
8)
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Missing weir for skimmer. .2518(k) Replace missing weirs. - Intent to suspend item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items stored beside spa equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Some bags of chemicals on the floor. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Dec 20, 2023 6 demerits · 2 violations
Inspector comments: Inspection conducted by Devon Moeller under supervision of Stacie Rhea.
CPO signed paper copy of inspection.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some debris in the skimmer. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Operator will correct No permit action.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor. Chemicals in chemical room not stored in orderly fashion. Organize chemical storage room and raise bags off the floor.
Mar 14, 2023 6 demerits · 2 violations
Inspector comments: Inspection conducted with Rodney Searcy.
Spa filtration pump motor not bonded. G.S. 130A-2(3) Bonding wire shall be attached to the pump motor. - Corrected.
Spa floor and benches chipping. Recommend replastering the spa.
No label on Spa filtration pump. Verified Pentair Challenger pump with 1 HP motor.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Some debris in the skimmer. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
Some chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Aug 10, 2022 8 demerits · 2 violations
#3 · Water quality: pool water pH −6
Observed pH level at the spa of 7.1 .2535(1) Maintain pH at 7.2 to 7.8. Corrected to 7.4 during inspection.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed wet floor in the pump room .2533(d) Pump room floor shall be kept dry and free of standing water.
May 16, 2022 6 demerits · 2 violations
Inspector comments: Inspection conducted with Anthony Amey.
No label on filtration pump. Observed Pentair Challenger pump with 1 HP motor.
Emergency phone line has a backup line that it sometimes pulls from. This line is not posted on the signage for the emergency phone. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. Numbers must match what 911 has.
Permit issued.
Paper permit will be on our website, Meckpools.Charemeck.org in 3-5 business days to print a copy for your records.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not functioning. Installed backwards. .2518(g) Install flow meter on return line per manufacturer instructions. - Corrected.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items stored beside spa equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Some chemicals in the pump room. Observed loose bromine briquets on the floor. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
Nov 3, 2021 20 demerits · 6 violations
Inspector comments: Inspection conducted with inspector Naly Lor and manager Katherine Conrad. Due to COVID-19 precautions, inspection not signed by the manager.
No label on filtration pump. Verified that pump was a Pentair Challenger Pump with a 1 HP motor.
Operator attempted to correct pH. Efforts were reversed by automatic feeder. Recommend recalibrating automatic chemical controller.
Filtration pump motor not connected to the bonding wire. G.S. 130A-2(3) Pump motor shall be properly bonded to the spa. - Immediate suspension item.
Immediate suspension issued.
3)
Pump motor not bonded
#3 · Water quality: pool water pH −6
pH 6.9. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No Main Drain checks observed. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for total alkalinity. - Intent to suspend item.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail loose. .2521 Install handrails per manufacturer instructions.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. .2518(g) Keep flow meter operational. - Intent to suspend item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some items stored beside spa equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Some chemicals in the pump room. Observed loose bromine briquets on the floor. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
Some pipe labeling worn off. .2518(d) Piping and valves shall be labeled with color codes or labels.
Jan 26, 2021 16 demerits · 4 violations
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 6.9. CDI- pH corrected to 7.5.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
.2535(11) The pool operator must maintain records for at least six months. Observed no CA checks since October.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
.2518(g) Keep flow meter operational. Observed flow meter stuck.
#26 · Equipment room: valves and pipes identified by color codes or labels −2
.2518(d) Piping and valves shall be labeled with color codes or labels. Observed piping in need of more labels.
Jul 13, 2020 12 demerits · 3 violations
Inspector comments: Inspection conducted with maintenance. Due to COVID-19 precautions, inspection was not signed by the operator.
Some lights operate on a timer and a photocell. Will make a site visit tomorrow at 7 AM to verify lighting.
“Executive Order No. 141 or subsequent Orders are in effect unless such Orders are rescinded or superseded by another applicable
Order.”
#3 · Water quality: pool water pH −6
pH 7.0. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.6.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
No Total Alkalinity checks for July. No Main Drain checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator that normally checks TA was off, will start checking again. No place for Main Drain checks on sheet. Will start using CYA column for Main Drain checks.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Leak in the pump room. .2533(d) Pump room floor shall be kept dry and free of standing water.
Light in pump room burned out. .2533(b) Provide sufficient lighting in pump room.
Bag of dry chemicals on the ground in the chemical storage room. .2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Mar 4, 2020 6 demerits · 1 violation
Inspector comments: *NOTE: Equalizer line was plugged at the wall when spa was registered. Plug line in the skimmer per state guidelines and provide updated PDSC form to Environmental Health.
*NOTE: Pool Inspection was completed for Alexis Welch Authorization. NC State Regional Heather Misenheimer was present during time of inspection.
#3 · Water quality: pool water pH −6
.2535(1) Maintain pH at 7.2 to 7.8. Observed pH at 7.0. Corrected during inspection to 7.4
Jan 22, 2020 16 demerits · 3 violations
Inspector comments: Equalizer line was plugged at the wall when spa was replastered. Plug line in the skimmer per state guidelines and provide updated PDSC form to Environmental Health. Verification visit will take place next week.
Intent to suspend issued.
20)
#3 · Water quality: pool water pH −6
pH 7.0. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.4.
#20 · Premises: caution signs posted at hot water spas −4
Some signage missing. .2532(17) A sign shall be posted requiring a shower for each user prior to entering the spa or hot tub and
prohibiting oils, body lotion, and minerals in the water.
#22 · Premises: emergency telephone provided −6
Incorrect dialing instructions posted. Phone automatically dials 911 when lifting the handset. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. - Temporary signage posted. Will order a new permanent sign.
Oct 17, 2019 16 demerits · 4 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no records for daily main drain checks or weekly checks for cyanuric acid/ total alkalinity.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly.
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity.
#20 · Premises: caution signs posted at hot water spas −4
Spa sign posted with incorrect verbiage. Provide signage exactly as directed in rules. Intent to suspend issued.
.2532(15) Provide Caution sign in 1/2" lettering 1/2" in height according to Rule .2532(15).
#22 · Premises: emergency telephone provided −6
Observed emergency phone inoperable. Corrected on site. 911 operator had different phone number than what was posted on sign. Corrected onsite. Advised that emergency phone has to have a dedicated phone line.
.2530(f) Emergency phone shall remain operable.
.2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed bags of backing soda on chemical room floor. Store bags off of the ground.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
Jan 16, 2019 0 demerits · 0 violations
Inspector comments: No violations observed at time of visit.
No violations were recorded for this inspection.
Nov 27, 2018 10 demerits · 2 violations
Inspector comments: Issued intent to suspend for #8 (missing weir).
#3 · Water quality: pool water pH −6
Observed pH at 7.0. Adjusted pH to 7.4 onsite.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed weir missing in skimmer. Replace. Intent to suspend issued.
Feb 22, 2018 16 demerits · 4 violations
Inspector comments: Heavy foam on the spa when jets are on. Maintain good water quality.
7) Coping damaged directly above some of the spa jets. Maintain in good condition.
13) A few of the tiles for the contrasting color band on the spa bench missing. Provide at least 2 inch contrasting color band no more than 1 inch from the edge of the spa bench.
#3 · Water quality: pool water pH −6
pH 8.1. Maintain between 7.2 and 7.8. Corrected by operator to 7.5.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Spa floor chipping. Recommend replastering the spa.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Skimmer weir missing. Provide functional weir. Corrected by operator.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Recently recieved chemicals stored outside the pump room on the pool deck. Store chemicals inside the chemical storage room. Corrected.
Nov 15, 2017 20 demerits · 5 violations
Inspector comments: Posted permits are from last year. Post current permits in the pool area. Permits can be found at Meckpools.Charmeck.org.
*Imminent Hazard - spa motor not bonded to the spa. Ensure that spa motor is properly bonded to the spa and is inspected by Code Enforcement.
Immediate suspension issued.
3)
24)
Contact Will Harrison (704-507-6824) for reinspection when issues have been corrected.
#3 · Water quality: pool water pH −6
pH < 6.8. Maintain between 7.2 and 7.8. - Immediate suspension item.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Plaster chipping and pitted. Maintain in good condition.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir missing. Install functional weir. - Intent to suspend item.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter missing. Install flow meter that is capable of measuring 1 1/2 times the flow of the spa and is accurate to within 10 percent of true flow. - Intent to suspend item.
Spa filtration motor not bonded to the spa. Ensure that motor is properly bonded to the spa and is inspected by Code Enforcement. - Immediate suspension item.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Some leaks in the pump room. Fix leaks.
Chemicals stored in the pump room. Store chemicals in the chemical storage room.
Exhaust fans for pump room and chemical storage room not working. Provide either continuous forced air ventilation or cross ventilation.
Mar 2, 2017 20 demerits · 5 violations
Inspector comments: Inspection conducted by Joy Wilson and Stacie Rhea.
Informed CPO of ground wire not connected on spa side of pumps.
Observed grill cleaner and empty spray bottles in chemical storage. Organize chemical storage room.
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Observed missing screw on two of the main drain covers. Immediate suspension.
Observed drain covers discolored. Need to repair/replace.
Observed incorrect information for pool drain safety compliance. Make sure to update.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed green debris on wall and steps of tub. Need to keep clean.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Missing weir. Need to replace. Intent to suspend on next visit.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter not operating. Make sure to repair.
Observed no spare basket. Need to have a spare basket.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed leak in room. Fix leaks.
Oct 27, 2016 14 demerits · 4 violations
Inspector comments: Posted permits have expired. Print and post copy of current permit. Permit can be found at Meckpools.Charmeck.org.
Unable to verify filtration pump. Observed Pentair Challenger pump with 1 HP motor.
Intent to suspend issued.
8)
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some chipping on steps and spa floor. Operator states they will soon be getting bids to replaster the spa. Maintain in good condition,
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir missing. Provide functional weir. - Intent to suspend item.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair or replace.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Leaks in pump room. Fix leaks.
Fan not working for chemical storage room. Provide proper ventilation.
Light in chemical storage room not working. Provide proper lighting.
Jan 28, 2016 16 demerits · 4 violations
Inspector comments: Verified that approved PDSC forms match installed equipement.Immediate suspension issued.3)Contact WIll Harrison (704-507-6824) for reinspection once issues have been corrected.
#3 · Water quality: pool water pH −6
pH 7.0. Adjusted to 8.4. Maintain between 7.2 and 7.8. - Immediate suspension item.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Recently used pool logs do not have a place for main drain checks. Check daily main drains.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair or replace.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Maintain at least 3 feet clear walkway around equipment in pump room.
Aug 27, 2015 10 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Spa with one skimmer, weir missng. Install functional weir. Corrected by operator.Water level above skimmer. Maintain proper water level so that skimmer can function effectively.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair or replace.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Unable to get faucet in restroom to work. Provide functional faucet.
Mar 16, 2015 14 demerits · 3 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Wad of hair in skimmer basket. Clean out basket regularly.
#22 · Premises: emergency telephone provided −6
Unable to reach 911 on emergency phone. Corrected by operator.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair or replace.
Sep 30, 2014 10 demerits · 2 violations
#6 · Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ −6
Bromine at 1.2 ppm. Corrected to 2.0 ppm.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Keep operational.
Mar 24, 2014 18 demerits · 4 violations
Inspector comments: Intent to suspend issued.8)21)
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Spa missing weir for skimmer. Install functional weir.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Missing one inlet fitting. Install.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Underwater light does not appear to be securely attached. Screw observed on spa bench, possibly from light. Install light securely.
#22 · Premises: emergency telephone provided −6
Signage for emergency phone not visible from phone. Corrected.
Sep 12, 2013 6 demerits · 2 violations
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Observed no alkalinity readings recorded. Record weekly.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Observed pump room floor wet. Keep dry.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “DRURY INN AND SUITES” or State ID 2060550160). Inspection type (routine vs. follow-up) is not published in the county's data.