Feb 16, 2026 12 demerits · 4 violations
Inspector comments: Daniel Osucha present during the inspection.
Permit Restriction: Flow meter on jets must remain operable. Combined flow of flow meters shall not exceed 360 gpm. Suction Hazard. Drains are single main drains and T in pump room with Stingl switch as SVRS.
Filtration main drains expire - 3/9/2030. Jet main drains expire - 2/1/2031
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Records missing for January 24/25. Ensure daily record keeping for chlorine, pH and main drains. If closed, indicate as such.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One step handrail loose. Tighten.
#23 · Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 −4
Automated feeder not detecting flow. Corrected during the inspection.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One sink not operable in women's. Keep fixtures operable.
Patron onsite indicated that two shower fixtures not operable and one toilet not operable in men's.
Dec 2, 2025 8 demerits · 3 violations
Inspector comments: Daniel Osucha present during the inspection.
Permit Restriction: Flow meter on jets shall remain operable not exceeding 200 gpm due to drains. Flow meters verified at 190 gpm. Stingle switch tested monthly per mfg. requirement.
Flow meter for jets not 5% accurate. Prior to 2026 operating season, flow meters shall be changed out per federal requirement to 5% accurate flow meters. New PDSC forms shall be filled out and submitted with documentation pictures.
Note: Feature main drains require replacement by 2/1/2026. A new PDSC form is required for approval. Permit will be suspended if not complete prior to expiration.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Pool grout missing from steps and entry into the pool. Repair grout prior to 2026 operating permit.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One step handrail loose. Tighten.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One sink in women's not operable. Shower faucet holster damaged in one shower stall in women's. Keep all fixtures in good repair.
Mar 31, 2025 12 demerits · 4 violations
Inspector comments: 13 - Contrasting color band on steps not 2" thick. Original construction. If ever retiled, ensure 2" thick band per rule requirement.
.2524 - ventilation not operable. Repair ventilation
Fan running with electrical drop cord running across floor. Floor wet. Due not run electrical cords directly across wet pool deck due to electrical hazard. Unplugged during the inspection.
Daniel Osucha present during the inspection.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some sand/debris in corners of spa near steps. Keep floor clean. Vacuum as needed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Right step handrail loose. Tighten and secure.
#21 · Premises: pool and deck lighting provided at pools that operate at night −4
Ventilation not operable inside spa area. Large amount of condensation on the walls and pooling around the spa. Repair ventilation. Intent to suspend issued.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Cold water handle broken in women's locker room. Repair fixture.
Nov 7, 2024 6 demerits · 2 violations
Inspector comments: 13 - Contrasting color band on steps is not 2x2 tile. Original construction. If spa ever re-tiled, ensure 2x2 tile used. Not directly addressed in spa rules section.
Daniel Osucha present during the inspection.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some debris on spa floor. Staining on grout in some areas. Ensure cleaning in spa as needed.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Step handrail loose. Keep tight.
Feb 12, 2024 4 demerits · 2 violations
Inspector comments: Daniel Osucha present during the inspection.
Jets permit restriction verified at 180 gpm each.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Ladder handrail loose. Tighten.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Hot water >113 F. Maintain at 110 F or below.
Two soap dispensers broken in women's restroom. Repair/replace.
Nov 16, 2023 8 demerits · 3 violations
Inspector comments: Daniel Osucha present during the inspection.
#5 · Water quality: daily written records of water quality and test kit kept on site −4
Build-up in bottom of test kit tubes for test kit. Replace test kit. Will verify when return visit is made for the main pool. No ITS issued. Still given 30 days.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Step handrail loose. Tighten.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Floor drain in pump room missing drain cover near filter for spa. Replace floor drain cover. Fixtures shall be maintained and kept in good repair to eliminate hazard.
Mar 17, 2023 6 demerits · 2 violations
Inspector comments: Daniel Osucha present during the inspection.
Intent to Suspend issued for:
.2518 - repair drain line on filter. Leaking.
PDSC form indicates (2) CHK pumps installed. Provide updated PDSC form with (1) CHK-50 and (1) CMK-50 by permit issuance 2023. No flow difference in either pump.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Leak at drain line from filter. Repair leak. Intent to Suspend issued.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Floor wet in pump room due to leak from filter. Keep floor dry.
Bicarb stored in pump room. Store all chemicals in chemical storage room.
Nov 22, 2022 6 demerits · 2 violations
Inspector comments: Inspection completed with pool operator, Daniel Osucha and trainee Hannah Howard.
Drain covers (Aquastar WAV9WR) expire 4-11-2023.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed leak at filter multiport. Leak was not severe enough to require repair. Continue to monitor and repair leak if condition worsens. No intent to suspend issued.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Bicarb stored in pump room. Store in chemical storage room.
Feb 1, 2022 8 demerits · 3 violations
Inspector comments: Daniel Osucha present during the inspection. No signature due to covid restrictions.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Doors on to pool deck not self-closing, self-latching. Intent to Suspend taken under main pool - 530056 ID. Repair doors to self-close, self-latch.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Bicarb stored in pump room. Store in chemical storage room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One shower clip broken in family restroom. Keep fixtures in good repair.
Sink faucet handles with springs not running for full hand wash. Repair faucet handles to ensure proper handwashing can occur.
Oct 28, 2021 10 demerits · 3 violations
Inspector comments: 5 - Test kit tubes with black build-up. Recommend replacing test kit tubes.
Danial Osucha present during the inspection. No signature due to covid restrictions. Intent to Suspend issued for barrier and spa filter.
Motors replaced on jet pumps. Inspected July 2020 and December 2020.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Multiple doors not self-closing, self-latching or self-closing with audible alarm. Repair to self-close, self-latch or self-close with audible alarm. Intent to Suspend issued.
1. Men's and women's doors from locker rooms.
2. Multi-purpose room.
3. Office rooms 116 and 114.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Drain line cap leaking on filter. Repair leak on filter. Intent to Suspend issued.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Sink faucet handles with springs not running for full hand wash. Repair faucet handles to ensure proper handwashing can occur. One sink missing handle in the family restroom. Keep all fixtures in good repair.
Mar 3, 2021 0 demerits · 0 violations
Inspector comments: Daniel Osucha present during the inspection. No signature due to covid-19 restrictions.
Note - Observed some sand build up at the corners of the spa floor. Keep clean and maintain.
Automated chlorinator verified during inspection.
No violations noted during the inspection.
Inspection conducted by Katie R. and Aimee L.
No violations were recorded for this inspection.
Sep 17, 2020 0 demerits · 0 violations
Inspector comments: Daniel Osucha present during the inspection. No signature due to covid restrictions.
Main drains for jets due in May 2021. Equalizer line cover due in March 2021. Please note that the flow rating for the 6HP has changed with the new cover 6HPHAxxx. The new cover is only rated for 92 gpm. Max flow for your filtration pump is 170 gpm. The new equalizer cover must be capable of handling at least 170 gpm. Once covers are replaced, submit updated pdsc forms for both systems.
Note: Test tube for cyanuric acid beginning to cloud. Replace test kit. Cyanuric acid not used in pool.
Automated chlorinator verified during inspection.
No violations noted during inspection.
No violations were recorded for this inspection.
Jan 29, 2020 8 demerits · 3 violations
Inspector comments: Note: Verify sizing on main drains. Records indicate WAV9WRxxx on floor and P12xxx on walls.
Note: Chlorinator verified at time of inspection to detect flow.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Step handrail loose. Keep in good repair.
.2521 Install ladders per manufacturer instructions.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One return fitting missing moveable eyeball fitting. Keep all fittings in place.
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Bicarb stored in pump room. Store up off floor in chemical storage room.
.2534(4) Provide storage for pool chemicals in waterproof containers or store up off the floor.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Oct 7, 2019 8 demerits · 3 violations
Inspector comments: 5 - DPD-2 reagent expired. Replace reagent.
Intent to Suspend issued for door repair.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Step handrail loose. Keep tightened.
.2521 Install ladders per manufacturer instructions.
#16 · Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained −4
Door to spa does not self-close, self-latch. Barrier extends to perimeter around main pool. One door inoperable. Repair door to self-close, self-latch. Intent to Suspend issued.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Some mildew around shower fixtures in women's restroom. One sink with spring not operating properly on sink faucet handle. Keep all fixtures in good repair.
Mar 13, 2019 2 demerits · 1 violation
Inspector comments: Verified PDSC information.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Repeat non-compliance: Observed left handle for steps loose.
.2521 Install ladders per manufacturer instructions.
Nov 28, 2018 12 demerits · 4 violations
Inspector comments: 24 - Chlorinator not verified at time of inspection. Automatic chlorinator. Operator not present to verify. System must detect flow and turn off when no flow.
Note: Doors near pump room sticking. Doors shall self-close, self-latch. Doors are fire egress and shall both be operational.
Intent to Suspend issued for weir.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir sticking in skimmer. Operator indicated that they have replaced with spring loaded. Weir shall freely move. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail loose on steps. Keep in good repair.
.2521 Install ladders per manufacturer instructions.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
One return inlet with eyeball in backwards.
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One faucet handle leaking in women's locker room.
.2626(m) Keep restrooms and fixtures clean and in good repair.
Apr 4, 2018 10 demerits · 3 violations
Inspector comments: 6 - Observed discoloration on main drains on spa floor. Per Aquastar when drains are discolored, they require replacement. Replace within 30 days and will verify on return visit for ITS.
23 - General Comment - Chlorinator not verified during inspection. CPO not present.
Intent to Suspend issued for spa timer, weir and and skimmer basket.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir pulled out of skimmer when checking skimmer. Replace weir. Assure working propertly and not sticking. Intent to Suspend issued. Skimmer basket damaged. Replace. Intent to Suspend issued.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail loose at steps. Tighten and keep in good repair.
#14 · Pool maintenance: spa timer working properly −4
Spa timer sticking and exceeding 15 minutes. Maintain at 15 minutes or less. Intent to Suspend issued.
Nov 6, 2017 10 demerits · 3 violations
Inspector comments: Liquid feeder not verified during inspection. Operator not trained on how to verify.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some build-up on deck drains. Keep clean.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir not functioning properly. Still in place. Basket damaged. Replace basket.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Handrail loose at steps. Keep in good repair.
Apr 3, 2017 8 demerits · 2 violations
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Weir damaged and sticking. Replace weir so operational. Intent to Suspend issued.
Some eyeballs in returns backwards. Repair where needed.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some build-up on deck drains. Keep clean.
Nov 22, 2016 18 demerits · 6 violations
Inspector comments: Note: Chlorinator could not be verified during the inspection.
Intent to Suspend issued for spa timer.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some staining on wall tiles. Keep clean.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
One step handrail loose. Keep in good repair.
#14 · Pool maintenance: spa timer working properly −4
Spa timer running >15 minutes. Correct to 15 minutes or less. Intent to Suspend issued.
#17 · Premises: decks unobstructed, properly drained, free of trip hazards −4
Some build-up on deck drains. Keep clean and in good repair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Acid barrels stored in pump room. Move to approved chemical storage room.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
Holders for portable shower heads in women's locker room damaged. Repair.
Jan 20, 2015 16 demerits · 5 violations
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Build-up on tiles and some missing. Keep clean and repair.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Some inlets missing fittings. Replace.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter stuck. Repair.
#25 · Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure −2
Pump room floor wet.
#29 · Dressing and sanitary facilities: required fixtures provided, clean, and in good repair −2
One sink leaking. Repair. One hand dryer not operable. Repair.
Oct 21, 2014 14 demerits · 4 violations
Inspector comments: 29 - General Comment: One hand dryer in womne's not operating. Repair.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Some build-up on spa walls. Keep clean.
One tile missing on step. Replace.
#11 · Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair −2
Step handrails loose. Repair.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Some eyeballs missing from fittings. Replace.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Flow meter not operating. Keep operational.
Feb 5, 2014 16 demerits · 4 violations
Inspector comments: 29 - General Comment: Observed one hand dryer not operational. Keep in good repair.
#7 · Pool maintenance: pool walls and floor kept clean, free of debris and in good repair −4
Observed build-up on wall tiles and rust on grout around skimmer. Keep in good repair.
#8 · Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris −4
Observed build-up in skimmer. Keep clean.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed some jets/inlets missing eyeball fittings. Provide fittings.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck. Corrected during inspection.
Oct 7, 2013 14 demerits · 3 violations
#4 · Water quality: water temperature of heated pool −6
Observed water at 105.4 F. Corrected to 104 F.
#12 · Pool maintenance: inlets and other fittings in place and in good repair −4
Observed some inlet/jets missing fittings. Replace where needed.
#24 · Equipment room: approved pump, filter, and flow meter operating properly −4
Observed flow meter stuck. Keep operational.
Permits at this address
Other permits for this place
Same name, separate permit (for example a pool, kitchen or lunchroom). Each is scored on its own.
- 12demeritsMecklenburg Co Aquatic CenterYear-Round Swimming Pool · Oct 2013 – Feb 2026 · 25 inspections
- 14demeritsMecklenburg Co Aquatic Ctr ShallowYear-Round Swimming Pool · Oct 2013 – Feb 2026 · 25 inspections
Matched by street address. Each permit has its own grade and history.
Source: Mecklenburg County Public Health – Environmental Health public inspection portal (search for “MECKLENBURG CO AQUATIC CENTER” or State ID 2060550081). Inspection type (routine vs. follow-up) is not published in the county's data.